GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM All rights reserved.

Similar documents
Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

Bus Bar Protection Relay B-PRO 4000

FITNESS GB s Pilot Multi-Vendor Digital Substation - Architecture and Design Philosophy

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China

TFS 2100 Traveling Wave Fault Location System

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Reason RPV311. Technical Manual. Distributed Multifunction Fault Recorder

How smart can the grid really be?

Trends in Station Bus and Process Bus Communications Via the Several IEC Protocols. Schweitzer Engineering Laboratories, Inc.

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control

IDM DATA ACQUISITION SYSTEM

THE INTEGRATED TESTING SOLUTION

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

MMLG 01, 02, 03, 04 MMLB01

Digital Substation Overview of Technology, Industry

MiCOM Alstom P14N, P14D, P94V

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

SEL Real-Time Automation Controller (RTAC)

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

Substations go fully digital but stay compatible

TWFL - Travelling Wave Fault Location System

Substation Automation Products. Line differential protection RED670 Relion 670 series

Multilin P30 Phasor Data Concentrator

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

AGILE DIGITAL SUBSTATIONS 2.0 RELEASING THE POTENTIAL OF DIGITAL TECHNOLOGIES

Automation System Solutions

Power System Monitoring Recorder

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

SM100. On-Line Switchgear Condition Monitoring

SPECIAL REPORT FOR STUDY COMMITTEE B5 (Protection and Automation)

Power System Monitoring Recorder. Product Overview. 10 Year WARRANTY

Products Portfolio. Pole mounted Vacuum Recloser

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

FLEXIBLE SOLUTIONS FOR THE ENERGY INDUSTRY

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

Lecture 5 Substation Automation Systems. Course map

Power System Monitoring Recorder TESLA 3000

NERC PRC-002 Recording Solutions

SEL Time-Domain Link (TiDL ) Technology

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

ISIO 200. Binary Input/Output (I/O) terminal with IEC interface

Digital Substation Unrestricted Siemens AG 2017 siemens.com/digital-substation

Chapter 2 State Estimation and Visualization

Control and Protection System Win-TDC

TFS-2100E Travelling Wave Fault Locator System Description and Specification

The PowerLogic range. Gain energy insight and control

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Products for increased power system availability

PowerFactory Monitor PFM300

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

COMMUNICATION NETWORKS. FOX615/612 TEGO1 IEC GOOSE Proxy Gateway interface module.

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Electrical Integration with Smart Communication

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

Real-time visualization for detecting and solving power system challenges

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

extending the boundaries of technology evolution of proven technology FEATURES

FEEDBACK ON INSTALLED EXPERIENCE WITH FULLY-DIGITAL SUBSTATIONS

Transformer Protection Relay

Jim McGhee, Utility Market Manager, RuggedCom Inc.

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

Lecture 6 Substation Automation Systems

SCE WASAS Combined Disturbance Fault Recorder (DFR) and Phasor Measurement Unit (PMU) Specifications. Anthony Johnson

MiCOM Agile P345 & P348

Implementing the protection and control of future DC Grids

MiCOM P521. Fast Feeder Differential Protection

MINER-S Station Controller. Substation Automation

Power Systems Communications Implementation of IEC61850 in a Substation Environment

A low-cost, economical solution for distribution feeder protection

COLLABORATE TO WIN. 03/31/2017 Digital Substation Turning IEC61850 features into benefits. Peter Rietmann, Program Manager Digital Substation NA

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

MiCOM P521. Fast feeder differential protection

Content REF615 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Experience with a Digital Substation Pilot in North Ame rica

Designing a new IEC substation architecture

REALISATION OF AN INTELLIGENT AND CONTINUOUS PROCESS CONNECTION IN SUBSTATIONS

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

TR-2100 Multi - Function Recorder

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

DRTS 33. The new generation of advanced three phase relay test set

MODULYS GP Unique, fully modular and redundant solution Green Power 2.0 range from 25 to 600 kva/kw

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Networks TN, TT, IT networks 3 and 4-phase networks Up to 4 single-phase networks

THE NEW GENERATION OF ADVANCED TEST EQUIPMENTS FOR RELAYS, ENERGY METERS, TRANSDUCERS AND POWER QUALITY METERS.

CMC 256plus. The High Precision Relay Test Set and Universal Calibrator

ISIO 200. Binary Input/Output (I/O) Terminal with IEC GOOSE Interface

OMICRON CMC 356. The Universal Relay Test Set and Commissioning Tool

Amsterdam 27 September 2017 David MacDonald

Transcription:

GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM 2014. All rights reserved.

GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM 2014. All rights reserved.

MEASUREMENT PRODUCT SOLUTIONS Reason RPV311 Digital fault recorder with fault location and PMU GRID/PRSHT/RPV311/EN/1.2014/GBR/1893 ALSTOM 2014. All rights reserved. The Reason RPV311 is the most powerful electrical system monitoring, recording and analysis device. Phasor measurement, power quality, precision fault location and process bus options deliver the highest integration capabilities for digital substation and widearea schemes (WAMS). CUSTOMER BENEFITS Flexible and scalable: excels in even the most demanding applications Suitable for both distributed and centralised architectures Digital substation ready Measures both AC and DC analogue inputs Precision fault location with TWFL A multifunction digital recorder solution that allows distributed or centralised installation The solution is composed of the RPV processing unit and remote acquisition units RA331, RA332 and/or RA333. It acquires monitors and records electrical quantities in applications where high performance, modularity, flexibility and high channels counts are demanded. The RPV is the most complete solution on the market for digital substation applications, thanks to its powerful suite of integrated functions, coupled with the scalability of the hardware. FUNCTIONALITY AVAILABLE Fault recorder Disturbance recorder Continuous recorder (waveform and RMS) Phasor Measurement Unit (PMU) Steady-state recorder Power Quality Recorder Sequence of events recorder Grid-SAS-L3-RPV311-3040-2014_01-EN. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. Alstom contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper. Real time monitor Travelling wave-based fault locator (TWFL) Process bus (IEC61850-9-2LE) recorder DC to 3 khz measurement IEC61850-8-1 support

RPV architecture The RPV architecture is comprised of separate processing and measurement acquisition units, which communicate using dedicated fibre-optic links of up to 2km, allowing flexible installation and mounting. It is possible to install all the units in one panel, in a centralised solution, or it is also possible to install the acquisition units in the protection panels, communicating to one central processing unit. In the distributed architecture the electrical cabling is reduced, since it is not necessary to take all signals to one concentrated DFR panel. The RPV processing unit can be connected to either up to 8 RA331 Remote Acquisition Units, or to up to 4 RA332, or to up to 4 RA333, or a combination of them. Each RA331 can have up to 8 analogue inputs and 32 digital inputs, each RA332 can have up to 16 analogue inputs and 32 digital inputs, and each RA333 can have, in addition to the 3 default voltage high speed travelling-wave acquisition inputs, up to 8 analogue inputs and 16 digital inputs. The RPV processing unit can also accept sample data inputs of analogue signals and digital inputs from IEC61850-9-2 merging units. The RPV can be connected to a combination of inputs from RA33x acquisition units and merging units. Communications The RPV is fitted with 2 network Ethernet ports for communication to two separate networks or for redundant communications. Both copper and fibre (optional) ports are available. A third network Ethernet port for IEC61850-9- 2LE communications is available. Modbus, DNP3 and IEC 61850-8-1 protocols are implemented for integration with SCADA and DCS systems. An RS232C serial port is included for Modem communications. Signalling outputs Available are 4 dry contact relays for remote signalling one of which is used by the device self-monitoring watchdog. The other 3 outputs are user configurable. Local interface The local interface consists of 4 buttons used to navigate the LCD display to show the unit status, monitor the measurement values, identify which record files have been generated, etc. Remote interface There is an integrated web-based graphical interface for monitoring and configuration of the RPV units. The web-based interface allows the configuration of all features of the RPV311 either directly connected or via a remote Ethernet link. A standalone version of the configuration system is also available as part of the supplied RPV software tools to allow the configuration to be developed offline without the need to be connected to a physical unit. The configuration produced offline can be stored and then downloaded to multiple units using the web-based interface. The monitoring interface allows measurements being generated by the RPV311 to be viewed without any other monitoring software needing to be available. This is particularly useful during commissioning when the RPV311 will probably be the first system commissioned. The total number of input channels available in the scheme is 64 analogue inputs (current, voltage and DC transducer signals), 256 digital inputs and in addition up to 256 binary inputs related to GOOSE messages. The analogue inputs are sampled at 256 samples per cycle and have a frequency response of DC to 3 khz. The RPV is fitted with a 50GB solid state memory drive (SSD), and is time synchronised by connection to an external IRIG-B reference or using SNTP over Ethernet. Web-monitoring example: Trending of analogue quantities CAPTION_WHITE_lore_ipsum_(Optional)

MEASUREMENT PRODUCT SOLUTIONS RPV311 Process bus applications with IEC 61850-9-2 The RPV is ready for sampled value applications according to IEC 61850-9- 2LE. The distributed architecture of the scheme, whereby the RPV central unit subscribes to data from local or remote acquisition units means that the user can specify the MU320 as the chosen acquisition unit, or can subscribe directly to other merging units or digital instrument transformers which are publishers of sampled value data streams. Interoperability is assured with Alstom s own MU320 and MU Agile merging units, the COSI range of digital instrument transformers, plus third party devices compliant to the standard. Conventional instrument transformers may be hardwired to RA33x or MU320 acquisition units, at the same time as other measurements are obtained from digital instrument transformers, allowing a mix of transformer technologies within a scheme. Such flexibility permits standardisation of the DFR solution across substations employing different primary technology generations; it prepares for future substation extensions, and allows a migration path to the full digital substation. The MU320 merging unit used to digitise the output of conventional CT and VTs has the advantage that it performs both an analogue merging unit function and binary I/O marshalling. It may be termed an integrated merging unit, making it particularly cost-effective in applications requiring bay measurements and switchgear control and monitoring in a single intelligent device. As per the RA33x, the MU320 may be deployed in a distributed scheme whereby it performs the plant interfacing in yard kiosks close to the switchgear. RA33x technology and DC applications The RA33x acquisition units use intelligent shunt measurement with optical isolation between the external world and the internal electronics. This extends Alstom s leadership in digital instrument transformer (DIT) technology, such that the measurement circuit becomes a DIT in the box. The acquisition circuit is thus transformerless, with no core to magnetise, no core to saturate, and hence negligible error. Such greater accuracy is important in high-precision measurement and phasor applications, whilst also permitting DC quantities to be measured. The analogue acquisition in the scheme produces a more accurate representation of DC and harmonic components in AC applications, also supporting full DC application too. References exist for Reason DFR solutions deployed in HVDC installations. The solution right from simple applications up to the full digital substation.

PHASOR MEASUREMENT UNIT (PMU) The RPV is able to construct accurate synchrophasor data based on the incoming measurements from the scheme s acquisition units. This makes the solution highly scalable in terms of the number of analogue channels and phasors available. The scalability from small to large substations is achieved by means of additional acquisition units to accommodate the number of feeders, which is more cost-optimised than the addition of multiple discrete PMUs. Further advantages are achieved in that the Phasor Data Concentrator (PDC) only needs to connect to a single point in the substation (the RPV, which also acts as the Substation Phasor Data Concentrator - spdc) rather than requiring a connection to multiple discrete devices. Integrating the PMU function is an ideal way to make use of the measurement accuracy, the precision time distribution, and the communication architecture already provided within our DFR scheme, negating the requirement to install a duplicate architecture solely for PMU purposes. The RPV synchrophasor measurement and publishing are carried out according to IEEE C37.118, the standard for synchrophasors in power systems. The reported values are freely selectable by the user and include voltages and currents, positive and negative sequences for voltage and current circuits, frequency, scalar quantities such as DC signals, RMS values, voltage and current imbalances and THD, and the status of any digital channel. The RPV has been tested by NIST. The RPV (PMU) is designed to monitor entire substations and power plants. In process bus architectures, the RPV acts as a smart protocol conversion from IEC 61850-9-2 to IEEE C37.118. RECORDERS The disturbance and fault (waveform) recorders are enabled by using triggers which can be generated from analogue, digital and virtual (GOOSE) inputs. The continuous recorder generates records with 16 points-per-cycle sampling rate (waveform) and 1 pointper-cycle sampling rate (magnitude, phase, RMS, frequency, positive and negative sequence, imbalance, THD, and apparent, active and reactive power). The continuous recorders are very useful tools for monitoring long term oscillations and wide area events. DFR topology example CAPTION_WHITE_lore_ipsum_(Optional)

MEASUREMENT PRODUCT SOLUTIONS RPV311 TRAVELLING WAVE FAULT LOCATION Travelling wave (TW) fault location (TWFL) is a particularly efficient way to define precisely where a fault occurred on a transmission line, to locate it to the vicinity of a particular tower, or span length of conductors. Such accuracy to within a few hundreds of metres of the actual fault point is not possible to achieve with traditional impedance-based fault location, which conversely introduces measurement errors equivalent to a few percentage points of the full line length. The MHz sampling rate of the Reason unit, and intelligent processing allow dedicated high speed algorithms to be implemented which accurately monitor the propagation of the disturbance along the monitored circuit, securing the high accuracy result The highly reliable fault location system uses an innovative and patented combination of travelling wave and fault detection algorithms. All the triggers normally associated with Digital Fault Recorders (DFRs) can also be used as an external trigger to record the travelling wave associated with the event. Travelling wave fault location: Summary view The Master station software permits users to display the fault location on a Google-earth map, onto which the GPS coordinates of substations, towers and conductors have been plotted. Maintenance crews are thus directed to the exact location of the fault, without the need to resort to vehicular, helicopter or footpatrols to find the exact location. Alstom is the leader in the field of travelling-wave fault location, as our techniques work equally-well for short-circuits and high impedance faults. The latter will typically confuse other vendor s TWFL solutions as they rely on a change of state to trigger and will be unable to declare a calculation result, or will declare an inaccurate distance. The technique does not rely on a trigger, but correlates the trip command with the continuous disturbance record data, such that a correct result will be obtained. The TWFL can be compensated for the effects of conductor sag with varying ambient temperature and load current heating effects. This trigger is generated after some preset limits are exceeded for magnitude, angle, frequency deviation, positive sequence, negative sequence, imbalance, harmonic distortion, and power. It is possible to monitor up to 4 circuits with each RPV by using the RA333 Remote Acquisition Units. Precision is not affected by line resistance, mutual coupling effects (parallel lines), load, or compensation circuits (capacitor banks). To monitor a transmission line, RPV systems are installed at each end of the line. The travelling wave records are captured in both units and are automatically transmitted to the Master station for the fault location to be calculated. Travelling wave fault location: Map view Precision fault location to direct maintenance crews

RPV Software Tools The RPV is supplied with a suite of PC software tools to manage the product and the records produced. The Scanner searches for and uploads the record files from the connected RPV units in a single or multiple substations and stores them in an organised way for later analysis. The scan for new records is run periodically at an adjustable time period. The configuration tool is a version of the web based graphical tool which can be used offline to generate the product configuration required which can then be downloaded to multiple RPV products. The TW Fault Locator is a tool that uses the records of the traveling wave front signal from the RPV units at both ends of a transmission line to locate a fault on the line. The software can output the fault location in a format which allows mapping systems such as Google Earth to display the location. RPV Manager The RPV manager software allows the management of a system of multiple RPV units installed in multiple substations. It manages the communication links and reports their status and periodically scans the network for record files not previously uploaded. The software can also receive record files automatically sent by the RPV units if enabled or as required for TW fault location. The software can also be used to backup and upload the configuration files for all RPV units in the system. Analise The powerful analise package can merge multiple waveform files from different devices, time align them, and display as a single record for side-by-side signal analysis. This greatly assists in post-fault or post-disturbance analysis, where the types of IED and the availability of timesynchronising between substations may vary. In addition, impedance based fault location and harmonic analysis calculations can be performed. The graphical analysis can be output in various picture formats and the related data can be exported in a form readable by Microsoft Excel. Analise CAPTION_WHITE_lore_ipsum_(Optional) Web monitoring: Vectors

MEASUREMENT PRODUCT SOLUTIONS RPV311 Ordering Options Power quality Modbus interface GOOSE message detection Phasor measurement unit (PMU) Continuous recorder Trigger disturbance recorder Sequence of events recorder (SOE) Fault recorder IEC61850-9-2LE inputs Travelling wave fault location (TWFL) History of recorders Alstom's Reason recorders have a long history being originally designed in 1996 and having been continuously developed since. Features have been added in response to market requirements as the need for more detailed monitoring of power systems has increased. RPV311 Rear view The latest generation of the Reason RPV311 has been developed to meet current and future recording requirements and for installation in the latest types of monitoring schemes. With support for IEC61850-8-1, IEC61850-9-2LE and synchrophasors (IEEE C37.118) the RPV311 is suited to Smart Grid and Digital substation applications and wide area monitoring. RA332 Rear view CAPTION_WHITE_lore_ipsum_(Optional)

MEASUREMENT PRODUCT SOLUTIONS RPV311 Dimensions The RPV311 central unit is presented as a 19" rack (80TE) width, 3U height standard device. The RA33x acquisition units are presented in a compact-depth case, such that mounting in panels or kiosks with constrained depth is made simple. Mounting plates (5U) are available for mounting the RA33x in a 19" rack (80TE). The dimensions of the RA332 are shown below. Refurbishment projects Solutions are available for using the RPV311 and RA33x to replace certain existing centralised DFR products, with the existing wiring being re-used. GRID/PRSHT/RPV311/EN/1.2014/GBR/1893 ALSTOM 2014. All rights reserved. Picture caption Grid-SAS-L3-RPV311-3040-2014_01-EN. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. Alstom contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper. For more information please contact Alstom Grid: Alstom Grid Worldwide Contact Centre www.alstom.com/grid/contactcentre/ Phone: +44 (0) 1785 250 070 Visit us online: www.alstom.com