Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications

Similar documents
Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications

Structured Cabling Design for Large IT/Service Provider Data Centers

Fiber Backbone Cabling in Buildings

Corning Distance and Link-Loss Budgets for the Cisco 40GbE BiDi Transceiver

1 of 5 12/31/2008 8:41 AM

Fiber backbone cabling in buildings

ANSI/TIA/EIA-568-B Cabling Standard

Optical Fiber Premises Standards News & Trends

Corning Optical Network Evolution (ONE ) SD-LAN Applications Guide

The Green Advantage of 10G Optical Fiber

Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"

Anixter Standards Reference Guide

Optical Fiber for Today s Premises Applications

Optical Fiber Networks: Industry. and New Options for Networks

The Riser as a Contract Document. Peter Sharp, RCDD

Peter Sharp RCDD IBI Group

The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures. Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress

Pretium EDGE HD Solutions A LANscape Pretium Solutions Product

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3)

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

Plug & Play Universal Low-Loss Systems A LANscape Pretium Solutions Product

How You Can Optimize Passive Optical LAN Through Structured Cabling

Data Center Design and the ANSI/TIA-942 Standard

Enterprise Network Design

STANDARDS REFERENCE GUIDE ANIXTER anixter.com. Products. Technology. Services. Delivered Globally.

Copper Cabling Standards

Standards Update. by Paul Kish NORDX/CDT

Telecommunications Structured Cabling Systems

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers

ANSI/TIA/EIA-568-B Cabling Standard

Cabling a Data Center to TIA-942 Standard

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

Hands-On Fiber Optic Designer

Application Note. Data Center Standards and Layouts

Connectivity Solutions Utilizing Base-8 Structured Cabling

Cabling Infrastructure

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee

Anaerobic-Cure Connectors

Enterprise Network Design

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

EDGE Solutions Trunk Cable, SMF-28 Ultra OS2, MTP to MTP, 12 fibres

EDGE Solutions Trunk Cable, OM4, Low- Loss, MTP to MTP, 12 fibres

The six major components of a structured wiring system are:

Anticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards

FTTE Revisited for New Technologies

Pretium EDGE Solutions Trunk Cable, OM3, Low-Loss, MTP to MTP, 24 fibres

Chapter 10: Planning and Cabling Networks

Adventum Plenum Rated Indoor/Outdoor Optical Cable

Structured Cabling Guidelines For The State Of Oregon

Communication

ISO/IEC 11801: (E)

Plug & Play Universal Trunks

Structured Cabling System (SCS) for IT Network and Intelligent Building/ Building Automation Systems

LTK-400 Series Optical Sources, Meters and Kits Without Data Storage Capabilities

Pretium EDGE Solutions Trunk Cable, OM4, Low-Loss, MTP to MTP, 24 fibres

Distributed ConvergeIT Systems. Lee Funnell EMEA Technical Manager

DATA CENTER CABLING DESIGN FUNDAMENTALS

AMP NETCONNECT XG FIBER SYSTEM

Conflicts in Data Center Fiber Structured Cabling Standards

FuseLite Single-Fiber Splice-On Connectors

Plug & Play AnyLAN Systems A LANscape Solutions Product

Increase Network Reliability and Reduce Costs with Cabling Management Software and Services Designed Especially for SYSTIMAX Installations

UniCam High-Performance Connectors, Multimode and Single-Mode

(Data Center Networks & Cloud Computing Security)

Defining the Next Generation of the IP Connected Enterprise: A Practitioner s Guide to Best Practices Proudly presented by: Andy Jimenez ANIXTER INC.

EDGE Solutions Hybrid Trunk, OM4, Low- Loss, MTP to LC Duplex Uniboot, 24 fibres

Are Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk?

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant

DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005

Testing Network Infrastructure

CLOSET CONNECTOR HOUSING

Corrigendum 1 to Amendment 2 1 ISO/IEC ISO/IEC (second edition 2002) Information technology Generic cabling for customer premises

Implementation considerations for cabling supporting remote powering

Telecommunications Business Overview. Clark Kinlin President & Chief Executive Officer Corning Cable Systems

f) Telecommunications Equipment Rooms

Data Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems

Building Buildings Better

Plug & Play Universal Systems

Cabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India

Atras Network Communications

Structured Cabling Design for Large IT/Service Provider Data Centres. Liang Dong Yuan, Technical Sales manager, CDCE

Data center cabling design fundamentals

Laying the groundwork for a new level of Power over Ethernet

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett

Tarleton State University. Specifications

THE NEW OPTICAL FIBRE CATEGORIES What do they promise?

Using Low DMD, Laser Optimized Multimode Fiber to Expand 10-Gigabit Network Design Options

Wall-Mountable Connector Housings (WCH)

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

Corning Optical Network Evolution (ONE ) SD-LAN Ordering Guide

Leveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions

Universal connectivity grid design guide

Trends in Data Centre

Bend, Bandwidth or Both: enterprise networks. Ravi Yekula

Bonding and grounding NETCONNECT copper cabling systems

The Threaded Case Study

Alcatel 1671 Service Connect

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT

Transcription:

Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications Author: David Kozischek Marketing Manager, Data Center Applications Corning Optical Communications Systems engineers at Corning are routinely asked these two questions: 1. How do I determine the type of fiber needed for my campus backbone? 2. How do I determine the number of fibers needed for my campus backbone? Both of these questions require some analysis to help the network designer make the best decision. This article provides design guidance to help put analysis behind the decision-making process. This paper discusses the following: Fiber types used in the campus backbone Designing the cabling infrastructure Determining the fiber type and fiber mix for 10 Gigabit Ethernet Determining the total fiber counts Conclusion Fiber Types Used in the Campus Backbone There are many factors that go into the determination of which fiber type to use in a campus backbone. Two of the main factors are the type of media that is needed along with the distance of the cable run. A single fiber type may not be satisfactory for all applications and multiple fiber types may be needed. Before Gigabit Ethernet, determining fiber types for the campus backbone was an easy decision. Standard 62.5/125-micron multimode fiber was generally used for any application up to 2000 meters, and single-mode fiber was used for anything else. With the introduction of 10 Gigabit Ethernet, these rules have changed for multimode fiber. Laser-optimized 50-micron multimode fiber was introduced to offer increased performance for 10 Gigabit Ethernet, and the fiber performance was included in TIA/EIA-568revB. Section C.3 - Table 6 of the TIA-568.0-D Standard shows the maximum supportable distances for multimode optical fiber applications and Table 7 has the maximum supportable distances for single-mode applications. Corning Optical Communications White Paper LAN-2131-AEN Page 1

Designing the Infrastructure Before attempting to determine the fiber types, we need to determine the cabling topology for the campus. do this, let us create a campus backbone model using our campus illustrated in Figure 1. Let us assume the following: 1. All buildings contain multiple floors with a minimum of one telecommunications room (TR) acting as a horizontal cross-connect/distributor A. 2. All distances are in meters. This includes the length from the entrance facility (EF) at each building back to the main cross-connect (MC)/distributor C. 3. All network analysis is based on a Gigabit Ethernet building-to-building fiber optic backbone and a 10G Ethernet fiber backbone. The design of the cabling topology can be separated into five smaller steps to help the network designer make the best choice: 1. Consult the TIA-758-B and 568.0-D for design topologies. 2. Determine the location of the main cross-connect (MC)/distributor C, entrance facilities intermediate cross-connects ()/distributor B, and horizontal cross-connects/distributor A. 3. Determine the fiber distances needed for each fiber optic cable run. 4. Consult TIA-568.0-D for the maximum supportable distances for single-mode and multimode fiber applications to determine the appropriate fiber type. 5. Determine fiber counts needed. Let s look at each of these steps. 1. Consult the TIA/EIA-758-B and TIA-568.0-D standards The TIA-758-B standard gives design rules for cabling a customer-owned outside plant telecommunications infrastructure, and TIA-568.0-D for generic telecommunications cable for customer premises. This includes: It is recommended that the backbone cable be designed in a star topology. This is the most advantageous backbone design because it provides flexibility and the opportunity for centralized administration and management. In a star topology, there shall be no more than two levels of cross-connects in the backbone cabling. Connections between any two horizontal cross-connects (HC)/distributor A shall pass through three or fewer cross-connects. Large campuses should be designed using a hierarchical star configuration. This allows selected s/dbs to serve a number of buildings rather than having all of the buildings connecting directly to the MC/DC. Redundancy/diversity should be provided for continuity of service and security. Sometimes a star topology is not always feasible as the distances between buildings may exceed the allowable cable lengths. Corning Optical Communications White Paper LAN-2131-AEN Page 2

Subsystem 3 Subsystem 2 Subsystem 1 DB DC DB Subsystem 3 Subsystem 2 EO EO EO EO EO EO EO Subsystem 2 DC Subsystem 1 EO DB Legend Equipment outlet Distributor A Distributor B DC Distributor C Optional cabling Optional consolidation point Subsystem 1 EO EO EO Source: ANSI/TIA-568 2. Determine the location of the MC/DC, /DB, and HC/ Before determining the location of the MC/DC, s/dbs, and HCs/s, let s define the function of each. The MC/DC is the central connection facility in a star topology. The /DB is an optional intermediate cross-connection between first level (subsystem 3) and second level backbone (subsystem 2) cabling. The HC/ is the optional cross-connect that is cabled between the equipment outlet (EO) and distributor B or distributor C. In the campus model, assume each TR will act as the HC/ and connects to the building /DB. Next, the s/dbs connect back to the MC/DC in a physical star topology. The key decision is how to determine the location of the MC/DC. The location of the MC/ DC can be dictated by where most of the servers, switches, and routers are housed. If a certain building is already chosen based on these criteria, then all length calculations would be from that point. If any of the buildings can act as the MC/DC, then you need to determine which building is centrally located to minimize cable lengths. In our sample campus design, selecting the admin financial building as the MC/DC, yields a practical solution since it is centrally located on the campus. In our example, there is only one path between the MC/DB and each building entrance. If pathway redundancy is needed, multiple divergent routes and entrances facility diversity for each building will be needed. The cable routes and distances are shown in Figure 1. Campus Network Model Physical Cable pology Figure 1 Handhole Conduit Note: Drawing not to scale Admin Fin 230 m 210 m Physical Architecture MC Corning Optical Communications White Paper LAN-2131-AEN Page 3

3. Determine the fiber lengths Though the cable is deployed as a physical star, other logical topologies can be considered such as ring and mesh network. These logical topologies can be achieved through the use of cross-connects in the MC/DC. In our scenario, we want to create a logical mesh network on a physical star. In a logical mesh architecture, all switches will be connected together to create logical redundancy. See Figure 2. 210 m Admin Fin MC Admin Fin 230 m Figure 2 Physical Architecture Logical Architecture get a better understanding of the fiber distances, it is a good idea to construct a matrix that defines the fiber distance between any two buildings in the backbone. Remember that the admin financial building is the MC/DC for our campus, so all network connections flow through the MC/ DC. Table 2 illustrates this concept for our campus model. In Table 1, all of the lengths highlighted in green are the lengths from our MC/DC in admin financial to each of the buildings that we want to network. The lengths that are highlighted in white are the lengths for each building that we want to mesh via a cross-connect in the MC/DC. Ch Length Calculator (Meters) : : 210 190 190 230 210 400 400 440 190 400 380 420 190 400 380 420 230 440 420 420 Table 1: Fiber Distance Matrix 4. Choose the fiber type Based on the cable routes chosen for our campus model, the next step is to determine the fiber types based off of the maximum supportable distances for the media dependent protocol that we want to use. Since we are concentrating on the campus backbone (building-to-building links) and 1 Gigabit and 10 Gigabit Ethernet technologies, we need to look at length restrictions based on fiber type. These maximum supportable distances can be found in TIA 568.0-D. In our example, we are going to be looking at a 10GBASE-S application. This comparison is shown in Table 2. By knowing the maximum supportable distances and the maximum channel lengths of our campus, we can choose the correct fiber type. Corning Optical Communications White Paper LAN-2131-AEN Page 4

Fiber Type Versus Distances (Meters) OM1 OM2 OM3 OM4 1 G 300 600 1,100 1,100 10 G 33 82 300 400 Table 2: 1G and 10G Ethernet Distances The 1 Gigabit and 10 Gigabit Ethernet distances shown in Table 2 are a function of the fiber core size and the associated effective modal bandwidth (EMB). Looking at Table 3, there are some questions that you can ask yourself. Though 62.5-micron fiber has been used in the past in campus backbones, is it worth switching over to 50 micron? Also, what should the fiber mix of multimode to single-mode be? answer these questions, we need to apply our logical mesh networking scenario to the physical star topology. analyze this network you need to look at how many fibers and what type of fibers (multimode and single-mode) are needed in operating the network at 1G and 10G. This will vary based on the type of fiber used and the total distance required to support the logical mesh topology. This is shown in Table 3. Based on Table 2, any links over 400 meters will need to have single-mode fiber to support the 10 GigE backbone. Though all the point-to-point links are under 400 meters, some of the cross-connected links are greater than 400 meters. Note that the fiber mix (multimode vs. single-mode) changes based on the type of fiber we choose. In this example, the recommended fiber mix would be OM4+. The reason for this is to maximize the number of links we can operate over lower cost multimode electronics. 5. Determine fiber counts In our campus model, an electronic redundant point-to-point logical mesh topology is implemented. This architecture uses redundant electronics in all buildings to reduce single points of failure. In this example, the campus backbone is sized for 1 Gigabit and 10 Gigabit Ethernet. Based on the results shown in Table 3, a mix of OM4+ was determined to be the best choice. But how was the fiber count calculated? Fiber Backbone Optimizer for 1 GigE and 10 GigE Fiber Count Comparison (pology and Fiber Type) MC Fiber Type 62.5 µm Core OM1 50 µm Core OM2 50 µm Core OM3 50 µm Core OM4 tal Fiber Counts Campus Backbone-Distributed Rec. Fiber Count This is accomplished by referring back to Table 1 for the building-to-building link lengths and comparing the fiber type to the length restrictions for 1 GigE and 10 GigE in Table 2. As stated above, any links over 400 meters will need to have single-mode fiber to support the 10 GigE backbone and anything below 400 meters can be supported by OM4. Table 3: 1G and 10G Ethernet Distances Corning Optical Communications White Paper LAN-2131-AEN Page 5

The last step is to determine the final fiber counts for each cable. Table 4 gave us the minimum fiber counts to migrate the backbone 10 GigE, but what about other applications that might run across the network? Applications such as security video, card readers, video conferencing, and control systems are applications that require additional fibers. Unless all applications are going to operate over an IP network, you will also need to add spare fibers in the cables. Spare fiber can run anywhere from 25 percent to up to 100 percent in a campus design. In this campus model, a 50 percent spare rule is used. The overall breakdown is shown in Table 4. Campus Backbone-Distributed tal Fiber Counts MC GigE Fiber Count Additional Fibers 10 GigE Fibers Spare Fibers tal Fibers Recommended Count OM4 12 4 14 2 42 6 12 4 14 2 42 6 12 4 14 2 42 6 4 12 10 6 30 18 Table 4 With this in mind, the following fiber counts were recommended: Minimum: 16 multimode OM4 for 1 GigE Minimum: 12 multimode OM4 + 4 single-mode for three 10G links and 4 OM4 + 12 single-mode for one 10G link Minimum + spare %: 42 multimode OM4 and 6 single-mode fibers for three links and 30 multimode and 18 single-mode for one link Cable to order based on common stocked: (3) 48 multimode OM4 and 12 single-mode cables and (1) 36 multimode and 24 single-mode cable Conclusion In summary, a few key points can be drawn from this analysis to help make the best decision when determining fiber types and fiber counts for a campus network. 1. Use the standards. They were created to protect the end user. 2. Do some analysis. Understand the network applications and possible traffic growth. 3. Understand the physical topology and the logical topology. 4. Examine where you can save money: MC selection, electronics choice, cable routing. 5. For distances less than 400 meters, a laser-optimized (OM4) multimode fiber is the best solution. 6. For distances greater than 400 meters, single-mode fiber is the best solution. Corning Optical Communications White Paper LAN-2131-AEN Page 6

Are You Corning Connected? www.corning.com/wireless-networks Corning Optical Communications LLC PO Box 489 Hickory, NC 28603-0489 USA 800-743-2675 FAX: 828-325-5060 International: +1-828-901-5000 www.corning.com/opcomm Corning Optical Communications reserves the right to improve, enhance, and modify the features and specifications of Corning Optical Communications products without prior notification. A complete listing of the trademarks of Corning Optical Communications is available at www.corning.com/opcomm/ trademarks. All other trademarks are the properties of their respective owners. Corning Optical Communications is ISO 9001 certified. 2017 Corning Optical Communications. All rights reserved. LAN-2131-AEN / February 2017