XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

Similar documents
XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New)

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

MRT1 Test Unit. Manual MRT1 (Revision A)

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

High-Tech Range. MRG2- Generator-mains monitor/vector surge Relay. C&S Protection & Control Ltd.

MRG2 - Generator mains monitor / vector surge relay

XRN2 Mains decoupling relay

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Contact protection relay

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

02/11/2015

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

02/11/2015

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

STEP-PS/1AC/24DC/1.75

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

QUINT-BUFFER/24DC/24DC/40

Electronic timer CT-ERS.21

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Electronic timer CT-ARS.11

MRP2-S3 Apparent Power Relay. Manual MRP2-S3 (Revision A)

Earth-fault Relay SPAJ 110 C. Product Guide

08/07/2015

Three-phase monitoring relay

TRIO-DIODE/12-24DC/2X10/1X20

Electronic timer CT-AHD.22

Arc protection relay. Features Three-phase overcurrent function. Application

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

02/11/2015

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Electronic timer CT-ERD.12

PHOENIX CONTACT - 01/2007

MINI-PS AC/10-15DC/8

RM4JA01F current measurement relay RM4-J - range ma V AC

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Siprotec 7ST61 / 7ST63

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Zelio Control-modular measurement and control relays 1

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

PHOENIX CONTACT - 07/2006

Installation / Control Technique

RM4JA32MW current measurement relay RM4-J - range A V AC DC

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

MINI MCR-SL-UI-REL(-SP)

Messaging module CP-C MM

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Feeder protection relay SPAA 121 C. Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

Power supply CP-C 24/5.0

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

MINI MCR-SL-PT100-UI(-SP)(-NC)

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

RM4TR31 three-phase network control relay RM4-T - range V

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Redundancy unit CP-A RU

SIMOCODE 3UF Motor Management and Control Devices

MRP2 - Directional Power Relay. Manual MRP2 (Revision B)

RM4JA31M current measurement relay RM4-J - range ma V AC

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Bulletin 817 Thermistor Protection Relay

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

QUINT-PS/ 1AC/24DC/ 5

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH)

QUINT-PS-3x AC/24DC/10

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

RM4TA32 three-phase network control relay RM4-T - range V

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

Binary output and supervision 520CSD01 Data sheet

Transcription:

XG2 Generator-/Mains Monitor Manual XG2 (Revision A)

Woodward Manual XG2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken. Woodward 1994-2008 2 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward Contents 1. Applications and features... 4 2. Design... 5 3. Function... 7 4. Operation and settings... 12 4.1 Setting of DIP-switches... 13 4.2 Setting of tripping values... 14 4.3 Communication via serial interface adapter XRS1... 15 5. Relay case and technical data... 16 5.1 Relay case... 16 5.2 Technical Data... 17 DOK-TD-XG2 Rev.A 3

Woodward Manual XG2 GB 1. Applications and features Vector surge relay XG2 of the PROFESSIONAL LINE pro-vides reliable protection for generators in parallel operation with the mains, by switching off very quickly in case of mains failure. Supervision of the phase sequence is also possible. When compared to conventional protection equipment all relays of the PROFESSIONAL LINE reflect the superiority of digital protection techniques with the following features: High measuring accuracy by digital data processing Fault indication via LEDs Extremely wide operating ranges of the supply volt-age by universal wide range power supply Very fine graded wide setting ranges Data exchange with process management system by serial interface adapter XRS1 which can be retrofitted RMS measurement Extremely short response time Compact design due to SMD-technology In addition to this relay XG2 has the following special features: Supervision of the phase sequence Switching over from 1-phase measurement to 3-phase measurement 4 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward 2. Design Figure 2.1: Connection two-wire system Figure 2.2: Connection three--wire system Δ Figure 2.3: Connection four-wire system Y/Δ DOK-TD-XG2 Rev.A 5

Woodward Manual XG2 GB Analog inputs The analog voltage input signals are connected to the protection device via terminals L1-L3 and N. Auxiliary voltage supply Unit XG2 can be supplied directly from the measuring quantity itself or by a secured auxiliary supply. Therefore a DC or AC voltage must be used. Unit XG2 has an integrated wide range power supply. Voltages in the range from 19-55 V DC can be applied at connection terminals A1 (L-) and A2 (L+). Terminals A1/A3 are to be used for voltages from 50-750 V DC or from 36-520 V AC. Contact positions Figure 2.4: Contact positions of the output relays 6 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward 3. Function The vector surge supervision protects synchronous generators in mains parallel operation due to very fast de-coupling in case of mains failure. Very dangerous are mains auto reclosing for synchronous generators. The mains voltage returning after 300 ms can hit the generator in asynchronous mode. The same very fast de-coupling is also necessary in case of transient mains failures. Generally there are two different applications: a) Only mains parallel operation no single operation. In this application the vector surge supervision protects the generator by tripping the generator circuit breaker in case of mains failure. b) Mains parallel operation and single operation. For this application the vector surge supervision trips the mains circuit breaker. Here it is insured that the gen.-set is not blocked when it is required as the emergency set. A very fast decoupling in case of mains failures for synchronous generators is known as very difficult. Volt-age supervision units cannot be used because the synchronous alternator as well as the consumer impedance support the decreasing voltage. The voltage reaches the threshold of voltage supervision unit because of this reason after a couple of 100 msec. and therefore a safe detection of auto reclosing in the mains is not possible with single-voltage supervision units. Also frequency relays cannot be used, because even a fully overloaded generator decreases the speed after 100 msec. Current protection relays detects the fault, by existing short circuit currents. Power sensing relays can also detect but cannot avoid the decreasing change of power to short circuit power. A problem is also the failure tripping of this kind of devices when to suddenly loading the generator. Without any mentioned limitation, the XG2 described detects mains failures within 70 msec., because it was specially designed for such kind of applications, where the kind of fault requires a very fast decoupling from the mains. The total tripping time lies still under 170 msec. even, when the circuit breaker time and the relay time is added. Requirement for a tripping of the generator mains monitor is a change of power of more than 15-20 % nominal power. Slow changes of the system frequency, for example controlling of the governor does not trip the relay. Short circuits in the mains can also trip the relay, be-cause a vector surge higher than the preset threshold can be detected. The value of the vector surge is de-pendent on the short circuit distance to the generator. This function offers the advantage for the utility that the mains short circuit capacity and therefore the energy feeding the short circuit is limited. DOK-TD-XG2 Rev.A 7

Woodward Manual XG2 GB Measuring principle of vector surge When a synchronous alternator is loaded, the rotor displacement angle is build between the terminal voltage (mains voltage U1) and the synchronous electromotive force (Up). Therefore a voltage is difference ΔU is built between Up and U1 (fig. 3.1). Figure 3.1: Equivalent circuit of synchronous generator in parallel with the mains Figure 3.2: Voltage vectors at mains parallel operation The rotor displacement angle between stator and rotor is depending of the mechanical moving torque of the generator shaft. The mechanical shaft power is balanced with the electrical feeded mains power, and therefore the synchronous speed keeps constant (figure 3.2). 8 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward Figure 3.3: Equivalent circuit at mains failure In case of mains failure or auto reclosing the generator suddenly feeds a very high consumer load. The rotor displacement angle is decreased repeatedly and the voltage vector U1 change its direction U1 (figure 3.3 and 3.4). Figure 3.4: Voltage vectors at mains failure DOK-TD-XG2 Rev.A 9

Woodward Manual XG2 GB Figure 3.5: Voltage vector shift As shown in the time diagram the voltage jumps to another value and the phase position change. This procedure is named phase or vector surge. The XG2 are continuously measuring the cycles, starting each zero message up ward slope. The cycle time is internally compared to the quarz table reference time. In case of vector surge as shown in fig. 3.5, the zero message is delayed and the device trips instantaneously. The trip angle Δ and consequently the sensitivity of the vector surge detection is adjustable. Information for use Although the vector surge relay guarantees very fast and reliable detection of mains failures under nearly all operational conditions of mains parallel running alternators, the following borderline cases have to be considered accordingly: a) No or only insignificant change of power flow at the utility connection point when a mains failure occurs This can arise during peak lopping operation or in CHP stations (Combined Heat and Power) where the power flow between power station and the public grid may be very low. For detection of a vector surge at parallel running alternators, the load change must be at least 15-20 % of the rated power. If the active load at the utility connection point is regulated to a minimal value and a high resistance mains failure occurs, then there are no vector surge nor power and frequency changes and the mains failure is not detected. This can only happen if the public grid is disconnected near the power station and so the alternators are not additionally loaded by any consumers. At distant mains failures the synchronous alternators are abruptly loaded by remaining consumers which leads directly to a vector surge and so mains failure detection is guaranteed. If such a situation occurs the following has to be taken into account: In case of an undetected mains failure, i.e. with the mains coupling C.B. in operation, the vector surge relay reacts upon the first load change causing a vector surge and isolates the mains C.B. 10 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward For detecting high resistance mains failures a zero sequence relay with an adjustable time delay can be used. A time delay is needed to allow regulating ac-tions where the current may reach "zero" at the utility connection point. At high resistance mains failures, the mains coupling C.B. is tripped by the zero sequence relay after the time delay. To prevent asynchronous switching on, an automatic restart by the public grid should be not possible during this time delay. As a further measure the load regulation at the utility connection point should be such that an active energy of 5 % of the alternator rated power is always flowing. b) Short circuit type loading of the alternators at distant mains failures At any distant mains failure, the remaining consumers cause sudden short circuit type loading of the power station alternators. The vector surge relay detects the mains failure in about 70 ms and switches off the mains coupling C.B. The total switch off time is about 150-170 ms. If the alternators are provided with an extremely fast short circuit protection e.g. able to detect di/dt, the alternators might be switched off unselectively by the alternator C.B., which is not desireable because the power supply for the station is endangered and later on synchronized changeover to the mains is only possible after manual reset of the overcurrent protection. To avoid such a situation, the alternator C.B.s must have a delayed short circuit protection. The delay time must be long enough so that mains disconnection by the vector surge relay is guaranteed. DOK-TD-XG2 Rev.A 11

Woodward Manual XG2 GB 4. Operation and settings All operating elements needed for setting parameters are located on the front plate of the XG2 as well as all display elements. Because of this all adjustments of the unit can be made or changed without disconnecting the unit from the DIN-rail. Figure 4.1: Front plate For adjustment of the unit the transparent cover has to be opened as illustrated. Do not use force! The transparent cover has two inserts for labels. Figure 4.2: How to open the transparent cover 12 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward LEDs LED "ON" is used for display of the readiness for operation (at applied auxiliary voltage Uv) and flashes at wrong phase sequence. LED Δ signals tripping of the vector surge function. Test push button This push button is used to test tripping of the relay and when pressed for 5 s a check up of the hardware takes place. Both output relays are tripped and the tripping LED lights up. 4.1 Setting of DIP-switches The DIP switch block on the front plate of unit XG2 is used for adjustment of the nominal values and setting of function parameters: DIP-switch OFF ON Functions 1* Un = 100 V Un = 110 V Setting of rated voltage 2* Un = 100 V Un = 230 V 3* Un = 100 V Un = 400 V 4* Inactive Active Phase sequence supervision 5* 1-phase 3-phase Single/three-phase measurement 6* 7* 8* Table 4.1: Function of DIP-switches * Only one of the DIP-switches 1-3 shall be in ON -position at the same time. Rated voltage The required rated voltage (phase-to-phase voltage) can be set with the aid of DIP-switch 1-3 to 100, 110, 230 or 400 V AC. It has to be ensured that only one of the three DIP-switches is switched on. The following DIP-switch configurations for adjustment of the rated voltage are allowed: Figure 4.3: Adjustment of rated voltage Rated voltage chosen too low does not cause destruction of the unit but leads to wrong measuring results which may lead to false tripping. Phase sequence supervision If DIP switches 4 and 5 are in position "ON", the phase sequence supervision is active. Wrong phase sequence is indicated with the flashing LED "ON" and all output relays will be tripped. A correct phase sequence is indicated with the permanently lit LED "ON". The phase sequence supervision is activated when UB< is exceeded. When connected to two-wire systems, the phase sequence supervision must be switched off. DOK-TD-XG2 Rev.A 13

Woodward Manual XG2 GB Supervision of single- and three-phase AC voltages For supervision of single phase AC voltages DIP-switch 4 + 5 must be switched off. If three phases should be supervised, DIP switch 5 has to be in position "ON". For supervision of 3-wire systems without N the DIP switch 5 must be in position ON. Note! Single-phase supervision (DIP switch 5 = OFF) can also be switched on with three-phase connection. The device triggers if in at least one of the three phases the set limit value Δ is exceeded and the surge in the remaining phases is not bigger than 1 in the opposite direction. The three-phase supervision (DIP switch 5 = ON) trips if in at least two of the three phases the set limit value is exceeded and the surge in the remaining phase is not bigger than 1 in the opposite direction. The vector surge supervision is only active when the blocking period of tv = 5 s has expired and the phase voltages exceed the blocking voltage UB<. Thanks to the criterion of the angular surges in the opposite direction, unintented disconnection during transient balancing processes is prevented. 4.2 Setting of tripping values The PROFESSIONAL LINE units have the unique possibility of of high accuracy fine adjustments. For this, two potentiometers are used. The course setting potentiometer can be set in discrete steps of 5. A second fine adjustment potentiometer is then used for setting of the final 1-6. Adding of the two values results in the precise tripping value. Vector surge tripping By using the potentiometer shown on the following figure, the vector surge trip relay can be adjusted in a range from 1 to 31 in 1 steps. Example: The requested tripping value to be set is 19. To achieve this, the setting value of the potentiometer on the right is simply to be added to the value of the potentiometer on the left. (The arrow of the potentiometers must always be in the middle of the marked bar, otherwise a definite setting value is not possible). Figure 4.4: Adjusting example Blocking time To prevent wrong trippings caused by oscillations after the synchronizing procedure, tripping is blocked after applying the measuring voltage for a fixed time tv = 5 s. If the measuring voltage drops below U B < the blocking time tv is reset. tv is activated again if the measuring voltage exceeds UB<. Blocking voltage With the aid of potentiometer U B </Un the blocking voltage can be set continuously variable in the range from 20-70 % Un (phase-to-phase voltage). 14 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward 4.3 Communication via serial interface adapter XRS1 Figure 4.5: Communication principle For communication of the units among with a superior management system, the interface adapter XRS1 is available for data transmission, including operating software for our relays. This adapter can easily be retrofitted at the side of the relay. Screw terminals simplify its installation. Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the software, actual measured values can be processed, relay parameters set and protection functions programmed at the output relays. Information about unit XRS1 in detail can be taken from the description of this unit. DOK-TD-XG2 Rev.A 15

Woodward Manual XG2 GB 5. Relay case and technical data 5.1 Relay case Relay XG2 is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the PROFESSIONAL LINE. The front plate of the relay is protected with a sealable transparent cover (IP40). Figure 5.1: Dimensional drawings Connection terminals The connection of up to a maximum of 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see chapter 4). 16 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward 5.2 Technical Data Connection possibilities: System voltage Setting Un Connection Setting Connection Setting Connection 100/58 V 100 V 58 V Y 100 V 3-phase Δ 100/58 V single-phase four wire 110/63 V 110 V 63 V Y 110 V 3-phase Δ 110/63 V single-phase four wire 230/130 V 230 V 130 V Y 230 V 3-phase Δ 230/130 V single-phase four wire 400/230 V 400 V 230 V Y 400 V 3-phase Δ 400/230 V single-phase four wire 690/400 V not possible not possible not possible Setting Y/Δ Y/Δ Y/Δ Y/Δ Table 5.1: Connection possibilities Measuring input circuits Rated data Rated voltage Un: Rated frequency range: Power consumption at the voltage circuit: Thermal carrying capacity of the voltage circuit: 100, 110, 230, 400 V AC (phase-to-phase voltage) 35-78 Hz (35-66 Hz at communication via serial interface) 1 VA/per phase at Un continuously 520 V AC Auxiliary voltage Rated auxiliary voltage Uv/: 36-520 V AC (f = 35-78 Hz) or 50-750 V DC / 4 W (terminals A1-A3) Power consumption: 19-55 V DC / 3 W (terminals A1 (L-) and A2 (L+)) Common data Dropout to pickup ratio: Resetting time from pickup: Returning time from trip: Minimum initialization time after supply voltage has applied: Minimum response time when supply voltage is available: depending on the adjusted hysteresis <50 ms 500 ms 100 ms 70 ms Output relay Number of relays: 2 Contacts: 1 changeover contact for each trip relay Maximum breaking capacity: ohmic 1250 VA/AC or 120 W/DC inductive 500 VA/AC or 75 W/DC Max. rated voltage: 250 V AC 220 V DC ohmic load Imax. = 0,2 A inductive load Imax. = 0,1 A at L/R 50 ms 24 V DC inductive load Imax. = 5 A Minimum load: 1 W / 1 VA at Umin 10 V Max. rated current: 5 A Making current (16 ms): 20 A Contact life span: 10 5 operations at max. breaking capacity DOK-TD-XG2 Rev.A 17

Woodward Manual XG2 GB System data Design standards: VDE 0435 T303; IEC 0801 part 1-4, VDE 0160; IEC 255-4; BS 142 VDE 0871 Temperature range at storage and operation: -25 C to +70 C Climatic resistance class F acc. to DIN 40040 and DIN IEC 68, T.2-3: more than 56 days at 40 C and 95 % relative humidity High voltage test acc. to VDE 0435, part 303 Voltage test: 2.5 kv (eff.), 50 Hz - 1 min Surge voltage test: 5 kv, 1.25/50 µs, 0.5 J High frequency test: 2.5 kv/1mhz Electrostatic discharge (ESD) acc. to IEC 0801 part 2: Radiated electro-magnetic field test acc. to IEC 0801 part 3: Electrical fast transient (burst) acc. to IEC 0801 part 4: Radio interference suppression test acc. to DIN 57871 and VDE 0871: 8 kv 10 V/m 4 kv / 2.5 khz, 15 ms limit value class A Repeat accuracy: 0.2 Rated values: 0.4 Frequency effect: 0.2 for the whole frequency range Mechanical test Shock: class 1 acc. to DIN IEC 255-21-2 Vibration: class 1 acc. to DIN IEC 255-21-1 Degree of protection Front plate: Weight: Mounting position: Relay case material: GL-Approbation: IP40 when the front cover is closed approx. 0.5 kg any self-extinguishing 94658-94HH Parameter Setting range Graduation Δ 1-31 1 UB< 20-70 % Un continuously variable Table 5.2: Setting ranges and graduation Technical data subject to change without notice! 18 DOK-TD-XG2 Rev.A

Manual XG2 GB Woodward Setting-list XG2 Project: Woodward job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters Function Unit Default settings Actual settings Δ Vector surge setting 1 UB< Blocking voltage % Un 20% DIP-switch Function Default settings 1* 100 V 2* Adjustment of rated voltage 100 V 3* 100 V 4 Phase sequence supervision inactive 5 Single phase / three phase measuring single phase 6 7 8 Actual settings *Only one of the DIP-switches 1-3 shall be in ON -position at the same time. DOK-TD-XG2 Rev.A 19

Woodward Manual XG2 GB Woodward Kempen GmbH Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet www.woodward.com Sales Phone: +49 (0) 21 52 145 216 or 342 Telefax: +49 (0) 21 52 145 354 e-mail: salesemea_pgd@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: SupportEMEA_PGD@woodward.com 20 DOK-TD-XG2 Rev.A