time delay relays plug-in NON-PROGRAMMABLE ON DELAY, INTERVAL, TRUE OFF DELAY & FLASHER Onboard & remote adjustable or fi xed time delays from 0.05 seconds to 2 hours Uses industry-standard 8 pin octal s 10A DPDT output contacts with appropriate 800.238.7474 www.macromatic.com sales@macromatic.com INPUT VOLTAGE PRODUCT WIRING/ FUNCTION 50/60Hz. NUMBER ** SOCKETS ON DELAY 120V AC/DC TR-50222-** 12V DC TR-50226-** 8 PIN OCTAL 24V AC/DC TR-50228-** 70169-D 240V AC TR-50221-** INTERVAL ON 120V AC/DC TR-50522-** 12V DC TR-50526-** 24V AC/DC TR-50528-** 240V AC TR-50521-** TRUE OFF DELAY 120V AC/DC TR-50622-** 12V DC TR-50626-** 24V AC/DC TR-50628-** DIAGRAM 1 240V AC TR-50621-** FLASHER 120V AC/DC TR-50822-** (OFF 1st) 12V DC TR-50826-** 24V AC/DC TR-50828-** 240V AC TR-50821-** See Defi nitions of Timing Functions. ** Complete Product Number using two-digit Code from Table below. Note: If these products are ordered with the Remote Adjustable Time Delay modifi cation (suffi x -Rx), they will require an 11 pin octal see www.macromatic.com/remote for information. Remote Adjustable Time Delay not available on TR-506 products. Time Delays TR-5 Series TR-5 Series Products have three time delay options: Onboard Adjustable Time Delay--complete Product Number by adding two-digit Code from ** TIMING RANGE TABLE Table at right, i.e., TR-50222-05 is an On Delay Time Delay Range Code with a time delay range of 0.1-10 seconds. 0.05-5 Sec. 04 Onboard Fixed Time Delay--replace two-digit 0.1-10 Sec. 05 Code with suffi x F followed by delay [0.1... 0.3-30 Sec. 07 0.6-60 Sec. 08 100] followed by (S) seconds, (M) minutes or (H) 1.2-120 Sec. 09 hours, i.e., TR-50222-F5S is an On Delay with a 1.8-180 Sec. 10 time delay fi xed at 5 seconds. 3-300 Sec. 12 Remote Adjustable Time Delay--Selected TR-5 0.1-10 Min. 22 Series products can be built with two terminals 0.3-30 Min. 15 for remote adjustable or fi xed time delays. See 0.6-60 Min. 16 www.macromatic.com/remote for information. 1.2-120 Min. 17 Not offered on TR-506 Sockets & Accessories available Build your Time Delay Relays with the Online Product Builder 18
NON-PROGRAMMABLE OFF DELAY, SINGLE SHOT, WATCHDOG & SINGLE SHOT FALLING EDGE TR-5 Series INPUT VOLTAGE PRODUCT WIRING/ FUNCTION 50/60Hz. NUMBER ** SOCKETS OFF DELAY 120V AC/DC TR-51622-** 11 PIN OCTAL Control Switch Trigger 12V DC TR-51626-** 70170-D 24V AC/DC TR-51628-** 240V AC TR-51621-** SINGLE SHOT 120V AC/DC TR-51522-** Control Switch Trigger 12V DC TR-51526-** 24V AC/DC TR-51528-** 240V AC TR-51521-** WATCHDOG 120V AC/DC TR-51322-** Control Switch Trigger 12V DC TR-51326-** (Retriggerable 24V AC/DC TR-51328-** DIAGRAM 2 Single Shot) 240V AC TR-51321-** SINGLE SHOT 120V AC/DC TR-52222-** FALLING EDGE 12V DC TR-52226-** Control Switch Trigger 24V AC/DC TR-52228-** 240V AC TR-52221-** OFF DELAY 120V AC/DC TR-51922-** 11 PIN OCTAL Power Trigger 12V DC TR-51926-** 70170-D 24V AC/DC TR-51928-** 240V AC TR-51921-** SINGLE SHOT 120V AC/DC TR-51722-** Power Trigger 12V DC TR-51726-** 24V AC/DC TR-51728-** 240V AC TR-51721-** WATCHDOG 120V AC/DC TR-51822-** Power Trigger 12V DC TR-51826-** (Retriggerable 24V AC/DC TR-51828-** Single Shot) 240V AC TR-51821-** DIAGRAM 4 See Defi nitions of Timing Functions. ** Complete Product Number using two-digit Code from Table below. 8 Pin SPDT versions of these functions (except Single Shot Falling Edge) are available Time Delays TR-5 Series Products have three time delay options: Onboard Adjustable Time Delay--complete Product Number by adding two-digit Code from Table at right, i.e., TR-51622-05 is an Off Delay with a time delay range of 0.1-10 seconds. Onboard Fixed Time Delay--replace two-digit Code with suffi x F followed by delay [0.1... 100] followed by (S) seconds, (M) minutes or (H) hours, i.e., TR-51622-F5S is an Off Delay with a time delay fi xed at 5 seconds. Remote Time Delay--Selected TR-5 Series products can be built with two terminals for remote adjustable or fi xed time delays. See www.macromatic.com/remote for information. ** TIMING RANGE TABLE Time Delay Range Code 0.05-5 Sec. 04 0.1-10 Sec. 05 0.3-30 Sec. 07 0.6-60 Sec. 08 1.2-120 Sec. 09 1.8-180 Sec. 10 3-300 Sec. 12 0.1-10 Min. 22 0.3-30 Min. 15 0.6-60 Min. 16 1.2-120 Min. 17 Sockets & Accessories available Build your Time Delay Relays with the Online Product Builder Onboard & remote adjustable or fi xed time delays from 0.05 seconds to 2 hours Uses industry-standard 11 pin octal s 10A DPDT output contacts 800.238.7474 www.macromatic.com sales@macromatic.com with appropriate time delay relays plug-in 19
NON-PROGRAMMABLE REPEAT CYCLE, ON/OFF DELAY, & DELAYED INTERVAL TR-5 Series INPUT VOLTAGE PRODUCT WIRING/ FUNCTION 50/60Hz. NUMBER ** SOCKET time delay relays plug-in Onboard & remote adjustable or fi xed time delays from 0.05 seconds to 2 hours Independently adjustable ON & OFF times Uses industry-standard 8 or 11 pin octal s 10A DPDT output contacts with appropriate 800.238.7474 www.macromatic.com sales@macromatic.com REPEAT CYCLE* 120V AC/DC TR-53122-** (OFF Time First Followed 12V DC TR-53126-** 8 PIN OCTAL By ON Time 24V AC/DC TR-53128-** 70169-D and Repeating) 240V AC TR-53121-** ON/TRUE OFF DELAY 120V AC/DC TR-54622-** 12V DC TR-54626-** 24V AC/DC TR-54628-** 240V AC TR-54621-** REPEAT CYCLE* 120V AC/DC TR-55122-** (ON Time First Followed 12V DC TR-55126-** DIAGRAM 1 By OFF Time 24V AC/DC TR-55128-** and Repeating) 240V AC TR-55121-** DELAYED INTERVAL* 120V AC/DC TR-56122-** (OFF Time Followed by 12V DC TR-56126-** 11 PIN OCTAL ON Time Followed by OFF 24V AC/DC TR-56128-** 70170-D State Until Reset) 240V AC TR-56121-** ON/OFF DELAY* 120V AC/DC TR-54122-** Control Switch Trigger 12V DC TR-54126-** 24V AC/DC TR-54128-** 240V AC TR-54121-** DELAYED INTERVAL* 120V AC/DC TR-56522-** Control Switch Trigger 12V DC TR-56526-** (OFF Time Followed by 24V AC/DC TR-56528-** DIAGRAM 2 ON Time Followed by OFF 240V AC TR-56521-** State Until Reset) See Defi nitions of Timing Functions. * ON & OFF Time Ranges for these functions are the same. See www.macromatic.com/onoff for information on how to order a unit with different ON & OFF time ranges. ** Complete Product Number using two-digit Code from Table below. Time Delays TR-5 Series Products have three time delay options: Onboard Adjustable Time Delay--complete Product ** TIMING RANGE TABLE Number by adding two-digit Code from Table at right, i.e., TR-53122-05 is a Repeat Cycle with both Time Delay Range Code an ON & OFF time delay range of 0.1-10 seconds. 0.05-5 Sec. 04 See www.macromatic.com/onoff for information 0.1-10 Sec. 05 on how to order a unit with different ON & OFF time 0.3-30 Sec. 07 ranges. 0.6-60 Sec. 08 Onboard Fixed Time Delay--replace two-digit Code 1.2-120 Sec. 09 with suffix F followed by delay [0.1... 100] followed 1.8-180 Sec. 10 by (S) seconds, (M) minutes or (H) hours, i.e., TR- 3-300 Sec. 12 53122-F5S is a Repeat Cycle with a time delay fixed 0.1-10 Min. 22 0.3-30 Min. 15 at 5 seconds. Remote Time Delay--Selected TR-5 Series products 0.6-60 Min. 16 can be built with two terminals for remote adjustable 1.2-120 Min. 17 or fixed time delays. Not offered on TR-546 See www.macromatic.com/remote for information. Sockets & Accessories available Build your Time Delay Relays with the Online Product Builder 20
TR-5 SERIES Non-Programmable Application Data Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal. Load (Burden): Maximum of 2 VA for all voltages Setting Accuracy: Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +2% or 50ms, whichever is greater Repeat Accuracy (constant voltage and temperature): +0.1% or + 0.04 seconds, whichever is greater Reset Time: Input Voltage (All Functions) 0.100 Seconds Triggered Functions only 0.04 Seconds Start-up Time: (Time from when power is applied until unit is timing) 0.05 Seconds Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units Temperature: Operating: -28 o to 65 o C (-18 o to 149 o F) Storage: -40 o to 85 o C (-40 o to 185 o F) Output Contacts: (All TR-5 Series Products except TR-506 & TR-546) DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13 (TR-506 & TR-546) DPDT 10A @ 240V AC; 8A @ 28V DC, 1/2 HP @ 240V AC, 1/4HP @ 120V AC B300 & R300 Dimensions Life: Mechanical: Full Load: 10,000,000 operations (2,000,000 operations on TR-506 & TR-546 Series only) 100,000 operations Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage or contact Macromatic for information regarding leakage current limits and other solid state design considerations. Triggering Off Delay, Single Shot or Watchdog Units: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.05 seconds. IMPORTANT FOR TR-506 & TR-546 SERIES ONLY: These relays are shipped from the factory in the OFF state. A shock to the relay during shipping or installation may cause it to change to the ON state. It is recommended that input voltage be applied to the product for at least 0.1 second and removed to cycle the unit to the OFF state prior to use in the application. Please note that it will take as long as the OFF Delay setting to reset the unit once input voltage has been removed. Approvals: (All TR-5 Series Products except TR-506 & TR-546) (TR-506 & TR-546 only) (All TR-5 Series Products) File #E109466 File #E109466 Low Voltage & EMC Directives EN60947-1, EN60947-5-1 File #LR45565 with appropriate File #E109466 time delay relays plug-in 2.4 (60) 1.7 (43) All Dimensions in Inches (Millimeters) 2.9 (74) 3.5 (89) 800.238.7474 www.macromatic.com sales@macromatic.com 21
time delay relays plug-in NON-PROGRAMMABLE OFF DELAY, SINGLE SHOT & WATCHDOG 8 Pin SPDT Versions TR-5 Series These are 8 pin 10A SPDT versions of our standard 11 pin DPDT products Onboard & remote adjustable or fi xed time delays from 0.05 seconds to 2 hours Uses industry-standard 8 pin octal with appropriate 800.238.7474 www.macromatic.com sales@macromatic.com INPUT VOLTAGE PRODUCT WIRING/ FUNCTION 50/60Hz. NUMBER ** SOCKETS OFF DELAY 120V AC/DC TR-51662-** Control Switch Trigger 12V DC TR-51666-** 8 PIN OCTAL 24V AC/DC TR-51668-** 70169-D 240V AC TR-51661-** SINGLE SHOT 120V AC/DC TR-51562-** Control Switch Trigger 12V DC TR-51566-** 24V AC/DC TR-51568-** 240V AC TR-51561-** WATCHDOG 120V AC/DC TR-51362-** Control Switch Trigger 12V DC TR-51366-** (Retriggerable 24V AC/DC TR-51368-** Single Shot) 240V AC TR-51361-** DIAGRAM 11 OFF DELAY 120V AC/DC TR-51962-** 8 PIN OCTAL Power Trigger 12V DC TR-51966-** 70169-D 24V AC/DC TR-51968-** 240V AC TR-51961-** SINGLE SHOT 120V AC/DC TR-51762-** PowerTrigger 12V DC TR-51766-** 24V AC/DC TR-51768-** 240V AC TR-51761-** WATCHDOG 120V AC/DC TR-51862-** Power Trigger 12V DC TR-51866-** (Retriggerable 24V AC/DC TR-51868-** Single Shot) 240V AC TR-51861-** DIAGRAM 37 See Defi nitions of Timing Functions. ** Complete Product Number using two-digit Code from Table below. Note: if these products are ordered with the Remote Adjust Potentiometer modifi cation (suffi x -Rx), they will require an 11 pin octal see www.macromatic.com/remote for information. Time Delays TR-5 Series Products have three time delay options: Onboard Adjustable Time Delay--complete Product Number by adding two-digit Code from Table at right, i.e., TR-51662-05 is an Off Delay with a time delay range of 0.1-10 seconds. Onboard Fixed Time Delay--replace two-digit Code with suffi x F followed by delay [0.1... 100] followed by (S) seconds, (M) minutes or (H) hours, i.e., TR-51662-F5S is an Off Delay with a time delay fi xed at 5 seconds. Remote Time Delay--Selected TR-5 Series products can be built with two terminals for remote adjustable or fi xed time delays. See www.macromatic.com/remote for information. Sockets & Accessories available ** TIMING RANGE TABLE Time Delay Range Code 0.05-5 Sec. 04 0.1-10 Sec. 05 0.3-30 Sec. 07 0.6-60 Sec. 08 1.2-120 Sec. 09 1.8-180 Sec. 10 3-300 Sec. 12 0.1-10 Min. 22 0.3-30 Min. 15 0.6-60 Min. 16 1.2-120 Min. 17 Build your Time Delay Relays with the Online Product Builder 22
TR-5 SERIES 8 Pin SPDT Versions Application Data Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal. Load (Burden): Maximum of 2 VA for all voltages Setting Accuracy: Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +2% or 50ms, whichever is greater Repeat Accuracy (constant voltage and temperature): +0.1% or + 0.04 seconds, whichever is greater Reset Time: Input Voltage (All Functions) 0.100 Seconds Triggered Functions only 0.04 Seconds Start-up Time: (Time from when power is applied until unit is timing) 0.05 Seconds Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units Dimensions 2.4 (60) Temperature: Operating: -28 o to 65 o C (-18 o to 149 o F) Storage: -40 o to 85 o C (-40 o to 185 o F) Output Contacts: SPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13 Life: Mechanical: 10,000,000 operations Full Load: 100,000 operations Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage or contact Macromatic for information regarding leakage current limits and other solid state design considerations. Triggering Off Delay, Single Shot or Watchdog Units: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.05 seconds. Approvals: File #E109466 File #LR45565 Low Voltage & EMC Directives EN60947-1, EN60947-5-1 with appropriate File #E109466 time delay relays plug-in 1.7 (43) 2.9 (74) 3.5 (89) All Dimensions in Inches (Millimeters) 800.238.7474 www.macromatic.com sales@macromatic.com 23
DEFINITION OF TIMING FUNCTIONS Understanding the differences between all the functions available in time delay relays can sometimes be a daunting task. To begin with, time delay relays are simply control relays with a time delay built in. Their purpose is to control an event based on time. Typically, time delay relays are initiated or triggered by one of two methods, depending on the function: application of input voltage application of a trigger These triggers can be one of two signals: a control switch (dry contact), i.e., limit switch, push button, fl oat switch, etc., or voltage (commonly known as a power trigger). CAUTION: any time delay relay that is designed to be initiated with a dry contact control switch trigger could be damaged if voltage is applied to the trigger switch terminals. Only products that have a power trigger should be used with voltage as the trigger. To help understand, some defi nitions are important: Input Voltage - control voltage applied to the input terminals. Depending on the function, input voltage will either initiate the unit or make it ready to initiate when a trigger is applied. Trigger- on certain timing functions, a trigger is used to initiate the unit after input voltage has been applied. As noted above, this trigger can either be a control switch (dry contact switch) or a power trigger (voltage). Output (Load) - every time delay relay has an output (either mechanical relay or solid state) that will open & close to control the load. Note that the user must provide the voltage to power the load being switched by the output contacts of the time delay relay. In all wiring diagrams, the output is shown in the normal de-energized position. Below and on the following pages are both written and visual descriptions on how the common timing functions operate. A Timing Chart shows the relationship between Input Voltage, Trigger (if present) and Output. If you cannot fi nd a product to fi t your requirements or have any questions, Macromatic s Application Engineers offer technical information along with product selection and application assistance. Call us at 800-238-7474 or e-mail us tech-help@macromatic.com. Function/Code Operation Timing Chart ON DELAY Delay on Operate Delay on Make INTERVAL ON Interval OFF DELAY Delay on Release Delay on Break Delay on De-Energization Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized. Input voltage must be removed to reset the time delay relay & de-energize the output.. Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be removed to reset the time delay relay. the output is energized. Upon removal of the trigger, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Any application of the trigger during the time delay will reset the time delay (t) and the output remains energized. time delay relays definition of timing functions SINGLE SHOT One Shot Momentary Interval the output is energized and the time delay (t) begins. During the time delay (t), the trigger is ignored. At the end of the time delay (t), the output is de-energized and the time delay relay is ready to accept another trigger. 800.238.7474 www.macromatic.com sales@macromatic.com 24
DEFINITION OF TIMING FUNCTIONS Function/Code Operation Timing Chart time delay relays definition of timing functions FLASHER (Off First) FLASHER (ON First) ON/OFF DELAY SINGLE SHOT FALLING EDGE WATCHDOG Retriggerable Single Shot TRIGGERED ON DELAY Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is de-energized and the sequence repeats until input voltage is removed. Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is energized and the sequence repeats until input voltage is removed. the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the trigger is removed, the output contacts remain energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the time delay relay is ready to accept another trigger. If the trigger is removed during time delay period (t1), the output will remain de-energized and time delay (t1) will reset. If the trigger is removed during time delay period (t2), the output will remain energized and the time delay (t2) will reset. the output remains de-energized. Upon removal of the trigger, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefi nitely. the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefi nitely. the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition as long as either the trigger is applied or the input voltage remains. If the trigger is removed during the time delay (t), the output remains de-energized & the time delay (t) is reset. 25 800.238.7474 www.macromatic.com sales@macromatic.com
DEFINITION OF TIMING FUNCTIONS Function/Code Operation Timing Chart REPEAT CYCLE (OFF 1st) REPEAT CYCLE (ON 1st) DELAYED INTERVAL Single Cycle TRIGGERED DELAYED INTERVAL TRUE OFF DELAY ON DELAY/ TRUE OFF DELAY SINGLE SHOT-FLASHER ON DELAY- FLASHER Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is de-energized and the sequence repeats until input voltage is removed. Upon application of input voltage, the output is energized and the time delay (t1) begins. At the end of the time delay (t1), the output is de-energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is energized and the sequence repeats until input voltage is removed. Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay (t2), the output is de-energized. Input voltage must be removed to reset the time delay relay. the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the relay is ready to accept another trigger. During both time delay (t1) & time delay (t2), the trigger is ignored. Upon application of input voltage, the output is energized. When the input voltage is removed, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the input voltage during the time delay (t) will reset the time delay. No external trigger is required. Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the input voltage is removed, the output remains energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the input voltage during the time delay (t2) will keep the output energized & reset the time delay (t2). No external trigger is required. the time delay (t1) begins and the output is energized for the time delay (t2). At the end of this time delay (t2), the output is de-energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is energized and the sequence repeats until time delay (t1) is completed. During the time delay (t1), the trigger is ignored. Upon application of input voltage, the time delay begins (t1). At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay (t2), the output is de-energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is energized and the sequence repeats until input voltage is removed. time delay relays definition of timing functions 800.238.7474 www.macromatic.com sales@macromatic.com 26
SOCKETS & ACCESSORIES 8 Pin Octal Socket- Catalog Number 70169-D Surface or DIN Rail-Mounted 10A @ 600V 1 or 2 #12-22 AWG Wire Recommended Tightening Torque of 7 in-lbs. (12 in-lbs maximum) Pressure Wire Clamp Terminations File #E169693 File #LR701114 s & accessories 11 Pin Octal Socket- Catalog Number 70170-D Surface or DIN Rail-Mounted 10A @ 300V 1 or 2 #12-22 AWG Wire Recommended Tightening Torque of 7 in-lbs. (12 in-lbs maximum) Pressure Wire Clamp Terminations File #E169693 File #LR701114 8 Pin Octal Socket- Catalog Number SR6P-M08G Back-Mounted 10A @ 300V Pressure Wire Clamp Terminations File #E62437 11 Pin Octal Socket- Catalog Number SR6P-M11G Back-Mounted 10A @ 300V Pressure Wire Clamp Terminations File #E62437 44 800.238.7474 www.macromatic.com sales@macromatic.com
SOCKETS & ACCESSORIES Hold Down Spring Catalog Number 70166 Can be used for: Panel-Mounted Sockets Sockets Mounted to 35mm DIN Rail * * Requires two machine screws with washers & nuts-- contact Macromatic or www.macromatic.com/70166 for more information. DIN Rail Adaptor Kit Catalog Number 70500 Quick & Economical Way to Install Any THx Series 2 x 2 Encapsulated Time Delay Relays on 35mm DIN Rail Clip Comes with a Threaded Hole to Eliminate Need for a Washer & Nut All Mounting Hardware Included s & accessories 800.238.7474 www.macromatic.com sales@macromatic.com 45