INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

Similar documents
INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

INSTALLER'S GUIDE ECON-IN-30B 18-HE60D83-3. Accessory Economizer Downflow

INSTALLATION INSTRUCTIONS

Models: WA182, WA242. Contents. Cabinet Components. Control Panel. Blower Assembly. BARD MANUFACTURING COMPANY Bryan, Ohio 43506

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

WALL MOUNTED PACKAGE AIR CONDITIONER REPLACEMENT PARTS MANUAL. Models: WA181, WA241. Contents. General Notes. Important

IN STAL LA TION IN STRUC TION

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

Contents. Cabinet Components " Exploded View... 1 " Usage List U.S. Models... 2 " Usage List Canadian Models... 3 " Blank Page...

Field Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners

Downflow Economizers Z1ECON30 (98W09) ECONOMIZERS

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

INSTALLATION INSTRUCTIONS

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

INSTALLATION & OPERATING INSTRUCTIONS. ECONOMIZERS WITH EXHAUST for EQUIPMENT BUILDING APPLICATIONS

INSTALLATION INSTRUCTIONS ECOHPRS Series Horizontal Economizer for York PRESTIGE for ZX 04-07; ZY 04-06

INSTALLATION & OPERATING INSTRUCTIONS. ECONOMIZERS WITH EXHAUST for STANDARD APPLICATIONS

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

Installation Instructions

Installation, Start-up and Operating Instructions

FOR SERVICE TECHNICIAN S USE ONLY

ETM-2040 Service Manual

FOR SERVICE TECHNICIAN S USE ONLY

Installation Instructions

Installation Instructions

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

Installation Instructions

Zone Manager INSTALLATION MANUAL 40KMC KMQ QNC QNQ

INSTALLATION INSTRUCTIONS

CPH Series. Submittal Data Form. 7½- to 12½-Ton Self-Contained. Packaged Heat Pump. with R-410A

ETM-2050/ETM-2051 Service Manual

McQuay Climate Control Singer. Incremental. NE, NH, NR Vintage A. TYA, TAA No Vintage. Last Manufactured: 1993

FCU (FREE COOLING UNIT)

Economizer Controller Installation Guide

PARTS VIEW FOR CIDV-30-20

Serial ATA Hot Swap Drive Cage Upgrade Kit for: Intel Server Chassis SC5200 Intel Server Chassis SC5250-E

Solar Combiner Enclosure

INSTALLATION MANUAL FOR CARRIER/BRYANT 3-15 TON ECONOMIZERS 3-6 TON MODELS

THERMOSTATS & CONTROLLERS

READ COMPLETELY BEFORE INSTALLING!!!

Specification and Design Catalog. Waterside Economizer

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

ECON-ZIP-BASE. ZIP Economizer Base Module

DCC Commercial. Submittal Data Form Tons Packaged Air Conditioners

Megatouch FORCE Monitor Chassis Board Replacement

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

INSTALLATION MANUAL SLI 50 INVERTER

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

INSTALLATION INSTRUCTIONS MODELS (-)XRD-01RJDCM3 & (-)XRD-01RJDDM3 VERTICAL AIRFLOW ECONOMIZERS

ENCLOSURE HEAT DISSIPATION

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

Installation Instructions

PowerLogic High Density Metering System 1-Meter Enclosure

Installation and Maintenance Manual IM

E1135C PDU and Pod Upgrade Procedure

TLS-3XX Series Consoles

CSR-G6300 6U Rack Chassis. CSR-G3300 3U Rack Chassis. Operation Manual

Wireless Remote Controller Kit

PTAC. Package Terminal Air Conditioner. Parts Catalog. Amana Refrigeration, Inc th Trail PO Box 8901 Amana, Iowa 52204

MicroTech II TM Remote I/O Panel Installation Manual

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

Fast Route to Reliable Energy Savings ZIP Economizer

BTU 4 & Sensors. Installation and Operation Manual

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

Daikin McQuay. Incremental Comfort System. PKEI, PKES, PKHS 007, 009, 012, 014 Design 2. Replacement Parts List No Revision G 12/2013

Installation Instructions

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity

INSTALLATION INSTRUCTIONS MODELS (-)XRD-01RJHCM3 HORIZONTAL AIRFLOW ECONOMIZERS

WARNING. KMC BACnet Module Kits IMPORTANT! CONTROLS KITS AND ACCESSORIES

[GSE25SETACSS] FREEZER DOOR

Liebert XDA Air Flow Enhancer. User Manual

TM-2100 Series Room Command Module

8 Button RS232/IR. Control Panel. MuxLab Inc A / SE A

S66 Series Electronic Fan Speed Control

DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書

Installation and Maintenance

S-100X / S-200X Snow Machine User Manual

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout

KM-4800w. Installation Guide

(Catalog Numbers 1394-FK10TS and -FK22TS)

INSTALLATION INSTRUCTIONS MODELS RXRD-RJCM3 HORIZONTAL AIRFLOW ECONOMIZERS

SE7600E Series. Installation Guide for Commerical HVAC Applications CONTENTS

CONTROLLER INSTALLATION OPERATION & QUICK START

Customer Replacement Procedure

H7625A, H7635A Humidity/Temperature Sensors

Chore-Tronics IDM Board Instruction

Removal and Installation8

Computer Temperature Interface model CTI-2. Description. Installation. Control Module

RAIN BIRD RC-4Bi, RC-7Bi, RC-1260Bi SERIES INSTRUCTION MANUAL

Installation and Start-Up Instructions

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

DCG Commercial. Submittal Data Form

INSTALLATION INSTRUCTIONS MODELS (-)XRD-PJCM3 & (-)XRD-SJCM3 VERTICAL AIRFLOW ECONOMIZERS

Image Key Part Number Description Substitution Qty.

Junos WebApp Secure 5.0 Hardware Guide

Installation, Operation and Maintenance Manual

Transcription:

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST MODEL WGSEIFM-5 For Use with Bard 3 through 5 Ton Step Capacity Wall Mount Air Conditioners with Gas Heat Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-498A Supersedes: 2100-498 File: Volume III Tab 19 Date: 08-12-08 Copyright 200 Page 1 of 14

CONTENTS General General Information... 3 Unpacking... 3 Description... 3 Models... 3 Installation Basic Installation... 4, 5,, 8 Economizer Sequence of Operation Condition A Cool Outdoors... 13 Economizer Sequence of Operation Condition B Warm Outdoors... 14 Figures Figure 1 Removal of Exterior Panels... 4 Figure 2 Installation of Economizer... 5 Figure 3 Install Loose Piece Wire Harness... 6 Figure 4 WGSEIFM-5 Wiring Diagram... Figure 5 Economizer Logic Module... 9 Figure 6 Economizer Op - Single Compressor... 12 Figure Call for Blower Operation... 13 Figure 8 Call for Cooling Operation... 14 Tables Table 1... 3 Table 2... 8 Graphs WG3S Ventilation Airflow... 10 WG4S Ventilation Airflow... 10 WG5S Ventilation Airflow...11 Manufactured under U.S. Patent number 5,301,44 Other patents pending COPYRIGHT DECEMBER 200 BARD MANUFACTURING COMPANY, INC. BRYAN, OHIO USA 43506 Page 2 of 14

GENERAL GENERAL INFORMATION The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step by step procedure with which the mechanically inclined owner can install the package. The ventilator housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions. The economizer installation will function normally with the 2-stage thermostats already specified for usage with this 2-stage cooling unit. If the free cooling of the economizer cannot keep up with the cooling demand, it will de-energize the economizer and will then operate on 2nd stage mechanical cooling. Because of this, all units equipped with an economizer need to be equipped with the low ambient control. For field installed applications, install Bard Low Ambient Control Kit CMA-28. If using a Bard Master Controller, the Bard MC3000 controller is designed to control two (2) redundant Bard Wall Mount units equipped with economizers. Refer to the MC3000 Installation Manual (or consult Bard Technical Service) for the required connections and sequence of operation. UNPACKING Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped. Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt. DESCRIPTION The WGSEIFM-5 economizer is designed to be used with Bard WG*S 2-stage cooling, 1-stage heating gas electric model wall mounts that are equipped with fan cycling controls. They are an electromechanical economizer system designed to provide free cooling where the outdoor air temperature is cool enough to provide the needed cooling without running the compressor. When cooling is needed, the system automatically takes advantage of the cold outdoor air when available, and uses it for first stage cooling. Thus reducing the need to run the air conditioning compressor providing lower operating costs and increasing the service life of the equipment. If the outdoor air gets too warm or humid to be helpful, the enthalpy control detects the condition and automatically operates the internal damper and switches on the mechanical cooling. This is all accomplished automatically without attention from the user to achieve maximum savings. See Figure 6 for a block diagram of the economizer operation logic flow. The unit is equipped with a full modulating type damper motor, which controls the damper position to a factory set minimum supply air temperature. MODELS When installed in model series (refer to Table 1), the WGSEIFM-5 provides built in exhaust provisions. When the damper blade opens to bring fresh air in, the damper also opens an exhaust relief. The exhaust air will flow into the condenser section of the unit. The condenser fan will help draw exhaust air out. MODEL WGSEIFM-5 TABLE 1 FOR USE WITH FOLLOWING UNITS WG3S WG4S WG5S Page 3 of 14

INSTALLATION WARNING Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to off. BASIC INSTALLATION 1. Unpack the ventilator assembly which includes the integral ventilator with attached electrical harness, blank-off plate and miscellaneous hardware. 2. Remove and save the existing exterior blower access and service access panels (see Figure 1). 3. Remove and discard exhaust cover plate (see Figure 1). 4. In rear of opening towards duct connection, install exhaust opening adaptor plate (included). FIGURE 1 REMOVAL OF EXTERIOR PANELS EIFM CRV UNIT MIS-2414 FRONT DOOR VENT TERMINAL RIGHT FRONT CORNER EXHAUST COVER PLATE VENT OPTION PANEL MIS-2416 Page 4 of 14

5. Install ventilator sheet metal assembly by inserting the ventilator into the unit centering between the tubing on the left and the control panel on the right. Once the ventilator is fully inserted, slide the ventilator to align screw hole through the front of the condenser grille. (See Figure 2.) IMPORTANT: Position front lip of ventilator on top of front grille and condenser partition. (See Figure 2 inset.) This is important to ensure proper drainage of any water entering damper assembly. 6. Open control panel to gain access to unit low voltage terminal block.. Install loose piece wire harness plug into filter tray & route wires into low volt box. (See Figure 3.) (Save back two {2} long red wires with push-on terminals.) 8. Plug wire plug from vent package installed in Steps #1 through #6 into plug installed in Step #. FIGURE 2 INSTALLATION OF ECONOMIZER FIGURE 2 INSET SIDE SECTION Page 5 of 14

FIGURE 3 INSTALL LOOSE PIECE WIRE HARNESS PLUG ROUTE WIRES THROUGH WIRE MOUNT, AND INTO HOLE AT REAR OF UNIT INTO LOW VOLTAGE TERMINAL BLOCK AREA PLUG TO SECURE INTO FILTER TRAY MIS-2415 Page 6 of 14

Y FIGURE 4 WGSEIFM-5 WIRING DIAGRAM EIFM CONTROL PANEL 6 6 ORANGE! DANGER ENTHALPY SENSOR 4 1 3 * ELECTRICAL SHOCK HAZARD * DISCONNECT POWER BEFORE + RED 4 6 SERVICING S 9 O BLACK A B 8 RED BROWN 8 8 TR TR1 So + Sr + 5 1 2 3 4 T T1 P P1 LOGIC MODULE 16 9 RED CONROL RELAY 5 PL1 PL2 ORANGE BLACK ORANGE YELLOW PURPLE PINK BLUE 1 1 2 2 3 3 6 6 5 5 4 4 BK O Y PR PK BL C G R Y1 Y Y2 F E W1 W2 1 2 3 UNIT 24 VOLT TERMINAL STRIP R TH R UNIT BLOWER SECTION 4056-19 A 9. Mount mixed air thermistor sensor to blower as shown with screws provided. Route two (2) red wires from wire harness installed in Step # through cable holders, and connect to thermistor sensor as shown in Figure 2. 10. Connect the wires (with fork connectors) routed into the low voltage box in Step # to the low voltage terminal strips as follows per wiring diagram on Figure 4: Black to C Orange to G Yellow to Y1 Purple to Y Pink to Y2 Blue to W1 11. Replace right front unit corner and vent terminal. 12. Close upper unit door to seal blower discharge air. 13. Economizer Check Out A. Remove mist eliminator (Figure 2). Locate the minimum position potentiometer. (See Figure 5.) B. Energize the evaporator blower by switching thermostat to the manual fan position with heat/ cool in the OFF position. C. Cycle the minimum position potentiometer (factory set for 0% fresh air) 0 to full open. (See Figure 5.) Throughout checkout procedure observe operation of damper to insure there is free, unobstructed operation through the entire angle of damper travel. Then adjust the damper minimum open position to meet local codes or application requirements. See example below. Page of 14

EXAMPLE: 1. Measure return air temperature (RAT) (assume 5 F for example). 2. Measure outdoor air temperature (OAT) (assume 60 F for example). 3. Calculate the mixed air temperature (MAT) which will result from the desired combination of OAT (10 percent) and RAT (90 percent)..1 OAT +.9 RAT = MAT or substituting example values.1 (60 F) +.9 (5 F) = 3.5 F 4. Adjust the minimum position potentiometer knob until proper mixed air temperature as calculated above is reached. Care should be taken to insure thermometer is sensing air that is well mixed. 5. Mark correct setting on dial of minimum position potentiometer for future reference. D. Adjust the economizer logic module to position A, B, C and D to achieve the maximum combination of temperature and humidity acceptable for the installation as per Table 2. The suggested setting is between A & B 0 DB @ 55 percent RH. It is further recommended to always set the control at C or above.) (See Figure 5.) E. Switch the thermostat fan control to automatic and position the heat/cool switch to cool. Adjust the thermostat temperature to engage the first stage of cooling only (Y). This will cause the dampers to modulate to achieve mixed air temperature of 55 provided outside air enthalpy is sufficiently low. If enthalpy is too high for economizing, low enthalpy can be simulated by temporarily removing and jumping leads on terminals 2 and 3 of enthalpy control together. This will also cause the economizer damper to modulate away from minimum position. (Be sure to properly reconnect leads at end of checkout procedure). F. Readjust temperature on the thermostat to engage the second stage of cooling (Y2). The damper motor should return to previously set minimum position. Compressor motor should start. G. Switch thermostat to OFF fan and OFF heat/ cool positions to de-energize unit. Economizer damper should return to full closed (100 percent return air) position. Checkout is complete. 14. Replace control access panel and mist eliminator. 15. Remove blank off plate or barometric fresh air damper if installed on the service access panel. Plug the four (4) holes used to mount the BOP or BFAD with the plastic plugs supplied with the economizer. 16. Replace service access panel. 1. Economizer is now ready for operation. TABLE 2 ECONOMIZER LOGIC CONTROL SETTING Dial Setting 20% RH 50% RH 80% RH A 80 deg. F (26 deg. C) 3 deg. F (23 deg. C) 66 deg. F (19 deg. C) Enthalpy Contol Setting B C 6 deg. F (24 deg. C) 4 deg. F (23 deg. C) 0 deg. F (21 deg. C) 66 deg. F (19 deg. C) 63 deg. F (1 deg. C) 59 deg. F (15 deg. C) D 1 deg. F (21 deg. C) 63 deg. F (1 deg. C) 54 deg. F (12 deg. C) Page 8 of 14

FIGURE 5 ECONOMIZER LOGIC MODULE Page 9 of 14

00 WG3S Ventilation Airflow 600 500 Ventilation Airflow (CFM) 400 300 Stage #2 Operation Blower Only & Stage #1 Operation 200 100 0 0 2.5 5.5 10 12.5 15 1.5 20 22.5 25 2.5 30 Vent Position 900 WG4S Ventilation Airflow 800 00 Ventilation Airflow (CFM) 600 500 400 300 Stage #2 Operation Stage #1 Operation Blower Only 200 100 0 0 2.5 5.5 10 12.5 15 1.5 20 22.5 25 2.5 30 Vent Position Page 10 of 14

WG5S Ventilation Airflow 1000 900 800 Ventilation Airflow (CFM) 00 600 500 400 300 Stage #2 Operation Stage #1 Operation Blower Only 200 100 0 0 2.5 5.5 10 12.5 15 1.5 20 22.5 25 2.5 30 Vent Position Page 11 of 14

Page 12 of 14 FIGURE 6 ECONOMIZER OPERATION FOR SINGLE COMPRESSOR UNIT

ECONOMIZER SEQUENCE OF OPERATION CONDITION A COOL OUTDOORS First stage cooling closes and powers the economizer dampers to economizer mode and the indoor blower starts. Mixed Air Sensor senses a mixture of return air and outdoor air and modulates the dampers accordingly. Compressor operation is inhibited. (See Figure.) If second stage closes on the thermostat, the dampers return to the closed or minimum position setting and the compressor starts for mechanical cooling. FIGURE CALL FOR BLOWER OPERATION Page 13 of 14

CONDITION B WARM OUTDOORS First stage cooling cycles the compressor and dampers remain in mechanical cooling mode. FIGURE 8 CALL FOR COOLING OPERATION Page 14 of 14