LON bus LonWorks Network in Protection and Control Systems. User s manual and Technical description

Similar documents
SPA-ZC 100/SPA-ZC 102 LON /SPA Gateway. Programming Manual

LON bus communication devices 1MRS MBG Page 1 Issued: April 1999 Status: New Data subject to change without notice

SREDU Double Connection Option Card for Lon Star Coupler RER 111

SMS 510, CAP 505 LON Gateways Configuration Configuration Guide

Data communication and reporting unit

Data communication and reporting unit

SPA-ZC 200/SPA-ZC 202 IEC /SPA-gateway Modules. Installation Manual

LONWORKS Power Line Communication Adapter

Communication Gateway COM 500. Product Guide

SPA-ZC 17. Bus connection module SPA-ZC 17. User s manual and Technical description. Tx SC Rx BB BM MB MM SPA / RS 485 POWER SLAVE 1 MASTER 0

RER 123 Bus Connection Module. Technical Description

LONMANAGER NSS-10 MODEL

LNT 505 Installation and Commissioning Manual

MicroSCADA Pro SYS Connecting LONWORKS Devices

Sequential Event Recorder

in Berlin (Germany) Sponsored by Motorola Semiconductor NEC Electronics (Europe) Siemens Semiconductors Organized by

Relion 650 series. 650 series 2.1 IEC LON Communication protocol manual

Fieldbus Appendix ANYBUS -S LonWorks

Voltage regulator TAPCON 240

INSTALLATION INSTRUCTIONS

Modbus Remote Communication Protocol for REM 54_. Technical Description

Introduction to the LONWORKS Platform

Medium Access Protocols

Next Generation Intelligent Lon EIA/ANSI 709 Router Datasheet

Summary of MAC protocols

ICC. Metasys N2 Master Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

SmartRouters Optionally with Bus Diagnostics RTRS RTRSD

SPA-ZC 302. Profibus-DPV1/SPA Gateway. Product Guide. spa-zc302_rightco300

Earth-fault Relay SPAJ 110 C. Product Guide

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

Chapter 6: DNP Introduction. 6.2 Features of the DNP The OSI/ISO model. 6.3 Basic topology

LON Module for Variable Speed Drive

Pyxos FT Network Chip 11500R

COM600 Station Automation Series External OPC Client Access 3.1. User's Guide

Prepared by Agha Mohammad Haidari Network Manager ICT Directorate Ministry of Communication & IT

Gateway 1400 Reference Manual

THT-500-A/R (C5) 1. System Configuration COMMUNICATION INSTRUCTION MANUAL. No. THT5CE

DOMOTICA ED EDIFICI INTELLIGENTI UNIVERSITA DI URBINO

CPU. Switch 1 Switch 2

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Synchro-check relay. Application

MPU-32 AND FPU-32 TIA-485 NETWORK

THE OSI MODEL. Application Presentation Session Transport Network Data-Link Physical. OSI Model. Chapter 1 Review.

Feeder protection relay SPAA 121 C. Product Guide

Jim McGhee, Utility Market Manager, RuggedCom Inc.

Communicate IT Software module DR-COM. Buyer s Guide

Chapter 6 The Link Layer and LANs

MHz TRANSCEIVER. Bi-Directional Send and Receive. Compatible with: Transmitter Receiver Transceiver. Part # Part #

Relay configuration and setting tool package

HDV100A3 Command Response Protocol

General characteristics of C-type relay modules

750/760 COMMUNICATIONS GUIDE. Digital Energy Multilin. Feeder Management Relay

Relay Product Engineering Tools

J1939 OVERVIEW. 1

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

TOSHIBA CMOS Digital Integrated Circuit Silicon Monolithic TMPN3120FE5MG

Page 1. Reference: Networking and Integration of Facilities Automation Systems, Chapter 12

M242 COMPUTER NETWORS AND SECURITY

Ethernet Adapter. Modbus/TCP Brigde. Installation and Commissioning Manual

NodeBuilder 3.1 Development Tool Model 10020

The Link Layer and LANs: Ethernet and Swiches

Principles behind data link layer services

Residual overvoltage relay

Principles behind data link layer services:

Principles behind data link layer services:

SBPC-21-PB FifeNet to Profibus Gateway

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

R6-NE1 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL ETHERNET INTERFACE MODULE MODEL. (Modbus/TCP, for 32-point analog signals)

Neuron Chip. Network Transceiver. Figure 1. Architecture of a Neuron Chip-based node.

ET4254 Communications and Networking 1

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

M2400 Analog Output. Technical Description. Eiserstraße 5 phone 05246/ Verl fax 05246/ Date : Version : 2.

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Protection Terminal REF 54_ Protection Relay REX 521

2. LAN Topologies Gilbert Ndjatou Page 1

Configuration of Synchronous Protocols

COM600 Station Automation Series MNS is Connectivity (OPC) 3.2. User's Guide

LONMARK Product Conformance Review and Checklist

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration

Chapter 6 Addressing the Network- IPv4

REM 543 Machine Terminal. User s Guide for Modbus Configurations

PROFIBUS Workshop EN B U I L D I N G P R O C E S S M A N U F A C T U R I N G EUROPEAN FIELDBUS STANDARD. Chapter 1 Date 11/04/99, page 1

ICS Regent. Communications Package for W INTERPRET. Guarded Peer-Link Communications (T3831) PD-6041

CH : 15 LOCAL AREA NETWORK OVERVIEW

Sender Receiver Sender

Accessories / 7XV5662

Application of LonWorks Distributed Control Technology in Greenhouses

TOSHIBA CMOS Digital Integrated Circuit Silicon Monolithic TMPN3120FE3MG

Transporting audio-video data

Contents. Additional Instructions P-3X CANopen

Monitoringsystem TAPGUARD 260

Anybus X-gateway LonWorks Interface

Local Area Network Overview

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

AL2-MBU Advanced Manual

DeviceNet - CIP on CAN Technology

X-gateway Interface Addendum DeviceNet Scanner Interface

Data channel ports and LAN channel ports will be referred to as channel ports when distinction between the two is not required.

Transcription:

LON bus LonWorks Network in Protection and Control Systems User s manual and Technical description

1MRS 750035-MTD EN Issued 95-03-27 Version A Checked Approved Data subject to change without notice LON bus LonWorks Network in Protection and Control Systems Contents Introduction... 3 General description... 4 LonTalk application protocol... 4 Network variables... 4 Explicit messages... 4 Use of LonTalk application protocol in protection and control systems... 4 Layer 2...6 services... 5 Transport services... 5 Network addressing... 5 Communication buffers... 5 Timing parameters and priority channels... 5 Collision detection... 5 Physical layer interface... 6 Fiber optic interfaces... 6 LON interface module of the devices... 6 Star coupler... 7 Routers... 8 Message formats... 9 Network variables... 9 General network variable message format... 9 Network variable types... 9 Clock synchronization network variables... 11 Explicit messages... 12 General message format... 12 LSG format event messages... 12 Transparent SPA-bus messages... 13 LSG format configuration messages... 14 LON bus performace figures... 14 Echelon, LON, LonBuilder, LonManager, LonTalk, Neuron and 3150 are U.S. registered trademarks of Echelon Corporation. LonLink, LonMark, LonSupport, LonUsers, LonWorks, LonMaker, and 3120 are trademarks of Echelon Corporation. 2

Introduction This document describes the use of LonWorks Network and its protocol LonTalk protocol in our protection and control systems used in medium or high voltage substations, power stations or in industrial power distribution. The LonTalk protocol is designed for communication in control networks. These networks are characterized by short messages (few bytes), very low per node cost, multiple communication media, low bandwidth, low maintenance, multivendor equipment, and low support costs. It is also desined to support the needs of applications spanning a range of industries and requirements. The protocol follows the reference mode for open system interconnection (OSI) designed by the International Standardization Organization (ISO). The speed of the network is dependent upon the medium and tranceiver design. With protection and control devices we are using fiber optic media, which enables use of the maximum speed of 1,25 Mbits/s. The protocol is a peer-topeer protocol where all the devices connected to the network can talk to each other. The nodes are identified by their own subnet and node number (max. 255 subnets, 127 nodes per one subnet). The LON bus links together the different parts of the protection and control system. The measured values, status information and event information is spontaneously sent to the higher-level devices. The higher-level devices can read and write memorized values, setting values and other parameter data when required. Additionally the LON bus enables the bay level devices to talk to each other in order to deliver e.g. interlocking information between the bay controllers and blocking signals between the protective relays. The LonTalk protocol supports two types of application layer objects: network variables and explicit messages. Network variables are used to deliver short messages like measurement values, status information and interlocking/blocking signals. Explicit messages are used to transfer longer pieces of information like events and explicit read and write messages to access device data. Also SPA-bus messages can be transpararently sent in explicit messages in order to transfer e.g. parameter data. The benefits achieved by the use of LonWorks Network in protection and control systems include: direct communcation between all the devices in the system, support for multimaster or redundant system implementations and improved response times. Additionally LonWorks Network is an open system utilized in many application areas offering word-wide support for system integrators willing to utilize our relays and cotnrol units in their systems. 3

General description LonTalk application protocol The LonTalk protocol supports two types of application layer objects: network variables and explicit messages. Network variables The LonTalk protocol employs a data oriented application protocol. In this approach, application data items such as temperatures, pressures, states, text strings and other data items are exchanged between nodes in standard engineering and other predefined units. The command functions are then encapsulated within the application programs of the receiver nodes rather than being sent over the network. In this way, the same engineering value can be sent to multiple nodes which each have a different application for that data item. The data items in the LonTalk application protocol are called network variables. Network variables can be any single data item or data structure with the maximum length of 31 bytes. Network variables are addressed on application level using network variable selectors. The selector is a 14-bit number in the range 0...12287. Explicit messages Explicit messages containing up to 229 bytes of data can also be sent over the network. Different types of explicit messages are classified using an 8-bit message code. A special range of message codes is reserved for foreign frame transmission. Up to 229 bytes of data may be embedded in a message packet and transmitted like any other message. The LonTalk protocol applies no special processing to foreign frames - they are treated as a simple array of bytes. The application program may iterpret the data in any way it wishes. Some of the messages codes are reserved for LonTalk Network Management and Diagnostic services. So called "Foreign messages/responses" can be sent using messages codes 40H...4FH. Use of LonTalk application protocol in protection and control systems Process data like measurement values and indications are sent using either network variables or explicit messages. The explicit messages may be either LSG format events or AFD format messages. Control commands are sent using network variables or explicit messages of AFD format. Setting values and other parameter data are sent using explicit messages or files. The format of explicit messages to transfer parameter data is SPA or AFD. Files are sent using LonTalk file transfer protocol. In simple nodes parameter data may also be sent using network variables. LON network is configured using LonTalk Network Management messages. The following "Foreign message" codes are used for our special use: - LSG format event messages 40H - transparent SPA-bus messages 41H - LSG format configuration messages 43H - AFD messages 4CH - DMP messages 4AH 4

Layer 2...6 services Transport services The LonTalk protocol offers four basic types of message trasport services: - acknowledged service - unacknowledged repeated service - unacknowledged service - request/response service Most of the messages are sent using acknowledged service. Unacknowledged repeated service may be used to transfer data from one node to many receivers. Unacknowledged service is used e.g. for clock synchronization. Request/response service is used with network management messages and with network variable poll messages. Network addressing LonTalk addresses are hierachically structured. There are three basic address types with three components per address, as shown below: (Domain, Subnet, Node) (Domain, Subnet, Neuron_ID) (Domain, Group, Member) In our protection and control systems the application messages are sent using Subnet/Node addressing with Domain field = 0 (Domain address is not used). Communication buffers To enable the use of simple LON devices in the same network as more complex devices the max. length of communcation buffers is usually 66 bytes. Long explicit messages are sent in pieces of 32...45 bytes. Timing parameters and priority channels Each device which is sending interlocking/blocking messages or clock synchronizing messages must be assigned a priority channel to enable the use of priority with these messages. Priority messages may not be used for any other type of data. The timing parameters must be set according to the LonTalk Interoperability Guidelines. Collision detection Collision detection is optionally used. All the devices connected to the system do not have to support collision detection. It should be used by devices which send interlocking or blocking messages or other similiar type messages. Collision detection together with priority assingment is used to quarantee deterministic transfer of these messages also in heavy load conditions. 5

Physical layer interface Physical layer media of the LON bus is fiber optic cabling. The physical network is star network implemented using star couplers. The default speed of the network is 1.25 Megabits per second. Interfaces to other types of network cabling (e.g. transformer isolated twisted pair) can be arranged using LonWorks Routers. Also network parts with different speed than 1.25 Mbits/s can be used in the system with the help of routers. Fiber optic interfaces The fiber optic LON bus is implemented using eihter glass core or plastic core fiber optic cables. Specification of the fiber optic connections: Glass fiber Plastic fiber Cable connector ST-connector snap-in connector Cable diameter 62.5/125 µm 1 mm Max. cable length 1000 m 20 m Wavelength 820-900 nm 660 nm Transmitted power -13 dbm (HFBR-1414) -13 dbm (HFBR-1521) Receiver sensitivity -24 dbm (HFBR-2412) -20 dbm (HFBR-2521) When a device is not sending, no light is sent to the fiber. When device starts sending light transmitter is activated. LON interface module of the devices The fiber optic interface of a device is implemented using a "LON interface module", which is connected to a 9-pin, female D-connector of the device. The used signal levels are according to RS-485 standard. The pin assingment of the RS-485 LON bus D- connector is: Pin Usage 1 DATA A, data signal A (+) 2 DATA B, data signal B (-) 3 RTS A, request to send signal A (+) 4 RTS B, request to send signal B (-) 5 COL A, collision detection signal A (+) 6 COL B, collision detection signal B (-) 7 GND, signal ground for the power supply 8 Service Pin connection (TTL level signal) 9 +5V, power supply for the module The "LON interface module" is built to detect collision on the fiber optic connection. Collision will be detected and signalled to the attached device using COL signal pair, if the device keeps RTS active at the same time as ligth is received from the fiber optic receiver. (This is true, if the attached device attempts to send at the same time as some other device is sending.) The "LON interface modules" and also the star couplers are built so that they do not echo light back to the same fiber optic connection (transmitter/receiver pair) from which the light was received. 6

Star coupler The star couplers contain 3 or more fiber optic connections, each connection being a transmitter-receiver pair. The star couplers may be hierarchically arranged in two layers as illustrated in the following figure. The arrangement shoud be done so that a message sent from any of the devices in the system should not go through more than three star couplers to reach any other device in the system. Two devices may also be chained together using a LON interface module with two fiber optic connections. In this case one connectioin of the LON interface module is connected to a star coupler and the other is connected to another device's LON interface module. Care must be taken when building the system, a message sent by any of the devices in the system should not go through more than six fiber optic cables lines before reaching any other device in the system. "Higher-level devices Star Coupler Fibre-optic cables of the LON bus Star Coupler Star Coupler Protection and control devices Figure 1. Structure of the system built using star couplers and fiber optic cables. Star couplers arranged hierachically in two levels. Two devices chained together (on the right). The maximum recommended distance between any two devices connected with fiber optic cables to the same system is 2000m. That is, the system may include at most two 1000m fiber optic connections. Redundant fiber optic interfaces may be built using suitable LON interface modules and star couplers. 7

Routers The system may include LonTalk Routers to divide the network into smaller pieces. Routers may be configured to pass only selected messages from one part of the network to other parts of the network. Routers should be used e.g. to isolate big internal traffic of almost independently working subsystems (e.g. devices constituting a control circuitry) from the rest of the system. This kind of considerations should be made especially to relieve the possible overload problems of the "higher-level" devices. The routers also enable the connection of devices with other type of physical LON interface (e.g. twisted pair 78kbit/s) to the fiber optic LON network. "Higher-level devices Star Coupler Fibre-optic cables of the LON bus Star Coupler Subnet 1 R Router card Star Coupler R Router card Subnet 2 Transformer isolated, twisted pair connection Protection and control devices Figure 2. Example of a system utilizing routers. Router card in the rightmost star coupler isolates the internal traffic of subnet number 2 from the traffic of the rest of the system (subnet 1). Small device with twisted pair LON interface on the left is connected to the system using a router/repeater card in the leftmost star coupler. 8

Message formats Network variables Network variables contain the "value attribute" of the most frequently transferred data objects. In many cases (depending on the device cababilities) data values which are sent as network variables can alternatively be accessed transparently using explicit messages of SPA or AFD format. Those data objects, which are to be transferred as network variables must be assigned a network variable selector when system is configured. During configuration the data objects are addressed using a 8 or 16-bit network variable index - as in every standard LON node. General Network Variable message format The data part of a network variable message contains 2bits of control information and 14-bit network variable selector and the data itself. 1 X network variable X = 0, variable update message or response to a poll selector (14 bits) X = 1, variable poll message data 1...31 bytes Network variable types In our applications the analog values are sent as integer values using either 32 bit or 16 bit network variables. Digital data is sent using 16- bit network variables. The bit write (BWR) format is used in cases when e.g. mapping to ANSI X3.28 protocol's BitWrite command is required. 32 bit analog values: Also some other formats than formats defined in this chapter can be used, e.g. formats compatible with LonWorks Standard Network Variables. All the devices don't necessarily accept all the possible types, types must be checked when making network variable bindings or otherwise when one tries to read or write a variable. The Standard Nework Variables compatible with our 16-bit digital network variables (except BWR) are e.g. SNVT_count and SNVT_state. 1 0 selector msb selector lsb 32-bit analog value, 32-bit fixed point data 4 bytes integer value with scaling factor 1000. (E.g. value 1.05 is sent as 1050) 9

Network variable types (continued) 16 bit analog values: 1 0 selector msb selector lsb 16-bit analog value, 16-bit fixed point data 2 bytes integer value with scaling factor 100. (E.g. value 1.05 is sent as 105) 1 to 16-bit digital values: 1 0 selector msb selector lsb data 2 bytes 16-bit binary value. 16-bit digital values can carry one or more bits of digital data. The data may be interpreted as one or more separate bits or one HEX value. Bit write (BWR) message: 1 0 selector msb selector lsb i i i i x x x x iiii = bit number (0..15) xxxx xxxx xxx = not used x x x x x x x d d = bit value (0 or 1) Bit write message is used to set or reset one bit of a 16-bit bit string. The bit string is anyhow identified with one NV selector. Note: All the multi byte structures are sent msb-byte first and lsb-byte as last byte (in Motorola fashion). 10

Clock synchronization network variables The real-time clock of the LON devices is synchronized by broadcasting network variables nv_warning and nv_clock to the network one after another. The delay between nv_warning Network Variable nv_warning: and nv_clock may not exceed 100 milliseconds. The delays under approx. 30 ms cause significant amount of clock messages to be missed. 1 0 selector msb default value for selector lsb the selector is 2FFFH delay delay between sending the warning message and the time synch message (30 100 ms) Network Variable nv_clock: 1 0 selector msb default value for selector lsb the selector is 2FFFH 1 year year in binary format 2 3 month month in binary format 4 day day in binary format 5 hour hour in binary format 6 minute minute in binary format 7 second second in binary format 8 milliseconds and milliseconds and hundreds of microseconds 9 100 microseconds as 16-bit binary number 11

Explicit messages Explicit messages are used to transfer the "value attribute" and other attributes of the data objects. The format of the application data in these messages is one of the following: SPA-bus format, LSG-format, AFD-format or DMP-format. General message format The data part of the explicit messages contain the following: 0 message code (<80H) data 0...229 bytes The format of the data part of the message is defined by the message code. The special explicit messages formats used in our protection and control systems are the following: - LSG format event messages 40H - transparent SPA-bus messages 41H - LSG format configuration messages 43H - AFD messages 4CH - DMP messages 4AH LSG format event messages Event messages containing time-stamped event information from a device may be sent using explicit messages with message code 40H. The format of these messages is the following: 0 0 40H Message code 40H. 1 event type (8 bits) 2 object - SPA-event id. (type 0,7,8) or 3 address (16 bits) - 00 + 14-bit NV selector (type 1,2) 4-32-bit integer (scale 1000) or 5 event data - 16-bit mask + 16-bit data or 6 (32 bits) - 16-bit slave number + 16-bit data 7 8 year (msb) 9 year (lsb) 10 month 11 day 12 hour 13 minute 14 second Bytes 15 and 16 contains a 16 bit number 15 ms and 100 us (msb) including milliseconds and hundreds of 16 ms and 100 us (lsb) microseconds. 12

LSG format event messages (continued) The following event types are used: Type code Event type 0 SPA-bus event, event generated from SPA-bus events. 1 Analog event, event with 32 bit analog data value. The data value is a 32-bit integer value scaled with 1000. 2 Digital event, event with 16 bit data. Bytes 4,5 contain 16-bit mask indicating the changed bits and bytes 6,7 contain the 16-bit data itself. 7 SPA-bus analog event, event generated from SPA-bus analog event. Analog data in data part (32-bit integer scaled with 1000). 8 Extended SPA-bus event, event generated from SPA-bus events. Full SPA-bus slave number in data part bytes 4 and 5. With types 0 and 7 the the SPA-event identification (bytes 2,3) is as follows: - 1 + 3-bit SPA slave index + 6-bit channel number + 6-bit event number With type 8 the the SPA-event identification (bytes 2,3) is as follows: - 1 + 9-bit channel number + 6-bit event number Transparent SPA-bus messages SPA-bus messages may be sent using explicit messages with message code 41H. Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are sent using the same message code. It is recommended that one device sends out only one message at a time and waits for the reply before sending the next message. 0 41H Message code 41H. ">" or "<" Message start character ">" in messages to device ASCII character message following the "<" in reply messages from device rules of the SPA-bus protocol ":" End of data part/header. CC Two checksum characters. 0DH Message end character, carriage return. Long SPA-bus messages are sent in pieces at max. 45 bytes. Each separately sent piece contains end characters '&', 0DH, 0AH (except the last piece. 13

LSG format configuration messages LSG cofiguration messages are sent using explicit messages with message code 43H. These messages are used to send and read configuration data of LON/SPA-gateways. The same message code can be used for similiar purposes also with other devices. 0 43H Message code 43H. Command/response message composed of ASCII characters. 0DH Command/response end character, carriage return. LON bus performance figures The following figures can be used as basis when calculating the performance of the bus. The actual performance in a specific system depends on the type of devices that are used as part of the network: types of network interfaces of the devices, types of possible gateways, routers, etc. Also the software implementation of the devices in question affect the final performance. The performace should be separately calculated for each system, if detailed performance figures are required. When we assume that the LON bus speed is 1.25 Mbits/s and the average packet size is less than 10 bytes then the following can be said. The bus can handle a load of up to 500 packets per second. A node on the network can handle a maximum load of 300 packets per second. One node can receive up to 150 acknowledged messages per second. One node can send up to 70 acknowledged messages per second. If collision detection and priority is used then the packet throughput time through the network is less than 20ms (assuming no routers on the message path). The best case throughput time is about 6 ms. To assure the proper performance of the bus the following precautions should be made: use as short messages as possible for frequently sent data; send long messages in smaller pieces; allocate as many communication buffers as possible in the nodes, gateways and routers; use routers to partition the network in an appropriate way. Referencies: LonTalk Protocol Specification, Version 3.0, document number 078-0125-01A. Echelon Corporation, 1994. Neuron Chip Distributed Communications and Control Processors MC143150, MC143120. Motorola Semiconductor Technical Data. Motorola Inc, 1994. SPA-bus Communication Protocol V2.4, document number 34 SPACOM 3EN1C. ABB Asea Brown Boveri, 1992. SPA-ZC 100, LON/SPA-gateway User's Guide. ABB Asea Brown Boveri, 1994. LonMark Layers 1-6 Interoperability Guidelines, Version 1.3, document number 078-0014- 01D. Echelon corporation 1994. LonMark Application Layer Interoperability Guidelines, Version 1.3, document number 078-0120-01A. Echelon corporation 1994. LonMark Network Management Interoperability Guidelines. Echelon corporation 1995. The SNVT Master List and Programmer's Guide. Echelon corporation, April 1994. LonTalk Response Time Measurements, Lon Works Enginering Bulletin. Echelon Corporation, March 1992. Application Format Definitions, AFD, document number 1MRK 000023-98. ABB Asea Brown Boveri, 1994. 14

15

ABB Oy Substation Automation P.O.Box 699 FIN-65101 VAASA Finland Tel. +358 (0)10 22 11 Fax.+358 (0)10 22 41094 www.abb.com/substationautomation 1MRS 750035-MTD EN