RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

Similar documents
RTD-NET Installation Instructions

RTD-W Installation Instructions

Procon A1M. INSTALLATION MANUAL Version MITSUBISHI ELECTRIC FOR INSTALLERS

IO-INTERFACE. Procon. INSTALLATION MANUAL Version 1.01 MITSUBISHI ELECTRIC FOR INSTALLERS

FCU-4 FAN COIL CONTROLLER

LRC-XDP. LRC-XDP Datasheet. LRC-XDP Display Panel for Toshiba air-conditioning units. Description

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Installation Instructions. Procon IP-32M wir-1_ MITSUBISHI ELECTRIC

RXTP ROOM TEMPERATURE

MOD-RI Room Interface Modules with Modbus

Communicative controller for VAV systems

RXTH DUAL ROOM SENSOR / SWITCH

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning

Non-communicating room controllers

HLS34 Modbus FCU/VAV Controllers installation instructions

Daikin HVAC Controls Guide Specification

FCU-4 FAN COIL CONTROLLER

Carbon Monoxide Sensor - ModBus

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

UNIVERSAL CURRENT CONVERTER

UCU Room Display. Operation Modes. Features. Applications DATASHEET

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Modbus Interface Module

Room Temperature Controller

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Daikin HVAC Controls Guide Specification

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS).

LLR-MOD Modbus Light Level and Occupancy Sensor

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors.

Room unit with PPS2 interface

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss.

Temperature controller Ducted systems

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

Non-communicating room controllers

Measure & Control Temperature & CO2 levels with analog & digital I/O

Model HM-535 Power Supply Installation and Service Instructions

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

Small distributed I/O module

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

PoolPak SWHP Series ECCIII Modbus RTU BAS Interface DOCUMENT #: SVW05-ECCIIIMODBUS

Installation & Operation and Maintenance

FCU-MULTI Modbus Fan Coil Unit Controller

Room controller STRA-17

Procon MelcoRETAIL MINI

Copyright: December 2017 Nidec Issue: E

ASTAT XB/XBm Remote Operator

Room Temperature Controller

IntesisBox PA-AC-MBS-1

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

Dip Switch settings.

RS-WMB, RD-WMB Wallbus Room Sensors and Displays

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100

RHR-MOD Combined Room Temperature and Humidity Sensors (Controllers) with Modbus

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

STRA-17 Room controller. Installation and maintenance manual. Content

TER-MOD Active Room Temperature Sensors (Controllers) with Modbus

INTERFACE SPECIFICATION

Uponor Smatrix Move PRO Controller X-159 Modbus RTU interface

Room unit with PPS2 interface

CTR21, CTR22, CTR23, and CTR24 Wall Modules

Room Temperature Controllers

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Submittal Data Sheet intelligent Touch Manager DCM601A71

BAPI-Stat 4MB Modbus Temp or Temp/Humidity Sensor

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

AX-CNDR-HCE Digital room controller, 0-10V heating, cooling and fanspeed

Room unit with PPS2 interface

thanos RS485 Modbus Application Functions Multifunction Room Operating Unit Datasheet

Semi flush-mounted room temperature controllers with LCD

Strain Gauge Converter

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

Installation, Start-up and Operating Instructions

Room unit with PPS2 interface

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

1. Safety Danger Warnings Earthing and earth fault protection... 4

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

Master room unit for RRV controllers

Optidrive Applications Support Library

Warranty. Warning. Copyright. Contact Us

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Using the LR-HVAC-230-S Thermostat w/ HomeWorks QS

Supplementary operating instructions for your air curtain system Controller TMC 500

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

Duct humidity and temperature sensor for all HVAC duct applications. Designed for control and monitoring applications.

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

MODEL: R3-NE1. Remote I/O R3 Series. ETHERNET INTERFACE MODULE (Modbus/TCP) 27.5 (1.08)

Temperature Controller

Transcription:

RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B

LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V S2 DB+ DA- GND J1 SW1 2 J5 RS485 D-BUS DB DA GND + - DB(+) DA(-) GND DB(+) DA(-) GND J5 RS485 D-BUS DB DA GND + - 1 A B C ADDRESS 0 ADDRESS 1 2 21070-1.07.04 RTD-RA Installation Instructions 3

ADDRESS 0 ADDRESS 1 ADDRESS 2 ADDRESS 3 ADDRESS 4 ADDRESS 5 ADDRESS 6 ADDRESS 7 ADDRESS 8 ADDRESS 9 ADDRESS 10 ADDRESS 11 ADDRESS 12 ADDRESS 13 ADDRESS 14 ADDRESS 15 ADDRESS 16 ADDRESS 17 ADDRESS 18 ADDRESS 19 ADDRESS 20 ADDRESS 21 ADDRESS 22 ADDRESS 23 ADDRESS 24 ADDRESS 25 ADDRESS 26 ADDRESS 27 ADDRESS 28 ADDRESS 29 ADDRESS 30 ADDRESS 31 ADDRESS 32 ADDRESS 33 ADDRESS 34 ADDRESS 35 ADDRESS 36 ADDRESS 37 ADDRESS 38 ADDRESS 39 ADDRESS 40 ADDRESS 41 ADDRESS 42 ADDRESS 43 ADDRESS 44 ADDRESS 45 ADDRESS 46 ADDRESS 47 ADDRESS 48 ADDRESS 49 ADDRESS 50 ADDRESS 51 ADDRESS 52 ADDRESS 53 ADDRESS 54 ADDRESS 55 ADDRESS 56 ADDRESS 57 ADDRESS 58 ADDRESS 59 ADDRESS 60 ADDRESS 61 ADDRESS 62 ADDRESS 63 4 21070-1.07.04 RTD-RA Installation Instructions 3

5a 5b 5c 6a 6b 7a 7b 7c 4 21070-1.07.04 RTD-RA Installation Instructions

Warnings and Cautions Specifications All cable connections to the device must be adequately secured by suitable strain relief fasteners. Cables supplied with strain relief bands must be fitted in the corresponding cable guide slot with the strain relief band inside of the enclosure. The RTD must either be mounted in a suitable metal enclosure or plastic enclosure with a flammability rating of at least IEC60695-11-10 V-1. Do not install it inside the air-conditioning unit. In all cases access by non-qualified persons must be prevented (the enclosure may not accessible without a tool). The unit can be mounted horizontally or vertically. RS485 Cables must use stranded 24awg shielded or unshielded twisted pair to Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections DB,DA and an extra core for connection GND. Install RS485 cable to J5 terminals as shown in Figure 3. Cable connections to J6 inputs must be 0.5 to 0.75 mm 2 multi-stranded screened twisted pair. The screen must be earthed at one end only. The maximum distance from the RTD to the input source is 200m. Electrical Environmental Supply 15V DC, 50mA Regulated Temperature Power <1.0VA Storage -10oC to 50oC Connectors Network Rising clamp to 0.75mm2 cable Operation Humidity Inputs 0oC to 50oC 0-90% RH non-condensing RS485 <500m Volt-Free Contact S1..S2 5V, 1mA Your product is marked with the symbol shown to the left. This symbol on the product indicates that this product must not be disposed of with your other household waste. Inappropriate disposal may be harmful. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment. Units must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information. Observe precautions for handling Electrostatic Sensitive Devices Additional information, including Modbus configuration and Fault Codes are available from www.realtime-controls.co.uk/rtd 21070-1.07.04 RTD-RA Installation Instructions EN 5

Installation Instructions S21 CNECTI (FIGURE 2) The RTD-RA is a monitoring and control interface for the Room Airconditioner range of air-conditioning units. The interface is compatible with the indoor units that have a S21 remote controller network connection. Control functions include: STAND ALE MODE: Allows energy-efficient operation of a Room Air-conditioner by restricting user operating ranges and unit locked off defined by volt-free contact input. MODBUS SLAVE MODE: Allows control and monitoring of unit operation using RS485 Modbus commands. RTD CLE MODE: Configures the RTD-RA to duplicate the operating settings of another RTD or RTD-RA device on the RS485 network. Allows creation of group controlled devices. RTD-10 DUTY/STANDBY SLAVE: Configures the RTD-RA to operate in an RTD-10 Duty/Standby network. An RTD-10 Master controlling Skyair or VRV units can be integrated with one or more Room Air Conditioners in a Duty/Standby configuration. RTD-20 RETAIL CTROL MODE: The RTD-RA can be integrated into an RTD-20 Retail Control network. The RTD-RA can be configured to operate as a User Control Zone or to operate in Clone Mode and duplicate the control settings from anther device on the network. The RTD-RA is supplied with a pre-fitted lead for power and communication with the Room Air-conditioner. The lead allows a maximum distance of 950mm from RTD-RA to the connection point in the indoor unit The lead must be fitted and secured through suitable access points in the air-conditioner and the connector must be inserted into port S21 on the Room Air-conditioner indoor unit control PCB. The S21 lead enters the RTD-RA through Port D on the enclosure as shown in Figure 1, the lead is supplied pre-fitted to J1 on the RTD-RA PCB. The fitted strain relief band on the cable must be located on the inside of the enclosure. RS485 NETWORK INSTALLATI (FIGURE 3) The RS485 D-Bus network requires a twisted pair cable connecting terminals DB(+) and DA(-) on each RTD-RA. Terminal DB must be connected to all other DB terminals. Terminal DA must be connected to all other DA terminals. In addition the common terminal GND on all devices must be connected together. If a shielded cable is used then the shield can be used for this purpose. It is recommended that the GND connection is connected to local Earth at one point only. The network must be installed as a daisy-chained point-to-point Bus configuration, Star and Ring connections must NOT be used. The RS485 Network lead must be connected to terminals J5 on the RTD-RA PCB and must be fitted through Port B on the enclosure as shown in Figure 1. The PCB mounted strain-relief must be used to secure the network cable. Cables must have a maximum outside diameter of 5mm. 6 EN 21070-1.07.04 RTD-RA Installation Instructions

RS485 NETWORK LENGTH Standard installation for total network distances of up to 500m can be achieved following the basic daisy-chaining method showed in the above Figure 3. The network can be extended further using RS485 repeaters. LED FUNCTIALITY When the RTD-RA is powered up, or if it looses communication with the Remote Controller the RTD-RA enters A/C Unit search mode. Led behaviour is shown in the following figures Power-Up sequence: Factory Configuration Power-Up sequence: Custom Configuration A/c Unit Search. After power-up and during unit configuration No Fault State Unit Fault Device configuration error AC Unit Missing (U5 Fault) RS485 Communications timeout LED Key: Figure 5a Figure 5b Figure 5c Figure 6a Figure 6b Figure 7a Figure 7b Figure 7c OFF Flashing RTD-RA STANDARD INPUTS Inputs S1 and S2 are wired between the labelled Sensor terminal and the adjacent 0V terminal on the same connector block S1 and S2 cables must be 0.5 to 0.75mm 2 multi-stranded screened twisted pair. The screen must be earthed at one end only. The maximum distance from the RTD-RA to the input source is 200m. S1 and S2 cables should be connected to terminals J6 on the RTD-RA PCB and must be fitted through Port A on the enclosure as shown in Figure 1. The PCB mounted strain-relief must be used to secure the network cable. Cables must have a maximum outside diameter of 5mm. It is recommended that volt-free contacts or switch mechanisms have gold plated contacts to ensure a low resistance circuit when the switch is made. ADDRESSING The RTD-RA has the facility to create control groups using multiple RTDs connected together on the RS485 D-Bus network. In standard configuration up to 64 RTD-RA devices can be connected together. Each RTD is assigned a D-Bus address using the configuration switches SW1.3 to SW1.8. (FIGURE 4). EN 21070-1.07.04 RTD-RA Installation Instructions 7

MODBUS CFIGURATI Different data types are returned using specific conventions Network 3 wire RS485 Mode Modbus RTU Slave Baud 9600* Parity None* Stop bits 1 Register Base 0 *RTD interfaces can be configured with different baud rate and parity settings if required Modbus address range 0 to 63 set using SW1 (Figure 5). Details of the Modbus Protocol can be found in the Modicon Modbus Protocol Reference Guide available on the internet. MODBUS REGISTERS The RTD-RA supports two types of register, analogue Holding Registers and analogue Input Registers. Register Addresses are 0 based in the range 0..65535. Register Type Access Function Holding Register Read/Write Control and Command Registers Input Register Read Only Readback and Monitoring Registers All analogue and digital values are accessed through these registers. All register values are 2 byte (16 bit) values. Data Type Range Convention Digital 0..1 0=FALSE, 1=TRUE Integer 0..65535 No scaling required Temperature 0..65535 Temperatures values are generally returned multiplied by 100 to allow greater precision. To allow for negative temperature the value is returned as a signed integer, this means that any value greater than 32767 must be converted into a negative value by subtracting 65536. Examples: A readback value of 2150 is a positive temperature so: 2150 / 100 = 21.50 o C A readback value of 65036 is a negative temperature so: 65036 65536 = -500-500 / 100 = -5.00 o C Registers are accessed using standard Modbus functions. The following four functions are supported by the RTD interface. Function Code (hex code) Function Name 03 (03h) Read Holding Registers 1..10 04 (04h) Read Input Registers 1..10 06 (06h) Preset Single Holding Register 1 16 (10h) Preset Multiple Holding Register Register Count 8 EN 21070-1.07.04 RTD-RA Installation Instructions 1..10 In this document, Holding registers are written as H0010 where H indicates Holding register and 0010 indicates the register address 0010. Similarly Input registers are referred to as I0010 where I indicates an Input register

STAND-ALE MODE Address 0 The RTD-RA will operate in Stand-Alone Mode if SW1.3 to SW1.8 are set to OFF. S1 Unlock Only User Setpoint Control Input Name Range (default) S1 Unlock+ Wide deadband Mode it is unlocked. Unoccupied Temperature Protection (S2) If a Short-Circuit is applied to Input S2 then the unit will be overridden and operate in Heating if the room temperature falls below 12 C at any point, even if input S1 is Open-Circuit. Heating will continue to operate until the room temperature rises above 15 C. If room temperature rises above 28 C the unit will operate in Cooling until temperature falls below 25 C. Extended Mode (S2) If a 10kΩ resistor* is applied to input S2 then the RTD-RA will operate in Extended Mode. In Extended Mode the Unoccupied Temperature Protection function is activated with an extended temperature range as shown in Table 1. If Wide Deadband mode is selected the Wide Deadband Temperature range is also adjusted as shown in Table 1. *A 10k Resistor is supplied with the RTD-RA, attached to the front of the installation manual S1 Unit Unlock Open Circuit: Unit OFF + Locked Closed Circuit: Unit Unlock (+Switch ) S2 Unoccupied Temp/ Extended Mode Open Circuit: Not Active Closed Circuit: Standard Unoccupied Temperature Protection 10k Resistor: Extended Mode + Unoccupied Temperature Protection Standard Mode Extended Mode Low Temperature Mode On <12 C <5 C Low Temperature Mode Off >15 C >12 C High Temperature Mode On >28 C >32 C High Temperature Mode Off <25 C <29 C Unit Lock (S1) If Input S1 is Open-Circuit then the unit will be locked OFF and will not operate except during Unoccupied Temperature Protection. If Input S1 is Closed-Circuit then the unit can be switched on by the User. DIP Switch SW1.1 determines the operation of the unit when S1 is initially Closed-Circuit. If SW1.1 is OFF then the unit will unlock and remain OFF. If SW1.1 is then the unit will be switched when Wide Deadband Heat Setpoint 21 C 21 C Wide Deadband Cool Setpoint 25 C 28 C Table 1. WIDE DEADBAND MODE Setting DIP Switch SW1.2 activates Wide Deadband mode. In this mode the Setpoint and Operating Mode of the Room Air-conditioner 21070-1.07.04 RTD-RA Installation Instructions EN 9

are determined by the RTD-RA. The User can switch the unit and OFF and change the Louvre and Fanspeed settings, however changes to Setpoint and Mode are overridden. The Room Temperature is monitored and the unit is switched between FAN and HEAT or COOL if the temperature is outside of the Wide Deadband Heating or Cooling setpoints, determined by selection of Standard or Extended Mode. Modbus Slave Operation Address >0 If the RTD-RA Modbus Address is configured to a value of 1 or higher then the RTD-RA will function as a Modbus Slave device and all standalone functions will be disabled. All control commands are written from Modbus. MODBUS MASTER TIMEOUT The RTD-RA can be configured to operate with an optional Modbus Master timeout. In this configuration if no Holding Register writes occur for a period of 120 seconds then a timeout event will occur and all A/C units will be switched on with their current settings. In a timeout condition the RTD Leds will indicate an RS485 Communications Timeout as illustrated in the LED Functionality section of this datasheet. SW1 DIP Switch settings to enable or disable Modbus Master Timeout are shown in the following table. Switch Setting Function No Timeout Timeout if no Holding Register WRITE command for 120 seconds. All units switched with current settings. Remote controllers UNLOCKED. Timeout if no Holding Register WRITE command for 120 seconds. All units switched with current settings. Remote control LOCK state unchanged. 10 EN 21070-1.07.04 RTD-RA Installation Instructions

Control Functions UNIT CTROL The RTD-RA can be used to control all of the operating functions of the air-conditioning system that are available from a standard remote controller. All control registers are analogue Holding Registers. Holding Register Name Range H0001 Setpoint Heat: 10..30, Cool: 18..32 1 H0002 Fanspeed 0..5 (0: Auto, 1:Fan 1, 2: Fan 2, 3: Fan 3, 4: Fan 4, 5: Fan 5 2 ) H0003 Mode 0..4 (0:Auto, 1:Heat, 2:Fan, 3:Cool, 4:Dry) H0004 Louvre 0..1 (0:Stop, 1:Swing) 2:Local Unlocked Updates to holding registers are not sent to the unit. 3:OnChange Unlocked Unit setting is updated when a holding register WRITE occurs only if the value CHANGES. The Last Touched update mode allows updates from local control or Modbus registers. This requires that WRITES to the Modbus holding register only occur when a change is made. If the Modbus master repeatedly writes the value then this will overwrite the user setting. The On Change update mode can be used if repeated writes occur, in which case updates are only sent to the AC unit if the written value changes. The Global Update register H0010 can be used to set the update mode. H0005 OnOff 0..1 (0:Off, 1:On) H0037 Force Thermo Off 0..1 (0:Enable Thermo, 1:Thermo Off) Holding Register Name Lock Mode* 1 Setpoint Ranges may vary. Check model for supported ranges. 2 Certain models support less than 5 fan speeds. Check model for supported speeds. CTROL UPDATE MODE A Global Update Register determines how the control commands update the unit and if local control operation is locked or unlocked. Four update modes are available: Update Mode Keypad Button(s) Functionality 0:LastTouch Unlocked Unit setting is updated when a holding register WRITE occurs even if the value is unchanged. 1:Central Locked The corresponding keypad buttons are locked. The value in the holding register is repeatedly written to the unit. H0010 Global Update 0:LastTouch,1:Central,2:Local,3:OnChange The default settings on power up are all fields in Last Touch mode. CTROL LIMITING The Control Limit registers allow adjustment from the remote controller or central controller to be limited to specified ranges. The setpoint can be optionally limited to minimum and maximum specified values. Fanspeed, Mode and Louvre settings can also be limited to specific settings using an inhibit value. If the limit values are set to 0 then no limit is applied. Holding Register 21070-1.07.04 RTD-RA Installation Instructions EN 11 Name Range H0020 Setpoint Min 16..32, 0 = No Limit H0021 Setpoint Max 16..32, 0 = No Limit

H0022 Fanspeed Inhibit 0 = No Inhibit, else Inhibit Value H0023 Mode Inhibit 0 = No Inhibit, else Inhibit Value H0024 Louvre Inhibit 0 = No Inhibit, else Inhibit Value Fanspeed, Mode and Louvre inhibit values are calculated by adding the inhibit values for each setting to be inhibited. The values are as follows Fan Inhibit Mode Inhibit Louvre Inhibit Fanspeed Inhibit Value Auto 1 Fan 1 2 Fan 2 4 Fan 3 8 Fan 4 16 Fan 5 32 Run Mode Inhibit Value AUTO 1 HEAT 2 FAN 4 COOL 8 DRY 16 Louvre Position Inhibit Value Stop 1 Swing 2 Examples: To limit the Mode setting to Heat, Cool and Fan: Mode Inhibit Value = AUTO + FAN + DRY = (1 + 4 + 16) = 21 Readback Data All readback data is available in analogue Input Registers. UNIT READBACK Unit data is available for each of the indoor units on the P1,P2 network. Unit Input registers are numbered using the indoor unit numbering in the range 1 to 16 x 100 added to an offset relating to a specific feature. Input Register Name Range Notes I0121 Is Fault 0..1 0: No Unit Fault, 1: Unit in Fault I0122 Fault Code 0..65535 255: No Fault, else fault code 12 EN 21070-1.07.04 RTD-RA Installation Instructions I0123 Return Air Temperature Degrees C x 100 Unit Return Air Sensor Value I0130 Thermo On 0..2 0:Idle/Fan, 1:Heating, 2:Cooling I0131 FAULT CODES Coil Inlet Temperature Degrees C x 100 Coil Inlet Temperature Fault codes are encoded using a standard table to allow standard Daikin fault codes to be generated from the readback value. The no fault value is 255.

Special fault codes generated by the RTD are as follows Code Value Meaning 0 Waiting for data 255 No Fault 14384 (80) Group Fault, timeout on no units found All other codes are Daikin fault codes. The full table of fault code values is available from http://www.realtime-controls.co.uk/rtd Fault codes returned from a Modbus Input register are 16 bit values. The fault code is encoded in the 16 bit value by encoding the two 8 bit fault characters in the high and low byte parts of the 16 bit value. Each of the 8 bit values represents an ASCII text character. 16 Bit Register Value 15 8 7 0 8 Bit High Byte 8 Bit Low Byte RTD Clone Mode Input Name Range (default) S1 S2 SPARE Clone Mode Open Circuit: Modbus Slave Mode Closed Circuit: Clone Mode Active Address >0 If input S2 is Closed-Circuit then the RTD-RA will operate in RTD Clone Mode. This mode disables Modbus Slave Mode. In RTD Clone Mode the RTD-RA will search the network for an RTD device at the next lower address, so if the RTD-RA is Address 1, then it will search for a Clone Master RTD at Address 0. If an RTD device is detected, including another RTD-RA, then the RTD-RA will activate Clone Operation, local user control is disabled and the control functions Setpoint, Fanspeed, Mode, Louvre, On/Off and Force Thermo Off will be copied from the Clone Master. 15 8 7 0 Multiple RTD-RAs can operate in Clone Mode on a network, allowing group control from a single RTD or RTD-RA Clone Master. Example: ASCII Character 1 ASCII Character 2 A fault code value of 16689 is returned. HighByte(16689) = 65 = ASCII Character A LowByte(16689) = 49 = ASCII Character 1 Fault Code: A1 21070-1.07.04 RTD-RA Installation Instructions EN 13

Address 1..8 RTD-10 Duty/Standby Slave Operation RTD-20 USER CTROL Address >0 ZE When configured for RTD-10 Duty/Standby Slave Operation the RTD- RA should be configured with an address in the range 1 to 8 as shown in Figure 4. An RTD-10 configured as a Duty/Standby Master will monitor the fault state and temperature condition of the RTD-RA and will operate the RTD-RA as a Duty/Standby Slave as documented in the RTD-10 Installation Manual (see www.realtime-controls.co.uk/ rtd). The RTD-10 Duty/Standby Master will support up to 7 slaves in any combination of RTD-10 and RTD-RA. A/C UNIT OPERATI The RTD-RA can be configured to operate as an RTD-20 User Control Zone (UCZ). RTD-20 UCZ Mode is activated by adding the RTD-RA to an RTD-20 Retail Control network, or by inserting a 10k resistor* into S1 to activate stand-alone UCZ operation. A User Control Zone allows users to alter unit operation during the OCCUPIED period. The Zone Primary co-ordinates the User Control Zone and ensures the zone is shut down when UNOCCUPIED or during FIRE conditions. User Control zones can be configured to support areas with permanent or temporary occupancy. *A 10k Resistor is supplied with the RTD-RA, attached to the front of the installation manual The RTD-RA unit mode is set to COOL and A/C unit operation is completely locked to prevent local operation. The setpoint, fanspeed and louvre operation will be transmitted from the RTD-10 Master. If communications with the master is interrupted, after 120 seconds the RTD-RA will operate the A/C unit in COOL with 21C setpoint. No Timed Off Occupancy Zone Timed Off Trade Zone When operating in an RTD-20 network, when the zone is UNOCCUPIED the A/C unit is locked and switched off. When unlocked the A/C unit is restricted to allow only AUTO and FAN modes. If other modes are selected the mode will be overridden. At the start of occupancy the mode is always reset to AUTO. Setpoints are also limited to the Retail Primary configured range See the RTD-20 Installation Manual for configuration information for the RTD-20 Retail Primary Zone. 14 EN 21070-1.07.04 RTD-RA Installation Instructions

Input Name Range (default) S1 Min Comfort/ Stand- Alone Open Circuit: Not Active Closed Circuit: Minimum Comfort in Timed Mode 10k Resistor: Stand-alone Operation Multiple RTD-RAs can operate in Clone Mode on a network, allowing group control from a single RTD or RTD-RA Clone Master. S2 Clone Mode Open Circuit: User Control Zone Closed Circuit: Clone Mode Timed Zone (DIP SW1.1) If SW1.1 is then the UCZ will operate as a timed zone based on unit operation, after 1 hour of operation the unit will switch off. When operating as timed User Control Zone the until will be initially OFF at the start of occupancy, manually switching the unit on will start the timed operation User Zone Type (DIP SW1.2) If SW1.2 is OFF then the unit will unlock and switch using the OCCUPIED time signal from the Zone Primary. If SW1.2 is the unit will unlock and switch using the TRADE time signal from the Zone Primary. Minimum Comfort Control (S1) When active Minimum Comfort control will maintain the room to Setpoint Range +/-2 C when the Zone Primary generates an OCCUPIED signal, even if the User Control Zone is currently OFF or controlled to the TRADE time signal. Clone Mode(S2) If input S2 is Closed-Circuit then the RTD-RA will operate in Clone Mode instead of UCZ mode. In RTD Clone Mode the RTD-RA will search the network for an RTD device at the next lower address, so if the RTD-RA is Address 1, then it will search for a Clone Master RTD at Address 0. If an RTD device is detected, including another RTD-RA, then the RTD-RA will activate Clone Operation, local user control is disabled and the control functions Setpoint, Fanspeed, Mode, Louvre, On/Off and Force Thermo Off will be copied from the Clone Master. The RTD-RA will still transmit data to the Retail Primary. 21070-1.07.04 RTD-RA Installation Instructions 15 EN