Thermistor motor protection relay CM-MSS.11

Similar documents
Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

Thermistor motor protection relay CM-MSS.31

Thermistor motor protection relay CM-MSS.41

Thermistor motor protection relay CM-MSS.21

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relay CM-MSS.41

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Switching relay CT-IRE with 1 c/o (SPDT) contact

Messaging module CP-C MM

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ERS.21

Electronic timer CT-ARS.11

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

Power supply CP-E 48/1.25 Primary switch mode power supply

Power supply CP-D 12/2.1 Primary switch mode power supply

Electronic timer CT-ERD.12

Redundancy unit CP-A RU

Power supply CP-E 24/0.75 Primary switch mode power supply

Contact protection relay

Three-phase monitoring relay

Power supply CP-E 24/10.0 Primary switch mode power supply

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Electronic timer CT-AHD.22

Boxed interface relays and optocouplers R600 Boxed slim relays, optocouplers and accessories

Redundancy unit CP-D RU Accessory for CP range power supplies (e.g. switch mode power supplies CP-D range)

Pluggable interface relays and optocouplers CR-P Pcb relays, optocouplers and accessories

Power supply CP-C 24/5.0

Pluggable interface relays CR-P Pcb relays

Accessories for pluggable interface relays CR-P Sockets

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Pluggable interface relays CR-M Miniature relays

Power supply CP-C 24/5.0

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

ABB i-bus KNX HCC/S Heating/cooling circuit controller

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

ABB i-bus KNX BCI/S Boiler/Chiller Interface

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

MINI-PS AC/10-15DC/8

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

TU531, TU532 Terminal Unit

Accessories for pluggable interface relays CR-P, CR-M Pluggable function module

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Accessories for pluggable interface relays CR-U Pluggable function modules

Output Voltage* (nom.)(adjustable)

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 07/2006

Bulletin 817 Thermistor Protection Relay

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

TF501, TF521 Terminal Bases

AO523 Analog Input Module

PHOENIX CONTACT Features

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

DI572 Digital Input Module

DC561, digital input/output module,

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

QUINT-BUFFER/24DC/24DC/40

DC562, digital input/output module,

Output Voltage* (nom.)(adjustable)

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

AI561 Analog Input Module

DI561 Digital Input Module

TRIO-DIODE/12-24DC/2X10/1X20

DX561 Digital Input/Output Module

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

RMCN22BD Analog Converter ma - for Zelio Analog

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

QUINT-PS-3x AC/24DC/10

Transcription:

Data sheet Thermistor motor protection relay CM-MSS.11 The thermistor motor protection relay CM-MSS.11 monitors the winding temperature of motors and protects them from overheating, overload and insufficient cooling. The device is available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 005 V0014 Characteristics 1 measuring circuit Automatic reset Dynamic interrupted wire detection Non-volatile fault storage LEDs to distinguish between different failure causes Overvoltage protected supply and measuring inputs According to the product standard IEC 60947-8 Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 22.5 mm (0.89 in) width Various certifications and approvals (see overview, document no. 2CDC112248D0201) Order data Type Rated control supply voltage Output contacts Connection technology Order code CM-MSS.11P 24-240 V AC/DC 1 n/o and 1 n/c contact Push-in terminals 1SVR740720R1400 CM-MSS.11S Screw terminals 1SVR730720R1400

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CM-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. 2 - Thermistor motor protection relay CM-MSS.11 Data sheet

Functions Operating controls 1 Indication of operational states with LEDs U: green LED - Status indication of control supply voltage V Control supply voltage applied F: red LED - Fault message R: yellow LED - Status indication of the output relay 2CDC 251 005 V0014 1 Application / Monitoring function The thermistor motor protection relay CM-MSS monitors the winding temperature and thus protects the motor from overheating, overload and insufficient cooling in accordance to the product standard IEC 60947-8, control units for built-in thermal protection (PTC) for rotating electrical machines. ATEX Suitably selected and adjusted devices of this type are necessary for the safe operation of explosion-protected motors. Only the sensor line is conducted into the explosive atmosphere. The motor protection relay itself must be installed outside the potentially explosive atmospheres. II (2) G Marking: I II (2) D Operating mode The thermistor motor protection relay CM-MSS.11 is used to monitor the temperature of motors or generators equipped with PTC resistor sensors type A. The sensors are built-in into the motor windings, measuring the motor heating. In case of an increase of the temperature in the motor, the resistance of the PTC sensors will increase as well. If the motor heatsup excessively (>2.83 kh) the output relays de-energize and the corresponding LED displays the overtemperature. A reset is only possible after cooling down of the motor (<1.1 kh) or after a wire interruption within the sensor circuit has been removed. Dynamic interrupted wire detection During the operation the device is permanently monitoring the measuring circuit. If the resistance in the measuring circuit rises, the device distinguishes if there is an overtemperature or an interrupted wire. Then the output relays de-energize. Reset Once the fault has been rectified and the measured value has dropped below the release threshold, an automatic reset is executed. Data sheet Thermistor motor protection relay CM-MSS.11-3

Electrical connection A1 13 21 T2 T1 T1 A1 14 22 A1 A2 Control supply voltage 13 14 n/o contact 21 22 n/c contact T1 T2 Measuring circuit ϑ T2 A2 13 21 14 22 A2 2CDC 252 018 F0014 Connection diagram CM-MSS.11 Indication of operational states LEDs, status information and fault messages (in order of priority) Operational State U: LED green F: LED red R: LED yellow Absence of control supply voltage OFF OFF OFF Internal fault 1) OFF W W Internal fault 1) X X X Control supply voltage not within the tolerance range X V OFF Interrupted wire V Z OFF Overtemperature V V OFF No fault V OFF V 1) Restart the device. If after restart the same fault is indicated, replace the device 4 - Thermistor motor protection relay CM-MSS.11 Data sheet

Function diagram A1-A2 2830 Ω 1100 Ω R [Ω] 13-14 21-22 1 2 1 Tripping caused by overtemperature 2 Control supply voltage interrupted 2CDC 252 037 F0214 Example of application Circuit diagram V+ A1 14 22 T1 M 3~ µc t T2 21 13 V- A2 2CDC 252 023 F0014 Data sheet Thermistor motor protection relay CM-MSS.11-5

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuit Supply circuit Rated control supply voltage U s A1-A2 24-240 V AC/DC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 15-400 Hz Typical current / power consumption 24 V AC/DC 29 ma / 0.55 VA 220-240 V AC 11 ma / 1.6 VA Electrical insulation between supply circuit and measuring circuit yes Power failure buffering time 20 ms Measuring circuit / Sensor circuit T1-T2 Number of sensor circuits 1 Sensor type PTC type A (DIN/EN 44081, DIN/EN 44082) Max. total resistance of sensors connected in series, cold state < 750 h Overtemperature monitoring switch-off resistance (relays de-energize) 2.83 kh w 1% switch-on resistance (relays energize) 1.1 kh w 1% Interrupted wire detection yes switch-off resistance (relays de-energize) dynamic switch-on resistance (relays energize) not available Non-volatile fault storage yes Maximum voltage in sensor circuit 1.33 kohm 2.5 V 4 kohm 3.7 V y kohm 5.5 V Maximum current in sensor circuit 3.7 ma Maximum sensor cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² Accuracy within the rated control supply voltage tolerance 0.50 % Accuracy within the temperature range 0.01 %/K Repeat accuracy (constant parameters) on request Reaction time of the safety function <100 ms Hardware fault tolerance (HFT) 0 Control circuit Control function auto reset yes Maximum no-load voltage 5.5 V Max. current 0.6 ma Maximum cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² User interface Indication of operational states Control supply voltage U LED green Relay status R LED yellow Fault message F see "LEDs, status information and fault messages" on page 4 6 - Thermistor motor protection relay CM-MSS.11 Data sheet

Output circuit Kind of output 13-14 relay, 1 n/o contact 21-22 relay, 1 n/c contact Operating principle closed-circuit principle Contact material AgNi alloy, Cd free Minimum switching voltage / Minimum switching current 24 V / 10 ma Maximum switching voltage / Maximum switching current see "Load limit curves" on page 10 Rated operational voltage U e and rated operational current I e AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC Rating (UL 508) utilization category (Control Circuit Rating Code) B 300 maximum rated operational voltage 300 V AC maximum continuous thermal current at B 300 5 A maximum making/breaking apparent power at B 300 3600/360 VA general purpose rating 250 V AC - 4 A Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime at AC-12, 230 V AC, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve short-circuit protection n/c contact 10 A fast-acting n/o contact 10 A fast-acting General data MTBF on request Duty cycle 100 % Dimensions see "Dimensional drawing" Weight, net Screw connection technology Easy Connect Technology (push-in) 0.127 kg 0.119 kg Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool Mounting position any Minimum distance to other units 10 mm (0.39 in) if switching current > 2 A 10 mm (0.39 in) if switching current > 2 A Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20 Electrical connection Connecting capacity Stripping length Tightening torque fine strand with(out) wire end ferrule rigid Screw connection technology 1 x 0.5-2.5 mm² (1 x 18-14 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 8 mm (0.32 in) 0.6-0.8 Nm (7.08 lb.in) Recommended screw driver DIN ISO 2380-1: Form A / 0.8x4.0 mm DIN ISO 8764-1: PZ 1 / Ø 4.5 mm Easy Connect Technology (push-in) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) - - Data sheet Thermistor motor protection relay CM-MSS.11-7

Environmental data Ambient temperature ranges operation -25...+60 C (-13...+140 F) storage -40...+85 C (-40...+185 F) Damp heat, cyclic (IEC/EN 60068-2-30) 6 x 24 h cycle, 55 C, 95 % RH Climatic class (IEC/EN 60721-3-3) 3K5 (no condensation, no ice formation) Vibration, sinusoidal 5-13.2 Hz: w1 mm; 13.2-100 Hz: 0.7 g Shock 10 g / 11 ms Isolation data Rated insulation voltage U i Supply circuit / Measuring circuit 1) 300 V AC Supply circuit / Output circuits 300 V AC Measuring circuit 1) / Output circuits 300 V AC Output circuit 1 / Output circuit 2 300 V AC Rated impulse withstand voltage U imp Supply circuit / Measuring circuit 1) 4 kv Supply circuit / Output circuits 4 kv Measuring circuit 1) / Output circuits 4 kv Output circuit 1 / Output circuit 2 4 kv Basic insulation Supply circuit / Measuring circuit 1) 600 V AC Supply circuit / Output circuits 600 V AC Measuring circuit 1) / Output circuits 600 V AC Output circuit 1 / Output circuit 2 300 V AC Protective separation Supply circuit / Measuring circuit 1) yes, up to 300 V (IEC/EN 61140, EN 50178) Supply circuit / Output circuits yes Measuring circuit 1) / Output circuits yes Output circuit 1 / Output circuit 2 no Pollution degree 3 Overvoltage category III 1) Potential of measuring circuit = Potential of control circuit Standards / Directives Standards IEC/EN 60947-5-1, IEC/EN 60947-8 Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU ATEX Directive 2014/34/EU RoHS Directive 2011/65/EU 8 - Thermistor motor protection relay CM-MSS.11 Data sheet

Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-2, IEC/EN 60947-8 electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv contact discharge, 8 kv air discharge radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz), 3 V/m (2 GHz), 1 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 1 kv L-L, 2 kv L-N conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 Level 3, 0.15-80 MHz, 10 V, 80 % AM (1kHz) fields voltage dips, short interruptions and voltage variations IEC/EN 61000-4-11 Class 3 harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Additional interference immunity according to product standard EN 60255-1 (reference on EN 60255-26) radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 10 V/m (80 MHz - 3 GHz) conducted disturbances, induced by radio-frequency fields IEC/EN 61000-4-6 10 V at stated frequencies damped oscillatory waves IEC/EN 61000-4-18 Signal lines, symmetric coupling: 1 kv peak voltage Power supply, asymmetric coupling: 2.5 kv peak voltage, Interference emissions IEC/EN 61000-6-3 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B high-frequency radiated Germanischer Lloyd increased requirements in the emergency call frequency band Data sheet Thermistor motor protection relay CM-MSS.11-9

Technical diagrams Load limit curves V V 300 200 V V 300 200 100 80 60 50 40 30 100 80 60 50 40 30 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 194 F0205 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 193 F0205 AC load (resistive) DC load (resistive) 1.0 0.9 Switching cycles F 0.8 0.7 0.6 250 V resistive load 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ 2CDC 252 192 F0205 Switching current [A] 2CDC 252 148 F0206 Reduction factor F for inductive AC load Contact life time / number of operations N 220 V 50 Hz 1 AC, 360 operations/h 10 - Thermistor motor protection relay CM-MSS.11 Data sheet

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 3A11 20 0.787 8 0.315 2CDC 252 186 F0005 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.01 Marker label for devices without DIP switches COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic relays and controls Catalog 2CDC 110 004 C02xx Operating and installation instructions CM-MSS.11, CM-MSS.21, CM-MSS.31 Instruction manual 1SVC 730 660 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls Data sheet Thermistor motor protection relay CM-MSS.11-11

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 215 D0201 Rev. F (01/2018) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2018 ABB All rights reserved