BACnet Protocol Implementation Conformance Statement

Similar documents
BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

SyxthSense Room Controller (SRC1) Platform. BACnet Protocol Implementation Conformance Statement

QC BAC-BOX PIC STATEMENT

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

NB-V3Tb Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE

NB-VAV Family Protocol Implementation Conformance Statement (PICS)

NXAC-120 Area Controller

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

NB-GPC Family Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile:

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

Date: Vendor Name: Product Name: Product Model Number: Applications Software Version: Firmware Revision: BACnet Protocol Revision:

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000

BACnet Protocol Implementation Conformance Statement

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.)

HMS-1655 BACnet MS/TP Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement (PICS) MULTICAL 62/601/602/6L2/6M2/801

Delta Control Unit (DCU) 3.30 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

MULTICAL 403 MULTICAL 603

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro

BACnet Protocol Implementation Conformance Statement

S4 Open: BACnet N2 Router

BACnet Protocol Implementation Conformance Statement

1. BACnet Protocol Implementation Conformance Statement

PXC Compact Series on BACnet/IP

1. BACnet Protocol Implementation Conformance Statement

ESAC ebacgw SNMP. Date: Mar 08,2009. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

Delta ORCAview Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name:

homelynk/spacelynk BACnet Protocol Implementation Conformance Statement

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

WT-BAC-IP Gateway Protocol Implementation Conformance Statement

IQ4NC/.../ BACnet PICS

Distech Controls Application Specific Controllers PICS

PICS EE160D & EE210D BACnet Protocol Implementation Conformance Statement

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet

PICS_EE10D // v1.0 / Technical data subject to change. PICS EE10D BACnet Protocol Implementation Conformance Statement

entelibus CPU Engine (eb-eng) Firmware

Delta Controller Engine (DCE) Firmware

BACnet Protocol Implementation Conformance Statement

PICS_EE800D // v1.2 / Technical data subject to change. PICS EE800D BACnet Protocol Implementation Conformance Statement

Input/Output Module (IOM) Series Protocol Implementation Conformance Statement

Sales and Engineering Data Sheet ED

Visi.Plus Protocol Implementation Conformance Statement (PICS)

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement

Protocol Implementation Conformance Statement (Normative) BACnet Protocol Implementation Conformance Statement

BCM-ETH BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

FX Server BACNET AWS Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

Honeywell Novar XIO Remote I/O Protocol Implementation Conformance Statement (PICS)

SHEET. BASgatewayLX Modbus to BACnet Gateway. BASgatewayLX

BACnet IP Enabled InFusion Controller Bacnet-IP-IC BACnet Protocol Implementation Conformance Statement

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement

PICS EE850D & EE820 BACnet Protocol Implementation Conformance Statement

Wireless Pneumatic Thermostat BACnet Gateway PICS. Document No rev 01

! BACnet Operator Workstation (B-OWS)! BACnet Advanced Operator Workstation (B-AWS)! BACnet Operator Display (B-OD)

ETC Reference Guide BACnet PICS for P-CCS

Product Implementation Conformance Statement bcx1-r

CAS BACnet Stack Product Data Sheet

Honeywell. BACnet Protocol Installation and User s Manual. SmartVFD HVAC. Variable Frequency Drives for Constant and Variable Torque Applications

BACnet Protocol Implementation Conformance Statement

NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement

ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

BACnet RIB March,

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC

SITRANS F. Ultrasonic Flowmeters SITRANS F US Clamp-on Communications Module. Introduction 1. F US Clamp-on Communications Module Kit 2

vacon nx optcj user manual bacnet option board ac drives

BASgatewayLX Modbus to BACnet Converter

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

Integration Specification Sheet

BACnet Protocol Implementation Conformance Statement

BACnet RIB July 1, 2014

BACnet RIB June 24, 2016

BACnet Protocol Implementation Conformance Statement (PICS)

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

BACnet RIB July,

Titan Products NetMaster TP-NM-R/2000

BACnet Protocol Implementation Conformance Statement

Protocol Implementation Conformance Statement (PICS)

BACnet P.I.C.S. For RDT900 configurable controllers. Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement (PICS)

vacon 100 ac drives internal bacnet installation manual

BACnetRIB June 24, 2016

BACnet Protocol Implementation Conformance (PIC) Statement

MicroTech II Multiple Air Handler Controller

LLR-BAC BACnet MS/TP Light Level and Occupancy Sensor

BACnet Protocol Implementation Conformance Statement (PICS)

BACnet RIB Jan

Carbon Monoxide Transmitter

MXB-50 BACnet Interface for Mitsubishi Air-Conditioning

Transcription:

BACnet Protocol Implementation Conformance Statement Date: Sept 19, 2017 Vendor Name: ABB, Vendor ID 127 Product Name: HVAC Drive Product Model Number: ACH580 Applications Software Version: Drive F: 2.x.x.x BACnet Appl: 2024 Firmware evision: 14.01 BACnet Protocol evision: 14 Product Description: The ACH580 is a high-performance variable speed drive (VSD) designed for HVAC and refrigeration applications. Product supports native BACnet, connecting directly to the MS/TP LAN. MS/TP baud rates are supported up to 115.2 kbps, as well as master and slave mode functionalities. Over BACnet, the drive can be fully controlled and monitored as a standard variable speed drive. In addition, the drive s standard I/O is available over BACnet to the user application. BACnet Standardized Device Profile (Annex L): BACnet Operator orkstation (B-OS) BACnet Advanced Operator orkstation (B-AS) BACnet Operator Display (B-OD) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA) List all BACnet Interoperability Building Blocks Supported (Annex K): DS-P-B DS-PM-B DS-P-B DS-PM-B DS-COV-B DM-DDB-B DM-DOB-B DM-DCC-B DM-D-B DM-TS-B Data Sharing-eadProperty Data Sharing-eadProperty Multiple Data Sharing-riteProperty Data Sharing-riteProperty Multiple Data Sharing-Change of Device Management-DynamicDeviceBinding Device Management-DynamicObjectBinding Device Management-DeviceCommunicationControl Device Management-einitializeDevice Device Management-Time Synchronization Segmentation Capability: Able to transmit segmented messages indow Size: - Able to receive segmented messages indow Size: - Standard Object Types Supported: Object instantiation is static, i.e. objects cannot be created or deleted. efer to tables at end of this document for object details.

Data Link Layer Options: BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ATA 878.1, 2.5 Mb. ACNET (Clause 8) ATA 878.1, EIA-485 ACNET (Clause 8), baud rate(s) MS/TP master (Clause 9), baud rate(s): 9.6k, 19.2k, 38.4k, 76.8k, 115.2k MS/TP slave (Clause 9), baud rate(s): 9.6k, 19.2k, 38.4k, 76.8k, 115.2k Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: BACnet/ZigBee (ANNEX O) Other: Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No Networking Options: outer, Clause 6 BACnet/IP to MS/TP BACnet/ ISO 8802-3, Ethernet to MS/TP BACnet/IP to BACnet/ ISO 8802-3, Ethernet BACnet/IP to BACnet/ ISO 8802-3, Ethernet to MS/TP Annex H, BACnet Tunneling outer over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No Max BDT (Broadcast Distribution Table)-Entries: - Does the BBMD support network address translation? Yes No Network Security Options: Non-secure Device is capable of operating without BACnet Network Security Secure Device is capable of using BACnet Network Security (NS-SD BIBB) Multiple Application-Specific Keys: Supports encryption (NS-ED BIBB) Key Server (NS-KS BIBB) Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ISO 10646 (UTF-8) IBM /Microsoft DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208 If this product is a communication gateway, describe the types of non-bacnet equipment/networks(s) that the gateway supports:

Object/Property Support Matrix The following table summarizes the Object Types/Properties Supported and default values: Object type Property Binary Binary Binary Analog Analog Analog Multistate Loop Input Output Input Output Object Identifier Object Name, P, P, P, P (1),P Object Type C C C C Status Flags Event State Out-of-Service Polarity, P, P Active Text Inactive Text Units Min Max Priority Array elinquish Default, P,P, P, P COV Increment,P,P,P Number Of States State Text Property List =ead Only, =ritable, C=able, P=Persist (1) AV16, AV17, AV21, AV22, AV40- AV44, AV55, AV56, AV59, AV120-129 have, P Max length of writable Object Names is 25 characters

Device Object Instance Summary The following table summarizes the Device Object supported: Device Object Property Flag Type Default value Object Identifier, OID 4194303 P Object Name, CharString, AC Drive 4194303 P max length 25 Object Type Enum DEV (8) System Status Enum Vendor Name CharString ABB Vendor Identifier Unsigned 127 Model Name CharString ACH580 Firmware evision CharString 14.01 Application Software evision CharString Description, P CharString, max length ACH580 is a high-performance variable speed drive designed for HVAC and refrigeration applications. Location, CharString, (not set) P max length 50 Protocol Version Unsigned 1 Protocol evision Unsigned 14 Protocol Services Supported BitString Protocol Object Types Supported BitString Object List Array of OID Max APDU Length Accepted Unsigned 480 Segmentation Supported Enum No segmentation (3) Local Time BACnetTime Local Date BACnetDate APDU Timeout, Unsigned 00 ms P Number of APDU etries, Unsigned 3 P Max Master, Unsigned 127 P Max Info Frames, Unsigned 1 P Device Address Binding List of Struct Database evision, P Unsigned Active COV Subscriptions Array of BACnetCOVSubscription Serial Number CharString Property List Array of Unsigned Flags: =ead Only, =ritable, C=able, P=Persist

Binary Input Object Instance Summary The following table summarizes the Binary Input Objects supported: Object ID Object Name Description Active/Inactive Text BI0 O1- Status of elay Output 1 On / Off BI1 O2- Status of elay Output 2 On / Off BI2 O3- Status of elay Output 3 On / Off BI3 O4- Status of elay Output 4 On / Off BI4 O5- Status of elay Output 5 On / Off BI5 DO1- Status of Digital Output 1 On / Off BI6 DI1- Status of Digital Input 1 On / Off BI7 DI2- Status of Digital Input 2 On / Off BI8 DI3- Status of Digital Input 3 On / Off BI9 DI4- Status of Digital Input 4 On / Off BI10 DI5- Status of Digital Input 5 On / Off BI11 DI6- Status of Digital Input 6 On / Off NOTE: For s, = ead-only, = riteable, C = able. able values support Binary Output Object Instance Summary The following table summarizes the Binary Output Objects supported: Object ID Object Name Description Active/Inactive Text BO0 O1- Output state of elay 1 On / Off C BO1 O2- Output state of elay 2 On / Off C BO2 O3- Output state of elay 3 On / Off C BO3 O4- Output state of elay 4 On / Off C BO4 O5- Output state of elay 5 On / Off C BO5 DO1- Output state of Digital Output 1 On / Off C NOTE: For s, = ead-only, = riteable, C = able. able values support

Binary Object Instance Summary The following table summarizes the Binary Objects supported: Object ID Object Name Description Active/Inactive Text BV0 UN-STOP- Drive s run status un / Stop BV1 Direction- otational direction of the everse / Forward motor BV2 OK-FAULT- Actual fault status of drive Fault / OK BV3 EXT1-EXT2- Actual control source Ext2 / Ext1 BV4 HAND-AUTO- Actual operating mode. Hand / Auto BV5 arning- Actual warning status arning / OK BV7 eady- Actual ready status eady / Not-eady BV8 At-Setpoint- Actual at setpoint status Yes / No BV9 Enabled- Actual run enabled status Enable / Disable BV10 UN-STOP- to start drive un / Stop C BV11 Direction- to rotational everse / Forward C direction BV12 un-permissive- to un Enable / Disable C Permissive command BV13 EXT1-EXT2- ed to External 1 Ext2 / Ext1 C or External 2 selection BV14 Fault-eset- ed to fault reset eset / No BV15-BV16 <eserved> BV18 Control-Override- the drive into BACnet Control Override. In this mode, BACnet acquires drive control from its normal source. Note that HAND mode of the panel has priority over On / Off C BV19 Control-Override- BACnet Control Override. Indicates if drive has been placed in BACnet Control Override by commanding BV18. In this mode, BACnet acquires drive control from its normal source. Note that HAND mode of the panel has priority over BACnet Control Override. On / Off BV20 Start-Interlock-1- to Start Enable Enable / Disable C 1 BV21 Start-Interlock-2- to Start Enable Enable / Disable C 2 BV24 Started- Actual start status Started / Not-Started BV25 Safe-Torque-Off- Actual status of Safe Active / OK Torque Off BV26 Underload- Indicates if ULC signal is lower than the Underload curve Underload / OK

Object ID Object Name Description Active/Inactive Text BV27 Overload- Indicates if ULC signal is Overload / OK higher than the Overload curve BV28 Motor-Heating- to Motor On / Off Heating mode BV29 Motor-Heating- Actual status of Motor On / Off Heating mode BV30 User0- Actual status of User On / Off bit0 in drive status word BV31 User1- Actual status of User On / Off bit1 in drive status word BV32 User2- Actual status of User On / Off bit2 in drive status word BV33 User3- Actual status of User On / Off bit3 in drive status word BV34 User0- s User bit0 in On / Off C drive status word BV35 User1- s User bit1 in On / Off C drive status word BV36 User2- s User bit2 in On / Off C drive status word BV37 User3- s User bit3 in On / Off C drive status word BV38 <eserved> BV39 Parameter-Save- to save drive Save / No parameters and BACnet property data (properties marked as P=Persist ) BV40 PID-Set-Select to Process PID Set1 or Process PID Set2 selection Set1 / Set2 NOTE: For s, = ead-only, = riteable, C = able. able values support Analog Input Object Instance Summary The following table summarizes the Analog Input Objects supported: Object ID Default Object Name Description AI0 AI1- Indicates the input level of Analog Input 1. AI1 AI2- Indicates the input level of Analog Input 2. Min / Max Units 0 Percent (%) 0 Percent (%) NOTE: For s, = ead-only, = riteable, C = able. able values support Analog Output Object Instance Summary The following table summarizes the Analog Output Objects supported:

Object ID AO0 AO1 Default Object Name AO1- AO2- Description Controls Analog Output 1 (drive must be configured for BACnet control). Controls Analog Output 2 (drive must be configured for BACnet control). Min / Max Units 0 Percent C 0 Percent C NOTE: For s, = ead-only, = riteable, C = able. able values support Analog Object Instance Summary The following table summarizes the Analog Objects supported: Object ID Default Object Name Description Min / Max Units Access Type AV0 Output-PM Motor speed nominal speed rpm AV1 Output-Freq Output frequency -50 500 Hz AV2 DC-Voltage DC bus voltage V 2000 AV3 Output-Voltage AC output voltage V 2000 AV4 Output-Current Output current of A drive nominal current AV5 Output-Torque Output torque of -160 % motor as a 1600 percentage of nominal torque AV6 Output-Power Output power in k AV7 Operating-Temp- Heatsink ange temperature AV8 <eserved> AV9 Kilowatt-Hour- Meter-N AV10-AV13 Drive s cumulative energy usage. This value is not resettable. <eserved> AV14 unning-hours Drive s resettable run time (reset by writing 0). nominal power (+/-) -4 160 65535999999 3.40282347e38 AV15 Motor-Temp- Degrees-C Motor temperature -1 200 AV16 Input-eference-1 Speed setpoint 1-15 150 AV17 Input-eference-2 Speed setpoint 2. -15 150 AV18 Active-Fault Displays most recent fault currently active. AV19 Previous-Fault-1 Displays most recent stored (non-active) fault k % kh hours C % C % C

Object ID Default Object Name Description AV34-AV39 AV40 AV41 AV20 Previous-Fault-2 Displays the second most recent stored (non-active) fault AV21 AO1- Output level of Analog Output 1 AV22 AO2- Output level of Analog Output 2 AV23 Accel-1-Seconds amp1 acceleration time AV24 Decel-1-Seconds amp 1 deceleration time AV25 Mbox-Param Parameter number to be used by mailbox function. AV26 Mbox-Data Set () or indicate () of the data value of mailbox function AV27-AV28 <eserved> AV29 Min-Speed Defines the allowed minimum output frequency AV30 Max-Speed Defines the allowed maximum output frequency AV31 Output-Speed Actual motor speed AV32 Output-Current- Actual motor ange current AV33 Max-Current Max motor current <eserved> LOOP-Feedback- LOOP-Setpoint- Loop controller feedback value after source selection, mathematical function and filtering (read-only) Loop controller setpoint value after source selection, mathematical function limitation and ramping (readonly) AV42 LOOP-Setpoint to store loop controller setpoint value used as input for the process AV43 LOOP-Feedback Stores the feedback value for Min / Max 1800 1800-50 500-50 500-20 200 200 nominal current Units Access Type % % s s Hz Hz % % A % % % C %

Object ID Default Object Name Description Loop controller AV44 LOOP-Output Loop controller output AV45 LOOP- Gain Loop controller gain AV46 LOOP-Integration- Loop controller Time integration time AV47-AV48 <eserved> AV49 LOOP-Deviation- Loop controller deviation AV50-AV52 <eserved> AV53 LOOP-1-Gain Loop controller gain (Set 2) AV54 LOOP-1-Integration- Loop controller Time integration time AV55 AV56 LOOP-2-Feedback- LOOP-2-Setpoint- (Set 2) External loop controller feedback value after source selection, mathematical function and filtering (read-only) External loop controller setpoint value after source selection, mathematical function limitation and ramping (readonly) AV57-AV58 <eserved> AV59 LOOP-2-Output External loop controller output AV60 LOOP-2-Gain External loop controller gain AV61 LOOP-2-Integration- Time AV62-AV63 AV64 <eserved> LOOP-2-Deviation- External loop controller integration time External loop controller deviation Min / Max 0.1, 3600 0.1, 3600 Units Access Type % s % s % % 0.1, 3600 % s % AV65-119 <eserved> AV120 Data-IO-1 Holds the value of parameter 58.101 AV121 Data-IO-2 Holds the value of parameter 58.102

Object ID Default Object Name Description AV122 Data-IO-3 Holds the value of parameter 58.103 AV123 Data-IO-4 Holds the value of parameter 58.104 AV124 Data-IO-5 Holds the value of parameter 58.105 (ead-only) AV125 Data-IO-6 Holds the value of parameter 58.106 (ead-only) AV126 Data-IO-7 Holds the value of parameter 58.107 (ead-only) AV127 Data-IO-8 Holds the value of parameter 58.108 (ead-only) AV128 Data-IO-9 Holds the value of parameter 58.109 (ead-only) AV129 Data-IO-10 Holds the value of parameter 58.110 AV130 AV131 AV132 AV133 Kilowatt-Hour-This- Hour Kilowatt-Hour-Last- Hour Kilowatt-Hour-This- Day Kilowatt-Hour-Last- Day (ead-only) Current hour energy consumption Last hour energy consumption Current day energy consumption Last day energy consumption Min / Max 3.40282347e38 3.40282347e38 3.40282347e38 3.40282347e38 Units kh kh kh kh Access Type

NOTE: For s, = ead-only, = riteable, C = able. able values support Multistate Object Instance Summary The following table summarizes the Multistate Objects supported: Object ID Object Name Description State Text MSV0 HAND- AUTO- eference Indicates whether the drive is under Hand or Auto control, or if override Off, Hand, Auto, MSV1 MSV2 Active-Fault- 1 Active-Fault- 2 mode is active. Enumerated type of the most recent fault currently active Enumerated type of the 2nd most recent fault currently active Override None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active, Other None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active,

Object ID Object Name Description State Text Other MSV3 MSV4 MSV5 MSV6 Active-Fault- 3 Active- arning-1 Active- arning-2 Active- arning-3 Enumerated type of the 3rd most recent fault currently active Enumerated type of the most recent warning currently active Enumerated type of the 2nd most recent warning currently active Enumerated type of the 3rd most recent warning currently active None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active, Other None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, un-permissive, Internal-arning, Start-Delay, Other None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, un-permissive, Internal-arning, Start-Delay, Other None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, un-permissive, Internal-arning, Start-Delay, Other

NOTE: For s, = ead-only, = riteable, C = able. able values support Loop Object Instance Summary The following table summarizes the Loop Objects supported: Object ID LOOP0 LOOP1 Object Name LOOP- Set1 LOOP- Set2 Description Loop object for process PID set 1 Loop object for process PID set 2 Manipulated Variable reference AV44 AV44 Controlled variable reference AV43 AV43 Setpoint eference AV42 AV42 Access Type NOTE: For s, = ead-only, = riteable, C = able. able values support