SIL Safety Manual DOC.SILM.EF.EN Rev. 0 March EL-O-Matic F-Series Pneumatic Actuator SIL Safety Manual

Similar documents
Hytork XL Pneumatic Actuator

SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 March EL-O-Matic F-Series Pneumatic Actuator SIL Safety Manual

Hytork XL Pneumatic Actuator

TEC2 LDM Programming Instructions

Loading Configuration from TEC2000 to TEC2 using DCMLink. Configuration Instructions TEC2-LOAD-1001 Rev. 1 September 2015

TEC2 Configuration file convert from TEC2000

Intelligent Valve Controller NDX. Safety Manual

FieldQ Control Module QC54 FOUNDATION Fieldbus

Rosemount Functional Safety Manual. Manual Supplement , Rev AG March 2015

Quick Start Guide DCM Rev. 2 August DCMlink Quick Start Guide

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE

Point Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics

Mobrey Hydratect 2462

Proline Prowirl 72, 73

Fisher 657 and 667 Size 30i - 76i Diaphragm Actuators

Fisher FIELDVUE DVC6200 HW2 Management of Change Guide

Safety manual for Fisher FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel

ControlWave Micro HART / BTI Interface Module

Hardware safety integrity (HSI) in IEC 61508/ IEC 61511

MANUAL Functional Safety

Fisher FIELDVUE DVC6200p Digital Valve Controller Device Setup and Accessing Communication and Calibration using Siemens SIMATIC Manager/PDM

3 BUTTERFLY VALVE MAINTENANCE MANUAL //

Fast Control Response Requirement

AMS ValveLink Software Quick-Start Guide

SVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown.

ControlWave PAC Digital Input / Output Modules

High Performance Guided Wave Radar Level Transmitter

IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications

Supplement to Fisher FIELDVUE DVC6000 SIS Series Digital Valve Controllers for Safety Instrumented System (SIS) Solutions Instruction Manual

S-series DeviceNet Interface Card

Type Switching repeater. Safety manual

M-series Profibus DP Series 2 Plus Interface Card

FBxConnect Configuration Software

Functional safety manual RB223

ControlWave PAC Analog Input / Output Modules

ida Certification Services IEC Functional Safety Assessment Project: Masoneilan Smart Valve Interface, SVI II ESD Customer: GE Energy

Products Solutions Services. Functional Safety. How to determine a Safety integrity Level (SIL 1,2 or 3)

Failure Modes, Effects and Diagnostic Analysis

It s a safe world after all

Introduction. Delivers four ports to provide increased input/ output per card. Takes advantage of all smart device capabilities

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual

VERTIV SERVICE CAPABILITY

ROC800-Series Thermocouple Module

S-series DeviceNet Interface Card

Keystone OM3 - EPI-2 Local Interface Module Installation and Maintenance Instructions

IntelliLED TM. Controls: User Guide. Picture for DALI only. Wireless adds external antenna. NOTE: These parts are NOT user serviceable

DeltaV VerticalPlus I/O Subsystem Carriers

Installation and operating instructions

SUN2000-(2KTL-5KTL)-L0. Quick Guide. Issue: 01 Part Number: Date: HUAWEI TECHNOLOGIES CO., LTD.

Certified Technical Training for Emerson Flow Instruments. Helping you to maximize your Flow instrument investment

OpenEnterprise Licensing User Manual

High Performance Guided Wave Radar Level Transmitter

ISASecure SSA Certification for DeltaV and DeltaV SIS

Plant Messenger. Introduction. DeltaV Product Data Sheet. Delivers the information you want when and where you want it

Failure Modes, Effects and Diagnostic Analysis

The evolution of the cookbook

Failure Modes, Effects and Diagnostic Analysis

Safety manual. This safety manual is valid for the following product versions: Version No. V1R0

ControlWave Micro Resistance Temperature Detector Module and Thermocouple Module

S-series Serial Interface

ControlWave PAC Resistance Temperature Detector Module and Thermocouple Module

Failure Modes, Effects and Diagnostic Analysis

Wireless Field Data Backhaul

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

M-series Foundation Fieldbus I/O

DeltaV M-series I/O Subsystem Horizontal Carriers

M-series Serial Interface Series 2

Safe & available...vigilant!

DK32 - DK34 - DK37 Supplementary instructions

FIELDVUE DVC6200 and DVC6200f Digital Valve Controller Management of Change Guide

LABEL. Invest in Confidence. SIL Actuators

Safety Manual. Vibration Control Type 663. Standard Zone-1-21 Zone Edition: English

DeltaV SIS Conditioning Components

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Rosemount VeriCase User Guide

ScannerCal Accuracy Verification System for the FlowScanner

System Integration of Fieldbus Electric Actuators

II ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown.

AV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range

FIELDVUE Digital Valve Controllers. Tri-Loop Signal Converter Operation with FIELDVUE Digital Valve Controllers

Flowserve Al-Rushaid Facility in Saudi Arabia

S-series Profibus DP Interface Card

DeltaV Connect Solution for Moore Systems

MANUAL Functional Safety

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

Partner for automation Water technology

Baumann Little Scotty Bronze Control Valve

Rosemount 370XA Natural Gas Chromatograph

DeltaV Bulk Power Supplies

Vibrating Switches SITRANS LVL 200S, LVL 200E. Relay (DPDT) With SIL qualification. Safety Manual. Siemens Parts

DeltaV Version 14 Safety Instrumented Systems Enhancements

Mounting and Operating Instructions EB EN. Electric Actuators Type 5824 without fail-safe action Type 5825 with fail-safe action

Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves

SAFETY MANUAL SIL Switch Amplifier

MACX MCR-EX-SD LP(-SP)

HST -TZ1 Guard-locking mechanism (Translation of Original Manual)

M-series Profibus DP Series 2 Plus Interface Card

Level Transmitter. SIL Safety Manual for Enhanced Model 705 Software v3.x. Functional Safety Manual. Application

MANUAL VAA-2E2A-G12-SAJ/EA2L Original Instructions Version 1.0

Transcription:

SIL Safety Manual DOC.SILM.EF.EN Rev. 0 March 2015 EL-O-Matic F-Series Pneumatic Actuator SIL Safety Manual EL Matic TM

EL-O-Matic F DOC.SILM.EF.EN, Rev. 0 Contents March 2015 Table of Contents Section 1: Functional Specification...1 Section 2: Configuration of the Product...2 Section 3: Service Condition Limitations (Limitation of Use)...3 Section 4: Expected Lifetime...4 Section 5: Failure Modes and Estimated Failure Rates...5 Section 6: Installation and Site Acceptance Procedure...6 Section 7: Periodic Test and Maintenance Requirements...7 7.1 General... 7 7.2 Full-Stroke Test... 7 7.3 Partial-Stroke Test... 8 7.4 Proof Test and Periodic Maintenance... 8 Section 8: Hardware Fault Tolerance...9 Section 9: Classification...10 Section 10: Safe Failure Fraction...11 Section 11: Mean Repair Time...12 Section 12: Systematic Capability...13 Section 13: Document Revision...14 Table of Contents I

SIL Safety Manual Section 1: Functional Specification DOC.SILM.EF.EN, Rev. 0 March 2015 Section 1: Functional Specification The safety function for El-O-Matic F-Series pneumatic actuator is defined as follows: Double-Acting Scenario: a. When an unsafe condition is detected in a plant by a process sensor, the controller, via actuator control system, drives the Actuator to close the shut-down valve, depressurizing (if under pressure) the Opening side of the actuator and pressurizing the Closing side of the actuator. b. When an unsafe condition is detected in a plant by a process sensor, the controller, via actuator control system drives the Actuator to open the blow-down valve, depressurizing (if under pressure ) the Closing side of the pneumatic actuator and pressurizing the Opening side of the pneumatic actuator. Single-Acting Scenario: a. When an unsafe condition is detected in a plant by a process sensor, the controller, via actuator control system drives the Actuator to rotate with sufficient torque to move a valve to its fail-safe state when hold-position air pressure is released. The El-O-Matic brand Actuator Selection Procedure provides functional definition with specifics on input variables and performance. In any case, the choice of the safety function to be implemented is responsibility of the system integrator. Functional Specification 1

Section 2: Configuration of the Product March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 2: Configuration of the Product The El-O-Matic F-Series are pneumatically operated actuators designed to operate Ball / Plug / Butterfly valves, automation of louvers and dampers & automation of any quarterturn mechanism. Both the double-acting and single-acting (spring-return) versions of the El-O-Matic F-Series pneumatic actuators are designed in such a way that there are no moving parts on the outside (with the exception of the position indicator). This makes them safe, easy to install and virtually maintenance free. For further details about actuator configurations, please refer to the El-O-Matic F-Series product data sheets, Safety guide and Installation, Operation and Maintenance manual. 2 Configuration of the Product

SIL Safety Manual Section 3: Service Condition Limitations (Limitation of Use) DOC.SILM.EF.EN, Rev. 0 March 2015 Section 3: Service Condition Limitations (Limitation of Use) The operating capabilities are listed below: Maximum Operating Pressure: Pneumatic Service Up to 120 psig (8.3 barg) Ambient Temperature: Temperature extremes require different solutions to maintain actuator operational integrity and reliability. For each El-O-Matic F-Series actuator is available in three different temperature executions. -20 C to +80 C (-4 F to +176 F) Standard temperature -20 C to +120 C (-4 F to +250 F) High Temperature -40 C to +80 C (-40 F to +176 F) Low Temperature Torque Output Range: Double-Acting El-O-Matic F-Series actuators, requiring pressure to rotate in either direction, are available with a torque range between 4.8 Nm (44 lbf.in) and 6,490 Nm (59000 lbf.in) The El-O-Matic F-Series spring-return models require pressure in only one direction of travel and are suitable for air-fail close and air-fail to open applications without modification. These models are available with a spring end torque between 2 Nm (20 lbf.in) and 2394 Nm (21000 lbf.in) Safety Function: For spring-return models, the safety function is self-evident performed by the springs. The safety function of double-acting models should be performed by the A-chamber for safety related systems. Figure 1 Use the A-Chamber for Safety Related Systems on Double-Acting Actuators Assembly Code: CW Assembly Code: CC = Safety Function is = Safety Function is Counterclockwise Rotation Clockwise Rotation B A Pinion A B Pistons A B A B Pistons Service Condition Limitations (Limitation of Use) 3

Section 4: Expected Lifetime March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 4: Expected Lifetime Actuator lifetime (for which failure rates indicated in Par. 5 are ensured) strongly depends on operating conditions. For normal service conditions, EL-O-Matic F-Series actuators can be in good conditions also after more than 10 years with planned minimum maintenance. Normal working life is 500.000 cycles. El-O-Matic F-Series carry a warranty period of: 18 months after delivery if properly stored in conditions that we declare or 12 months after installation on site. 4 Expected Lifetime

SIL Safety Manual Section 5: Failure Modes and Estimated Failure Rates DOC.SILM.EF.EN, Rev. 0 March 2015 Section 5: Failure Modes and Estimated Failure Rates Table 1. Failure Modes and Estimated Failure Rates El-O-Matic F-Series Actuator Failure Mode Failure on demand to Close/Open (FTC/FTO) - El-O-Matic F-Series Double-Acting Failure on demand to Close/Open (FTC/FTO) - El-O-Matic F-Series Single-Acting Estimated Failure Rate [1/h] 5.24E-08 4.63E-08 NOTICE No internal diagnostics is included in the device. These numbers are valid when taken in account the maintenance interval and procedure described in Section 7. Failure Modes and Estimated Failure Rates 5

Section 6: Installation and Site Acceptance Procedure March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 6: Installation and Site Acceptance Procedure Any necessary installation and site acceptance procedures are discussed in the EL-O-Matic F-Series actuators Installation, Operation and Maintenance manual. The Installation, Operation and Maintenance manual defines exercising of the actuator after installation and defines testing after maintenance. 6 Installation and Site Acceptance Procedure

SIL Safety Manual Section 7: Periodic Test and Maintenance Requirements DOC.SILM.EF.EN, Rev. 0 March 2015 Section 7: Periodic Test and Maintenance Requirements 7.1 General Please consider that the information in this paragraph are relevant only in regards of Reliability Tests; please refer to Doc. Installation, Operation and Maintenance manual for detailed information about product maintenance, handling and storage. Diagnostic tests may be made to increase the system reliability (Full-Stroke or Partial- Stroke Test). On site tests depend on Project/Plant facilities/requirements; however, a functional test must be executed on site, prior actuator operation. 7.2 Full-Stroke Test The Full-Stroke Test ( On-line ) must be performed to satisfy the PFD AVG (average probability of failure on demand) value. The full-test frequencies will be defined by the final integrator in relation to the defined SIL level to achieve. Procedure: Operate the Actuator/Valve assembly for No. 2 open/close complete cycles with complete closing of the valve. Verify the Correct performing of open close manoeuvre (for example, check locally, or automatically via Logic solver, the correct movement of the actuator/valve). Considering the application of the above described Full-Stroke Test procedure, the Test Coverage can be considered 99%. Periodic Test and Maintenance Requirements 7

Section 7: Periodic Test and Maintenance Requirements March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 7.3 Partial-Stroke Test The Partial-Stroke Test ( On-line ) can be performed to improve the PFD AVG value. A typical partial-stroke value is 15% of the stroke. The Partial-Stroke Test ( On line ) can be performed to satisfy PFD AVG (average probability of failure on demand) value. Recommended Test Interval = 1 to 3 months. Procedure: Operate the Actuator/Valve assembly for No 1 open/close cycles 15/20% of the stroke. Verify the Correct performing of partial-stroke operation (for example, check locally, or automatically via Logic solver, or via the PST system the correct movement of the actuator/valve till 15/20% of the stroke). The above parameters to check will depend from the partial-stroke test system available. Considering the application of the above described Partial-Stroke Test procedure, the Diagnostic Coverage is >90 %. 7.4 Proof Test and Periodic Maintenance We advise to perform the following checks upon each proof test interval complying with the rules and regulations of the country of final installation: Visually check the entire actuator as well as the control system (where foreseen). Ensure there are no leaks on the actuator parts under pressure. Check pneumatic connections for leaks. Tighten tube fittings as required. Check if manual override (where foreseen) is regular. Check if pneumatic filter cartridge (where foreseen) is sound and filter bowl (where foreseen) has been cleaned properly. Check the setting of the relief valves (where foreseen). Verify that the power fluid supply pressure value is within the required range. Remove built-up dust and dirt from all actuator surfaces. Inspect actuator paint work for damages to ensure continued corrosion protection. Touch-up as required in accordance with the applicable paint specification. Operate the Actuator/Valve assembly for No 2 open/close complete cycles with complete closing of the valve. Verify the correct performing of open close operations (for example, check locally, or automatically via Logic solver, the correct movement of the actuator). The Installation, Operation and Maintenance manual defines a minimum maintenance interval after 500.000 cycles for the EL-O-Matic F-Series actuators. This addresses components that may have age related degradation. When the maintenance interval has elapsed a complete overhaul of the actuator is required. 8 Periodic Test and Maintenance Requirements

SIL Safety Manual Section 8: Hardware Fault Tolerance DOC.SILM.EF.EN, Rev. 0 March 2015 Section 8: Hardware Fault Tolerance The HFT of the device is 0. The requirements of minimum hardware fault tolerance (HFT) according to Tab.6 of IEC 61511-1 have to be observed but, as long as has been performed an assessment report fully in compliance with IEC 61508 part 1 to7, alternative fault tolerance requirements have to be considered applicable according to Table 2 of IEC 61508-2 as per par. 11.4.5 of IEC 61511-1. Hardware Fault Tolerance 9

Section 9: Classification March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 9: Classification The equipment is classified Type A according to IEC 61508-2. 10 Classification

SIL Safety Manual Section 10: Safe Failure Fraction DOC.SILM.EF.EN, Rev. 0 March 2015 Section 10: Safe Failure Fraction SFF=0 without external diagnostic tests. SFF>0 with external diagnostic tests, carried out according to definition 3.8.7 of IEC 61508-4. SFF = 91% with Partial-Stroke Test. SFF = 99% with Full-Stroke Test. The SFF shall be evaluated for the entire final element sub-system. The diagnostic test shall be performed considerably more often than the demand of the safety function. Safe Failure Fraction 11

Section 11: Mean Repair Time March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 11: Mean Repair Time The MRT of the device is 1 hour. NOTICE The MRT is estimated considering availability of skilled personnel for maintenance, spare parts and adequate tools and materials on site (that is, it encompasses the effective time to repair and the time before the component is put back into operation). Procedures to repair or replace the EL-O-Matic F-Series actuators are provided in the respective Installation, Operation and Maintenance manual. Please refer to the Installation, Operation and Maintenance manual for any tools required for repair and replacement and required competency of technicians. Maintenance and subsequent test procedures are also covered in the Installation, Operation and Maintenance manual. Any failures, identified by the end-user during maintenance, repair or proof testing, that potentially impact the functional safety of the EL-O-Matic F-Series actuators should be reported back to Actuation Technologies Customer Service Coordinator. 12 Mean Repair Time

SIL Safety Manual Section 12: Systematic Capability DOC.SILM.EF.EN, Rev. 0 March 2015 Section 12: Systematic Capability The systematic capability of the device is 3. This systematic capability is guaranteed only if the user: 1. Use the device according to the instructions for use and to the present Manual. 2. Use the device in the appropriate environment (limitation of use). Systematic Capability 13

Section 13: Document Revision March 2015 SIL Safety Manual DOC.SILM.EF.EN, Rev. 0 Section 13: Document Revision Table 2. Revision Overview ECN DATE REV BY * DATE PRE RELEASE 00A ORIGINATOR J. Zorgdrager 27 January 2015 CHECKED R. Ouwendijk 27 January 2015 APPROVED 14 Document Revision

World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you: NORTH & SOUTH AMERICA 19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100 F +1 281 477 2809 Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3238 3788 F +55 15 3228 3300 ASIA PACIFIC No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211 F +65 6268 0028 MIDDLE EAST & AFRICA P. O. Box 17033 Dubai United Arab Emirates T +971 4 811 8100 F +971 4 886 5465 P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650 F +966 3 340 8790 24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700 F +27 11 451 3800 www.emerson.com/el-o-matic No. 1 Lai Yuan Road Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300 F +86 22 8212 3308 EUROPE Berenyi u. 72-100 Videoton Industry Park Building #230 Székesfehérvár 8000 Hungary T +36 22 53 0950 F +36 22 54 3700 For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com 2017 Emerson. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. EL-O-Matic TM is a mark of one of the Emerson family of companies. All other marks are property of their respective owners. The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice. EL Matic TM