Simplifying Direct Connect Deployment Using Field Term Plugs in Connect Cabling Systems

Similar documents
Field Term Plug Installation Guidelines

New Standardized Cabling Options for NBASE-T Devices

Power Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure

Ronald Tellas, Technology and Applications Manager, Enterprise Networking

PoE Lighting Benefits and Design Considerations. Creating more meaningful connections in the digital building

White paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com

Saving Critical Space. Cable Management Solutions

60-Watt Ultra Power over Ethernet Injector

Single-Port 10/100/1000Mbps 60W Ultra PoE Injector

Power Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure

Siemon PON Fiber Cabling Solutions

or go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS

Single-Port 10/100/1000Mbps 802.3bt PoE++ Injector (95 Watts, internal PWR)

POWER OVER ETHERNET SYSTEMS

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation

Single-Port 10/100/1000Mbps 802.3bt PoE Injector (95 Watts)

Industrial Single-Port 10/100/1000Mbps 802.3bt PoE Injector (60 Watts, -40~75 degrees C, 48~56V DC)

4-Port 10/100Mbps 802.3at/af PoE + 1-Port 10/100Mbps Desktop Switch

Zone Cabling for Cost Savings: Plenum Environments

4-Port 10/100Mbps 802.3at / af PoE + 1-Port 10/100Mbps Desktop Switch

PHYSICAL INFRASTRUCTURE SYSTEMS

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

CERTIFICATION PLUS SM

How You Can Optimize Passive Optical LAN Through Structured Cabling

1 of 5 12/31/2008 8:41 AM

Industrial Single-Port 10/100/1000Mbps 802.3bt PoE Injector (95 Watts, -40~75 degrees C, 12~48V DC)

ANSI/TIA/EIA-568-B Cabling Standard

Industrial 1-Port Gigabit 95W Ultra PoE Splitter

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

DATE: October 28, 2002 TO: Management FROM: Brandon Miller, John Thompson, Brett Walke RE: OUR RECCOMENDATIONS FOR OUR CLIENTS NETWORKING NEEDS

8-Port 10/100Mbps 802.3at PoE + 1-Port 10/100/1000Mbps Desktop Switch

Central Offi ce Connector Block Accessories

Universal connectivity grid design guide

EtherCAT P combines ultra-fast communication and power supply in a single cable

The Impact of Internet of Things on Cable Certification

Chapter 10: Planning and Cabling Networks

FREQUENTLY ASKED QUESTIONS (FAQs)

PANGEN SYSTEM WARRANTY. Warranty Guide

Light over PoE. Emanuele Colombo Country Manager R&M Italia October 2017

PHYSICAL INFRASTRUCTURE SYSTEMS

PANZONE ZONE CABLING SYSTEMS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The Indoor+Outdoor Security Starter Kit Quickstart Guide

4-Port 10/100/1000T 802.3at PoE + 2-Port 10/100/1000T Desktop Switch

Uniprise Structured Cabling Solutions Guide

FTTE Revisited for New Technologies

Fiber Backbone Cabling in Buildings

Cisco TelePresence TX1300 Series

Classroom WiFi Network Infrastructure Plan

4-Port 10/100/1000T 802.3at PoE + 2-Port 10/100/1000T Desktop Switch

Wireless Area Controller (WAC60)

Lantech IPGC-0101DSFP. User Manual. 10/100/1000T (PoE at) to 100/1000M SFP Industrial Switch Converter

CREE SMARTCAST TECHNOLOGY

Industrial 8-Port 10/100/1000T Wall-mounted Gigabit Ethernet Switch with 4-Port PoE+

V-Built Custom Preconfigured Solutions

Cabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring

Fiber backbone cabling in buildings

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA

IEEE 802.3at High Power over Ethernet Injector POE-163 / POE-164

Building Buildings Better

3M ID 3000 System. ID 3128 block. Disconnection module. ID 3100 block Wire guide housing

Fiber or Copper Which Costs More? Daniel Harman Aug 2006

Category 5e Solutions

Laying the groundwork for a new level of Power over Ethernet

2-Port Gigabit PoE+ Extender at and 802.3af m (330 ft)

6-Port Gigabit PoE Switch with 4 Gigabit PoE Ports

8-Port 10/100/1000T 802.3at PoE + 1-Port Gigabit Desktop Switch

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

1-Port Gigabit PoE+ Extender at and 802.3af m (330 ft)

Run a Smart Workplace Introducing the Digital Building. Digital Building Solutions

High Resolution Indoor/Outdoor Color Camera System

Unrestricted PoE+ range and convenience. Daisy chain for longer distance and flexibility. Gigabit PoE+ Extender at/af - 100m (330ft)

Anticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards

With the publication. Make the right connection: Bonding a shielded system. installation

Tools and Testers. Section Contents TOOLS AND TESTERS

Modular plugs, accessories and tooling

Frequently Asked Questions (FAQs) Siemon 10G ip Solutions

ANSI/TIA-568-C Cat 6A Field Test Specifications

Contents. Structured Cabling Solutions. LAN Cables Patch Cords Connectors Patch Panels... 06

The following pages contain a guide for the installation

Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks

CommScope harnesses the power of PoE in Madrid

Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement

Cabling Infrastructure

The Impact of Internet of Things (IoT) on Cable Certification

Cat.8 Shielded Field Termination Plug Description

IBDN 110 Cross-Connect System

Connected & Efficient Building. Field Application Engineer - Kutlugün Sürmeli CommScope

/STE BuyLine Pathways floor & wiring

The SYSTIMAX GigaSPEED X10D solution. The infrastructure modern enterprises and data centers depend on

PowerSense. Sending all the right signals. Sense the Power... Power over Ethernet Solutions

Dual Monitor USB-C Dock - 60W Power Delivery - 4K

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter

EX-UBT AVB/USB EXPANDER OPERATION MANUAL

User Manual CV-87K. PS/2 extender over cat.x. rev: Made in Taiwan

The AMP NETCONNECT Category 6 Cabling System

ANSI/TIA/EIA-568-B Cabling Standard

ORTRONICS SNAP CLARITY TERMINATED COPPER CABLING SYSTEMS & PORT REPLICATION. designed to be better.

September PORT 10/100M DESKTOP SWITCH WITH 4x PoE+ PORTS. 8 PORT 10/100M DESKTOP SWITCH WITH 8x PoE+ PORTS. PoE+ Switch

Transcription:

July 2017 Simplifying Direct Connect Deployment Using Field Term s in Connect Cabling Systems What is Direct Connect Cabling and Why is it Used? Direct connect cabling is an approach that installers increasingly use to attach deployed devices in enterprise networks. In direct connect cabling the horizontal link plugs directly into the network device rather than using a patch cord. Typical structured cabling approach: Horizontal cable terminates to a modular jack and a patch cord connects the device to the network (Figure 1): (Switch) Patch Cord Horizontal Cable Patch Cord Network Device Telecommunication Room Figure 1. Typical structured cabling approach. Direct connect cabling: Horizontal cable link terminates to a plug which is inserted directly into the device, connecting it to the network (Figure 2): (Switch) Patch Cord Horizontal Cable (inated ) Network Device Telecommunication Room Figure 2. Direct connect cabling approach. Direct connect cabling makes the most sense with devices that are in less accessible areas, require little or no contact, and are not moved very often. Table 1 lists devices that would benefit from direct connect cabling. COTB15- -S-ENG, Rev.0, 07/2017 2017 Panduit Corp. ll Rights Reserved. Page 1 of 6

Table 1. Good Candidates for Direct Connect Cabling. Device Examples Typical location of device or termination Need for access to device or termination Need for future movement of device Wireless access points, security cameras, sensors, digital signage, PoE lighting, etc. Ceiling level or high on wall Limited No For these types of applications, direct connect is a simple, cost-effective alternative to the traditional structured cabling approach. It allows for fewer connectors, easier running of the cable link, and higher reliability. Direct Connect Made Easy The Panduit While the Panduit TX6 (Figure 3) works within any architecture, it is ideally suited for direct connect applications which depend upon a high-performance plug that can be terminated on site. The plug is ideal for connecting network devices such as wireless access points, LED lighting, security cameras, sensors, building access units, display panels, and others. What s Different about the TX6? Figure 3. Panduit TX6 field term plug. Traditional modular plugs, while compact and cost effective, are comprised of several small parts and require multiple steps to terminate properly. Therefore, they are poorly suited to attaching to cable in field conditions. lso, while there are some plugs promoted as field-terminable they often are bulky and not very easy to assemble quickly or properly in typical field conditions. The TX6 (Figure 4) enables quick and easy termination to cabling and is compact enough to fit in similar spaces as traditional modular plugs. Figure 4. Typical (left) vs. Panduit field term plug (right). In contrast, the TX6 uses Panduit s pioneering TG Style wire cap (Figure 5) termination technology, the same easy forward motion technology used for more than 12 years with Panduit modular jacks. The method features: 2017 Panduit Corp. ll Rights Reserved. 2

Simple two-part assembly bility to handle a wide range of cable gauges n easy-to-learn yet reliable termination, even with Category 6 Fast termination times compact and lightweight termination tool Terminating the Panduit Figure 5. The TX6 uses a TG Style wire cap like those used on Panduit TG Mini-Com modular jacks. Terminating the TX6 is as simple as terminating a Panduit TG style jack. The wire cap of the has the identical wire map pattern and conductor retention features as a TG style jack. The uses the same forward-motion termination technology and the same termination tool (EGJT-1) as the TG style jack (Figure 6). Figure 6. Easy termination with the EGJT-1 Termination Tool. Fit and Compatibility with Devices The compact footprint of the TX6 enables it to fit in smaller spaces than most other field terminable plugs. 2017 Panduit Corp. ll Rights Reserved. 3

The Space Required shown in Figure 7 includes length clearance to insert & remove the plug. lways confirm the fit of the TX6 with the intended device. How to Test Direct Connected Links Panduit supports two ways to test direct connected links for performance and warranty purposes. In both cases, up to two TX6 s may be present in the link. Test Method 1 Standards Method Figure 7. Space required to fit TX6. System designers and users of data communications systems use the Terminated Link (MPTL) field terminable plug Standards Method to verify the performance of the permanent link used in a direct-connect designed infrastructure. The permanent link tested in this model includes up to 90m (295 ft.) of horizontal cable with a maximum of two (2) field terminable plugs. The connection to the equipment at either end of a permanent link is only included in the permanent link definition if measured via the Standards Model. Figure 8 shows schematic representations of the permanent link testing via the Standards Model. Category 6 Patch Cord Category 6 B Patch Cord Minimum segment length = 1m (3.28 ft.) Minimum segment B length = 9m (29.53 ft.) Maximum PL length = 90m (295.2 ft.) Figure 8. Schematic representations of permanent link testing via the Standards Model. 2017 Panduit Corp. ll Rights Reserved. 4

Test Method 2 The lternate Method System designers and users of data communications systems use the lternate Method field terminable plug test configuration to verify the performance of the permanent link in a direct-connect designed infrastructure where the Standards Method is not possible. In the lternate Method, the permanent link continues to have a maximum total horizontal cable length of 90m (295 ft.) and a maximum of two (2) field terminable plugs. The connection to the equipment at either end of a permanent link is not included in the lternate Method test and therefore requires a 1m plug-to-jack cord to properly test the UTP as part of the permanent link performance. Figure 9 shows schematic representations of this permanent link test configuration. Category 6 Category 6 -to-jack Cord 1m (e.g., Panduit FP6X88TC) Channel Category 6 B Category 6 -to-jack Cord 1m (e.g., Panduit FP6X88TC) Channel Minimum segment length = 1m (3.28 ft.) Minimum segment B length = 9m (29.53 ft.) Maximum PL length = 90m (295.2 ft.) Figure 9. Schematic representations of permanent link testing via the lternate Model. 2017 Panduit Corp. ll Rights Reserved. 5

Conclusion Direct connect cabling is gaining in popularity as a cost-effective and reliable way to connect stationary network devices such as wireless access points, cameras, sensors, PoE lighting, digital signage and others. The easiest way to deploy direct connect cabling is to attach a field-installable plug at the end of the horizontal cable link where it inserts into the network device. The Panduit TX6 is a simple, easy to install two-piece plug that can be used in all direct connect cabling applications in the field today for fast and reliable terminations. DISCLIMER: This Technology Brief is for informational purposes only. Each customer should evaluate its own requirements prior to determining the direct connect cabling strategy that best fits its needs. ll Panduit products are subject to the terms, conditions, and limitation of its then current Limited Product Warranty, which can be found at www.panduit.com/warranty. 2017 Panduit Corp. ll Rights Reserved. 6