Fiber Management Tray (FMT) User Manual

Similar documents
Two Rack Unit (2RU) Fiber Management Tray (FMT) User Manual

Next Generation Frame Fiber Termination Block With MPO Connectors (FTB w/mpo) User Manual

FL1000 Wall-Mount Box Installation and Operation Guide

TrueNet 1U and 2U Fiber Panel Installation and Cable Routing Instructions

Optical Line Splitter Installation Instructions

NG3 High-Density Fiber Distribution Frame System Termination, Termination/Splice, VAM, and MPO Panels

Ethernet Test Access Panel (ETAP) User Manual

DS3 SPOT Bays (CLEC and TIE Bay) Installation and Maintenance Guide)

Next Generation Cross-Connect Crossbox Add-on Cabinet (NCX-XBA) User Manual

16-Port Chassis Media Converter System Manual

3 Angled Connector Housing (MC) Installation

Soneplex QLX Two-Position Chassis Installation Instructions

Pretium Rack-mountable 1U Housing Hardware

Outdoor FDH Termination Pole-Mount Cabinet With Universal Splitter Chassis User Manual

Spec Sheet. TrueNet TFP Series Rack Mount Fiber Panels. Features: Applications and Benefits:

Universal Patch Platform Uni-Patch System Patch and Test Module User Manual

High Density PEACOC v. 3.0 Fiber Patch Panel& FleT

TrueNet TFP Series Rack Mount Fiber Panels

OCM5 Splitters and Pass-Through Modules for CSX-3 Cabinets

Fibre Enlosures and Splicing

Rack Mount Interconnect Center (RIC3)

FACT OPTICAL DISTRIBUTION FRAME SYSTEM

AMP NETCONNECT* Gen II Vertical Storage Area Management (SAM) System

Rack Installation Instructions

ONE SD-LAN Wall Mount Splitter Housing (1LAN-SPLT C)

OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide

TABLE OF CONTENTS SECTION 1 TABLETOP CONFIGURATION SECTION 2 TABLETOP CONFIGURATION ACCESSORIES SECTION 3 SLIDE CONFIGURATION

Model GS7000 Node Expanded Fiber Tray Installation Instructions

Rack Mount Cabinet with Fiber Mgmt System, accepts up to 3 Adapter Plates. Rack Mount Cabinet with Fiber Mgmt System, accepts up to 6 Adapter Plates

Mini Wall-mount Building Terminal (WBM)

G12/G12x USER S MANUAL

Rackmount Keyboard Installation Instructions. Revision A A-0000

Flat Panel Static Wall Mount MSP-SS (GSM-210)

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

HD Flex Zero RU Cassette Holder and Bracket

Installation Job Aid for Ethernet Routing Switch 5900 Series

Fiber Optic Panels. 1st Edition. Fiber connectivity solutions

LSX Optical Distribution Frame

SYSTIMAX 360 ipatch 96F LC Upgrade Kit

3M Fiber Distribution Units 8400 Series

Installing the Cisco MDS 9020 Fabric Switch

3M Fibrlok II Angle Fiber Splice 2529-AS 3M Fibrlok 250 µm Angle Fiber Splice 2540-AS

RMG Series Rack Mount Fiber Enclosures

VDL-004. Miniature Manual Variable Optical Delay Line. User Guide

Agilent N2916B 6000 and 5000 Series Oscilloscope Rack Mount Kit

Soneplex DS3 MUX Module Installation Instructions

with Fiber Management Bar

Ioline 300/350HF System

Tower to Rack and Rack to Tower System Conversion Guide

actilib Library 2U Quick Start Guide

MASTERLINE Ultimate Hybrid High Voltage 4/12 (MLUH HV 4/12) blunt cut at BTS side

2U, 4U, and 7U Systems

High Density LSX 288-Position Panel

Titan Media Cart. Installation and Operation Manual

Fiber Management Tray 2 Rack Unit (2 RU) Style FMT-G Series

FIBRE ENCLOSURES AND SPLICING ACCESSORIES

Ordering Guide for FIST Blue Label Racks (FIST-GR3)

3M Fiber Distribution Units 8400 Series. The Network of Networks. Flexibility for. Networks. Growing

Wall Mounted Building Entrance Enclosure Instructions

CSS1 Contractor Series Light Sources and CSM1 Contractor Series Optical Power Meters User s Guide

Broadband Automatic Disconnect Switch. User Manual

TRC-190 User s Manual

Serial ATA Hot Swap Drive Cage Upgrade Kit for: Intel Server Chassis SC5200 Intel Server Chassis SC5250-E

Cable Routing Procedures for Dell PowerEdge R630 Systems

Liebert XDA Air Flow Enhancer. User Manual

Datasheet. Fiber Optic Modular Patch Panel Features

Spec Sheet. OmniReach FTTX Solutions DLX Fiber Optic Connector

Rack Power Distribution Unit AP7530, AP7540

SATA II HDD Canister KISS DA 435 Quick Reference Guide

EOS-6000 Series Optical A/B Switch User Manual DC Version

Model 4001A Modular System Bin Operating and Service Manual

SAVE THESE INSTRUCTIONS

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE

S5048F-ON. Set-up Guide

System Storage EXP3000 Rack Installation Instructions

The Nureva Span ideation system. Installation guide. Single panoramic system

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

Rack Installation Instructions

Tiger Serve1 Assembly Guide

Dell Networking S4100-ON Series. Set-Up Guide

3-4 SAS/SATA II HDD Canister Entry version USER S MANUAL XC-34D1-SA10-0-R. Document number: MAN A

OmniReach Outdoor FDH Termination Cabinet With Pre-installed Cables

Keysight 11878A 50 Ohm 3.5 mm Adapter Kit

LegacyPlus 7-OR SERIES RETURN TRANSMITTER INSTRUCTION MANUAL 7-OR-RT/xxx

TrueNet WMG Series Wall Mount Fiber Enclosures

Introduction to the CRS Back-to-Back System

Installation Manual. Mounting Instructions Mechanical Mounting. Luminato. Teleste Corporation

Instruction Sheet. PCS Series. Fiber\Cable Management Spool

TRC-190 User s Manual

Installation Job Aid for Ethernet Routing Switch 3600 Series

OPERATING MANUAL LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES

Customer Replacement Procedure

Manual Version: V1.00. Video Decoder Quick Guide

RS-232 Fiber Link Card System

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

FPX Series Fiber Panels Next Generation FPL

SYSTIMAX 360 ipatch Network Manager Module Faceplate Instructions

120Ra-1 Pentium III Processor Installation Insert

Dell OptiPlex All-in-One. Stand Installation Guide

Customer Replacement Procedure

Transcription:

Fiber Management Tray (FMT) User Manual Fiber Management Tray Content Page INTRODUCTION............................................................................. 2 ADMONISHMENTS........................................................................... 2 GENERAL SAFETY PRECAUTIONS................................................................. 3 1 PRODUCT DESCRIPTION.................................................................. 3 2 SPECIFICATIONS........................................................................ 6 3 UNPACKING THE PRODUCT................................................................ 7 4 MOUNTING THE FMT ON THE RACK........................................................... 8 5 INSTALLING VERTICAL CABLE GUIDES......................................................... 8 6 INSTALLING AND ROUTING CABLES......................................................... 10 6.1 Routing and Securing Cables........................................................ 10 6.2 Termination Only FMT Configuration................................................... 11 6.2.1 24-Position Termination Only Tray, Universal Entry.................................. 12 6.2.2 32-Position Termination Only Tray, Universal Entry.................................. 13 6.3 Termination and Storage FMT Configuration.............................................. 14 6.3.1 12-Position Termination and Storage Tray, Universal Storage........................... 14 6.3.2 16-Position Termination and Storage Tray, Universal Storage........................... 15 6.3.3 24-Position Termination and Storage Tray, Left/Right Storage........................... 16 6.4 Storage Only FMT Configuration...................................................... 17 6.4.1 Discrete Storage Tray...................................................... 17 6.4.2 Bulk Storage Tray......................................................... 18 (continued) 1220545 Rev A Page 1

Content Page 6.5 Termination and Splice FMT Configuration............................................... 19 6.5.1 12-Position Termination and Splice Tray......................................... 19 6.5.2 16- or 24-Position Termination and Splice Tray..................................... 23 6.6 Splice Only FMT Configuration....................................................... 27 6.6.1 12-, 24-, or 48-Position All Splice Tray.......................................... 27 7 OPERATION.......................................................................... 28 7.1 Opening Tray................................................................... 28 7.2 Accessing Sliding Adapter Packs...................................................... 29 7.3 Accessing Bulkhead Plate Adapters.................................................... 30 7.4 Closing the Tray................................................................. 31 8 CUSTOMER INFORMATION AND ASSISTANCE................................................... 32 INTRODUCTION Revision History This manual describes the ADC Fiber Management Tray (FMT) and provides all information required to install and use this product. The FMT is a fiber optic tray that provides a variety of rack-mount and functional options. All options are covered in this manual to the extent of relevance when the FMT is installed and used. For pre-sale FMT selection guidelines, refer to ADC catalog 100489PR 8/01 or obtain product information at www.adc.com. ISSUE DATE REASON FOR CHANGE Issue 1 11/2001 Original. Issue 2 04/2003 Revised to reflect changes in product design. Trademark Information ADC is a registered trademark of ADC Telecommunications, Inc. Related Publications ADC Fiber Management Tray Catalog 100489PR 8/01 ADMONISHMENTS Important safety admonishments are used in this manual to warn of possible hazards to persons or equipment. The admonishments in the form of Dangers, Warnings, and Cautions must be followed at all times. These warnings are flagged by use of a triangular alert icon (shown below), and are listed in descending order of severity of injury or damage and likelihood of occurrence. Page 2

. ADCP-90-326 Issue 2 April 2003 Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided. GENERAL SAFETY PRECAUTIONS Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector. 1 PRODUCT DESCRIPTION The ADC Fiber Management Tray (FMT) is a rack-mount, front-access fiber optic tray available in any of the following configurations: 24- or 32-position termination only (universal entry); 12- or 16-position termination and storage (universal storage); 24-position termination and storage (left or right storage); 12-, 16-, or 24-position termination and splice (left or right splice entry); 12-, 24-, or 48-position splice only (universal entry); 32-, 48-, or 60-cable bulk slack storage (capacity dependent on cable diameter); 16-cable discrete slack storage. Rack-mount options include the following types and rack widths: EIA or WECO, 19-inch (48.26 cm); EIA or WECO, 23-inch (58.42 cm); ETSI, 20.28 inch (51.5 cm). All rack-mount options (EIA, WECO, or ETSI) provide any of the following recess options: 2.2-inch (5.59 cm), 3.1-inch (7.9 cm), 5-inch (12.7 cm), 6.5-inch (16.5 cm), or 44 mm (1.73 inch). Figure 1 shows one of the FMT configurations, the 12-position termination and storage tray. Some of the features common to all FMT configurations are displayed. Page 3

The features shown include the following (from bottom left clockwise): Edge Protectors Protect cables from sharp angles at bend points. TIE LANCES (2 EACH SIDE) LEFT REAR RADIUS LIMITER OPEN LATCH PROTECTIVE COVER STORAGE RADIUS LIMITERS RIGHT REAR RADIUS LIMITER 18533-A EDGE PROTECTORS (6) SLIDING ADAPTER PACKS SLIDING RADIUS LIMITER WITH TRUMPET FLARE (2) MOUNTING BRACKET (2) Figure 1. FMT Features (12-Position Termination and Storage Tray, Universal Entry, Shown) Lock Open Latch Allows the technician to lock the FMT while working in the tray. Rear Radius Limiters (Left and Right) Maintain a protective, minimum-bend radius for cables routed into panel. Tie Lances Provide anchor points for securing fibers. Storage Radius Limiters Provide service loop storage for cable terminated in panel. Protective Cover Protects top side of panel. Mounting Brackets Adapt the tray for the different mounting options. The brackets are mounted in the factory based on customer request. Sliding Radius Limiter Provides protective entry point for cables. Trumpet flare slides backward when tray is pulled out and forward when tray is closed. Sliding Adapters Packs Each with two adapters, provide easy access for connecting cables and cleaning connectors. Product offerings for adapters/connectors include most industry-standard multimode and singlemode types. Figure 2 shows the fixed bulkhead version of the FMT. In this version, the sliding adaper packs are replaced with a stationary bulkhead. Page 4

BULKHEAD PLATE ADAPTERS 18542-A Figure 2. Fixed Bulkhead Version of FMT Figure 3 shows another configuration option, the 24-position termination and splice tray. Two splice trays, each accommodating 12 splices, are stacked on top of one another. 18535-A SPLICE TRAYS Figure 3. FMT With Splice Tray (24-Position Termination/Splice Tray Shown) Page 5

Figure 4 shows a closed tray with the trumpet flare in a closed position. Also shown is the optional lock. 18534-A (OPTIONAL) SLIDING RADIUS LIMITER WITH TRUMPET FLARE Figure 4. FMT Features (Closed Tray Shown) 2 SPECIFICATIONS Table 1 lists specifications for the Fiber Management Tray. Figure 5 shows the FMT dimensions for rack type, rack width, and recess options. ITEM Table 1. Fiber Management Tray Specifications DESCRIPTION Dimensions (H W D) See Figure 5 on page 7. Approximate Weight 7.9 lbs. (3.98 Kg) Configuration Options and Capacity Termination only (24 or 32 fibers) Termination/storage (12, 16, or 24 terminations) Bulk storage 3 mm O.D. cable: 32 cables, length 1.7 m (66 in.) each 2 mm O.D. cable: 48 cables, length 3.4 m each (132 in.) 1.7 mm O.D. cable: 60 cables, length 3.9 m (154 in.) each Discrete storage 3 mm O.D. cable: 16 cables, length 1.6 m (62.5 in.) each 2 mm O.D. cable: 16 cables, length 4.7 m (184 in.) each 1.7 mm O.D. cable: 16 cables, length 5.4 m (211 in.) each Termination and splice (12, 16, or 24 splices) Splice Only (12, 24, or 48 splices) Page 6

17.39 IN. (44.2 CM) 11.01 IN. (27.96 CM) RECESS OPTIONS 40 mm 1.535 IN. 3.9 CM 2.2-INCH 2.25 IN. 5.7 CM 3.1-INCH 3.07 IN. 7.8 CM 5-INCH 5.0 IN. 12.7 CM 6.5-INCH 6.535 IN. 16.6 CM TOP VIEW 1.71 IN. (4.34 CM) FRONT VIEW RACK TYPE OPTIONS ETSI WECO EIA 0.98 IN. 1.0 IN. 1.25 IN 2.5 CM 2.5 CM 3.25 CM RACK WIDTH OPTIONS ETSI 20.28 IN. 19-INCH EIA/WECO 18.31 IN. 23-INCH EIA/WECO 22.32 IN 51.5 CM 46.5 CM 56.7 CM 18536-A Figure 5. FMT Dimensions 3 UNPACKING THE PRODUCT Unpack and inspect the Fiber Management Tray as follows: 1. Inspect the exterior of the shipping container for evidence of rough handling that may have damaged the contents of the container. 2. Unpack the FMT and check for possible damage. 3. If damage is detected or if parts are missing, file a claim with the commercial carrier and then notify ADC Customer Service. Save damaged carton for inspection by the carrier. 4. Refer to Section 8 for repair, replacement, and warranty information. 5. Save the shipping container for use if equipment requires shipment at a future date. Page 7

4 MOUNTING THE FMT ON THE RACK For all mounting options, the FMT uses two mounting brackets, one on either side, with two mounting holes in each bracket (see Figure 6). Install the tray on the rack by installing the four #12-24 screws (provided) in the four mounting holes. Note: In some configurations, the same screw is used for both the mounting bracket (top hole) and the vertical cable guide (see next procedure). 18537-A MOUNTING HOLES Figure 6. FMT Mounting Holes 5 INSTALLING VERTICAL CABLE GUIDES Vertical cable guides (VCGs) are a product accessory that may be installed with FMTs when space permits. Table 2 summarizes the possible uses of VCGs for various combinations of rack width and recess. Table 2. Possible Uses of VGCs RACK WIDTH RECESS FIGURE 19 inches 44 mm (1.73 inch) VCGs not advised (48.26 cm) 2.2-inch (5.59 cm) 3.1-inch (7.9 cm) Figure 7 5-inch (12.7 cm) 6.5-inch (16.5 cm) 23 inches (58.42 cm) 44 mm (1.73 inch) 2.2-inch (5.59 cm) 3.1-inch (7.9 cm) 5-inch (12.7 cm) 6.5-inch (16.5 cm) Figure 8 Mount the VCGs using the following procedure: 1. If the rack width is 19 inches (48.26 cm) or ETSI (20.28 inches, 51.5 cm) and: a. Recess is 44 mm (1.73 inch) or 2.2-inch (5.59 cm), use of VCGs is not advised. b. Recess is 3.1-inch (7.9 cm), 5-inch (12.7 cm), or 6.5-inch (16.5 cm), mount the VCGs on the rack narrow flange using the same screw and hole position as used for the top mounting screw on the panel mounting bracket. Refer to Figure 7. Page 8

VERTICAL CABLE GUIDE 18616-A MOUNTING BRACKET Figure 7. Installing VCGs (19-Inch Rack Mount) 2. If the rack width is 23 inches (58.42 cm), mount the VCGs on the rack narrow flange using the same screw and hole position as used for the top mounting screw on the panel mounting bracket. Refer to Figure 8. MOUNTING BRACKET VERTICAL CABLE GUIDE 18698-A Figure 8. Installing VCGs (23-Inch Rack Mount) Page 9

6 INSTALLING AND ROUTING CABLES Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector. 6.1 Routing and Securing Cables The FMT may be configured to provide termination only, termination and storage, storage only, termination and spice, or splice only functions. For each configuration, the fiber optic cables or patch cords are routed to the FMT, installed within the sliding tray, and secured. All cables enter the FMT though one of the two sliding trumpets flares, located on the left and right sides of the FMT. When properly installed, the slack loop that forms when the FMT is closed is taken up within the FMT by movement of the sliding trumpet flare. Figure 9 shows a typical routing. Prior to routing the cables, review the installation procedure that corresponds to the configuration (provided in subsections 6.2 through 6.6 below). Then use the following guidelines for routing and installing the cables or patch cords: 1. Open the tray fully and lock it using the lock open latch (see subsection 7.1). 2. Route the cables to the FMT. The cables may be routed from either overhead or under the floor and to the left or right side of the FMT depending on configuration requirements. 3. Secure the cable on the rack using a cable clamp such as shown in Figure 9. Note: Install the cable clamp kit following the instructions provided in the installation drawing shipped with the kit. 4. Route the cables into the FMT through the specified sliding trumpet flare(s). 5. Route and connect the cables within the FMT as required by the configuration. Refer to the installation procedure that corresponds to the FMT configuration. 6. Adjust the cables within the FMT until all excess slack is removed or stored. 7. Secure the cables to the back of the FMT at the rear tie-off point (see Figure 9). Note that a tie-off point is provided on both the left and right side. Page 10

CABLE CLAMP AND MOUNTING BRACKET TIE LANCES CABLE CLAMP AND MOUNTING BRACKET DETAIL OF CABLE TIE-OFF POINT ROUTE CABLE INTO FMT THROUGH TRUMPET FLARE 18538-A Figure 9. Routing and Securing Cable - Typical Configuration 8. Use the kurly locks provided to bundle fibers together between the sliding radius limiter and the rear radius limiter as shown in the applicable installation drawing. 9. Adjust the cable position with the cable clamp as required to remove excess slack. 10. Close the tray (see subsection 7.4). 6.2 Termination Only FMT Configuration Cables routed into the FMT for termination only will typically be pre-terminated individual cables of 2 mm or 3 mm diameter. Refer to the following instructions. Page 11

6.2.1 24-Position Termination Only Tray, Universal Entry Route and install the cables as shown in Figure 10. ROUTE FIBERS ALONG THE SOLID ARROW ON INDICATED PATH, THEN FOLLOW THE APPROPRIATE DOTTED LINE. 1 1 2 2 2 2 2 2 2 2 1 FROM BOTH SIDES ROUTE THE FIRST EIGHT FIBERS DIRECTLY INTO THE BACK EIGHT ADAPTERS. 2 FROM BOTH SIDES ROUTE THE REMAINING 16 FIBERS AROUND THE EDGE PROTECTORS (FOUR FIBERS PER EDGE PROTECTOR) AND INTO THE FRONT EIGHT ADAPTERS. 16899-A Figure 10. Cable Routing for 24-Position Termination Only Tray, Universal Entry Page 12

6.2.2 32-Position Termination Only Tray, Universal Entry Route and install the cables as shown in Figure 11. ROUTE FIBERS ALONG THE SOLID ARROW ON INDICATED PATH, THEN FOLLOW THE APPROPRIATE DOTTED LINE. 5 1 6 2 3 4 6 2 6 2 6 2 2 7 5 ROUTE THE FIRST EIGHT FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE LEFT REAR RADIUS LIMITER, AND INTO THE FIRST EIGHT ADAPTERS. 6 ROUTE THE NEXT 16 FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE LEFT REAR RADIUS LIMITER, AROUND THE EDGE PROTECTORS, AND INTO THE NEXT 16 ADAPTERS. 7 ROUTE THE REMAINING EIGHT FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE LEFT REAR RADIUS LIMITER, AROUND THE CORNER EDGE PROTECTOR, AND INTO THE REMAINING EIGHT ADAPTERS. 1 ROUTE THE FIRST SIX FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE RIGHT REAR RADIUS LIMITER, AND INTO THE FIRST SIX ADAPTERS. 2 ROUTE THE NEXT 18 FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE RIGHT REAR RADIUS LIMITER, AROUND THE EDGE PROTECTORS, AND INTO THE NEXT 18 ADAPTERS. 3 ROUTE THE NEXT FOUR FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE RIGHT REAR RADIUS LIMITER, AND INTO THE NEXT FOUR ADAPTERS. 4 ROUTE THE REMAINING FOUR FIBERS THROUGH THE TRUMPET, AROUND THE SLIDING RADIUS LIMITER, AROUND THE RIGHT REAR RADIUS LIMITER, AND INTO THE REMAINING FOUR ADAPTERS. 16903-A Figure 11. Cable Routing for 32-Position Termination Only Tray, Universal Page 13

6.3 Termination and Storage FMT Configuration Cables routed into the FMT for termination and storage will typically be pre-terminated individual cables of 2 mm or 3 mm outside diameter. For instructions on routing the cables within the tray, select from the subsections below based on the tray configuration being installed. 6.3.1 12-Position Termination and Storage Tray, Universal Storage Route and install the cables as shown in Figure 12. ROUTE FIBERS ALONG THE SOLID ARROW ON INDICATED PATH, THEN FOLLOW THE APPROPRIATE DOTTED LINE. 4 4 1 1 2 2 3 3 1 FROM BOTH SIDES ROUTE THE FIRST FOUR FIBERS AROUND THE FIRST EDGE PROTECTOR AND INTO THE FIRST FOUR ADAPTERS. 2 FROM BOTH SIDES ROUTE THE NEXT FOUR FIBERS AROUND THE NEXT EDGE PROTECTOR AND INTO THE NEXT FOUR ADAPTERS. 3 FROM BOTH SIDES ROUTE THE LAST FOUR FIBERS AROUND THE LAST EDGE PROTECTOR AND INTO THE LAST FOUR ADAPTERS. 4 WIND SLACK AROUND STORAGE SPOOL IN THE DIRECTION SHOWN. 16894-A Figure 12. Cable Routing for 12-Position Termination and Storage Tray, Universal Storage Page 14

6.3.2 16-Position Termination and Storage Tray, Universal Storage Route and install the cables as shown in Figure 13. ROUTE FIBERS ALONG THE SOLID ARROW ON INDICATED PATH, THEN FOLLOW THE APPROPRIATE DOTTED LINE. 8 7 6 5 9 9 1 2 3 4 1 ROUTE THE FIRST FOUR FIBERS AROUND THE FIRST EDGE PROTECTOR AND INTO THE FIRST FOUR ADAPTERS. 2 ROUTE THE SECOND FOUR FIBERS AROUND THE SECOND EDGE PROTECTOR AND INTO THE NEXT FOUR ADAPTERS. 3 ROUTE THE THIRD FOUR FIBERS AROUND THE THIRD EDGE PROTECTOR AND INTO THE THIRD FOUR ADAPTERS. 4 ROUTE THE LAST FOUR FIBERS AROUND THE FOURTH EDGE PROTECTOR AND INTO THE THIRD FOUR ADAPTERS. 5 ROUTE THE FIRST FOUR FIBERS AROUND THE FIRST EDGE PROTECTOR AND INTO THE FIRST FOUR ADAPTERS. 6 ROUTE THE SECOND FOUR FIBERS AROUND THE SECOND EDGE PROTECTOR AND INTO THE NEXT FOUR ADAPTERS. 7 ROUTE THE THIRD FOUR FIBERS AROUND THE THIRD EDGE PROTECTOR AND INTO THE THIRD FOUR ADAPTERS. 8 ROUTE THE LAST FOUR FIBERS AROUND THE FOURTH EDGE PROTECTOR AND INTO THE THIRD FOUR ADAPTERS. 9 WIND SLACK AROUND STORAGE SPOOLS IN THE DIRECTION SHOWN. 16897-A Figure 13. Cable Routing for 16-Position Termination and Storage Tray, Universal Storage Page 15

6.3.3 24-Position Termination and Storage Tray, Left/Right Storage Route and install the cables as shown in Figure 14. The figure shows a left-storage configuration with sliding adapter packs. For a right-entry storage, the routing is a mirror image of what is shown. Routing is the same for trays with bulkhead plate adapters (route left storage as shown below; route right storage as mirror image). ROUTE FIBERS ALONG THE SOLID ARROW ON INDICATED PATH, THEN FOLLOW THE APPROPRIATE DOTTED LINE. 3 AND 5 4 1 4 4 4 5 2 1 ROUTE THE FIRST 12 FIBERS AROUND THE BACK STORAGE SPOOL AND INTO THE BACK 12 ADAPTERS. 2 ROUTE THE SECOND 12 FIBERS AROUND THE FRONT STORAGE SPOO AND INTO THE FRONT 12 ADAPTERS. 3 ROUTE THE FIRST EIGHT FIBERS DIRECTLY INTO THE BACK EIGHT ADAPTERS. 4 ROUTE THE REMAINING 16 FIBERS AROUND THE EDGE PROTECTORS (FOUR FIBERS PER EDGE PROTECTOR) AND INTO THE FRONT EIGHT ADAPTERS. 5 WIND SLACK AROUND STORAGE SPOOLS IN THE DIRECTION SHOWN. 16898-A Figure 14. Cable Routing for 24-Position Termination and Storage Tray, Left Storage (Same Routing for Bulkhead Style) Page 16

6.4 Storage Only FMT Configuration Storage only FMT trays are of two types, discrete and bulk. Refer to the following subsections. 6.4.1 Discrete Storage Tray Route and install cables as shown in Figure 15. Storage tray operation is shown in Figure 16. 16896-A Figure 15. Cable Routing for Discrete Storage Tray 18539-A Figure 16. Discrete Storage Tray Operation Page 17

6.4.2 Bulk Storage Tray Note: The number and length of cables that can be stored in a bulk storage tray depends on the cable dimension (refer to Table 1 on page 6). Route and install the cables as shown in Figure 17. 16895-A Figure 17. Cable Routing for Bulk Storage Tray Page 18

6.5 Termination and Splice FMT Configuration Termination and splice trays include configurations providing 12, 16, or 24 termination and splice positions. For details, refer to the next two subsections. The first subsection covers the 12-position configuration. The 16- and 24-position configurations are documented together in the second subsection. Note: Splicing instructions are not included. For splicing instructions, follow local practice. 6.5.1 12-Position Termination and Splice Tray Install the cables for a 12-position termination and splice tray as follows: 1. Break out the cable corresponding to the dimensions provided in Figure 18. 900 MICRON JACKETED FIBERS SECTION OF SOFT WALL JACKET SOFT WALL PIGTAIL BUNDLE 48 IN. (121.9 CM) 1 IN. (2.5 CM) 16967-A 133 IN. (337.8 CM) Figure 18. 12-Position Termination and Splice Tray Breakout Dimensions 2. Route the cables into the tray as shown in Figure 19, and perform the splices outside the tray at an adjacent work area, as shown. Perform the splices following local practice. Refer to pigtail installation drawing (provided with FMT) for pigtail connection scheme. 3. Loop the cables three times around the radius limiters as shown in Figure 20. Note: Tie off the cable at the tie off point shown in Figure 20, using a one-inch section of soft wall jacket per the breakout dimensions shown in Figure 18. 4. Carefully position the tray within the splice area as shown in Figure 21. 5. Use the kurly locks provided to bundle fibers together as shown in Figure 22. 6. Verify that the completed tray looks as shown (see Figure 22). Page 19

TIE OFF TO SLIDING ADAPTER PACKS CUSTOMER CUSTOMER PRE-TERMINATED SPLICE TRAY 16974-A Figure 19. Cable Routing for 12-Position Termination and Splice Tray, Step 2 Page 20

TIE OFF TO SLIDING ADAPTER PACKS LOOP THREE TIMES CUSTOMER CUSTOMER PRE-TERMINATED SPLICE TRAY 16975-A Figure 20. Cable Routing for 12-Position Termination and Splice Tray, Step 3 Page 21

TO SLIDING ADAPTER PACKS TIE OFF CUSTOMER 16976-A Figure 21. Cable Routing for 12 Termination and Splice Tray, Step 4 TIE OFF S CUSTOMER PATCHCORDS CUSTOMER 16978-A Figure 22. Completed Cable Routing for 12-Position Termination and Splice Tray Page 22

6.5.2 16- or 24-Position Termination and Splice Tray Install the cables for a 16- or 24-position termination and splice tray as follows: Note: For 16- and 24-position termination and splice trays with bulkhead plate adapters, routing is the same as shown for trays in this procedure with sliding adapter packs. 1. Break out the cable corresponding to the dimensions provided in Figure 23. 900 MICRON JACKETED FIBERS SECTION OF SOFT WALL JACKET SOFT WALL PIGTAIL BUNDLE 48 IN. (121.9 CM) 1 IN. (2.5 CM) 17003-A 134 IN. (340.4 CM) Figure 23. 16/24 Termination and Splice Tray Breakout Dimensions 2. Route the cables into the tray as shown in Figure 24, and perform the splices outside the tray at an adjacent work area, as shown. Perform the splices following local practice. Refer to pigtail installation drawing (provided with FMT) for pigtail connection scheme. 3. Loop the cables three times around the radius limiters, as shown in Figure 25. Note: Tie off the cable at the tie off point shown in Figure 25, using a 1-inch (2.54 cm) section of soft wall jacket per the breakout dimensions shown in Figure 23. 4. Carefully position the tray within the splice area as shown in Figure 26. 5. Use the kurly locks provided to bundle the fibers together, as shown in Figure 24 and Figure 25. 6. Verify that the completed tray looks as shown (see Figure 27 for the 16-position tray or Figure 28 for the 24-position tray). Page 23

TIE OFF TO SLIDING ADAPTER PACKS CUSTOMER CUSTOMER PRE-TERMINATED SPLICE TRAY 16968-A Figure 24. Cable Routing for 16- or 24-Position Termination and Splice Tray, Step 2 Page 24

TIE OFF TO SLIDING ADAPTER PACKS LOOP THREE TIMES CUSTOMER CUSTOMER PRE-TERMINATED SPLICE TRAY 16970-A Figure 25. Cable Routing for 16- or 24-Position Termination and Splice Tray, Step 3 Page 25

TIE OFF TO SLIDING ADAPTER PACKS CUSTOMER 16971-A Figure 26. Cable Routing for 16- or 24-Position Termination and Splice Tray, Step 4 TIE OFF S CUSTOMER PATCHCORDS CUSTOMER 16973-A Figure 27. Completed Cable Routing for 16-Position Termination and Splice Tray (Same Routing for Bulkhead Style) Page 26

TIE OFF S CUSTOMER PATCHCORDS CUSTOMER 16972-A Figure 28. Completed Cable Routing for 24-Position Termination and Splice Tray (Same Routing for Bulkhead Style) 6.6 Splice Only FMT Configuration 6.6.1 12-, 24-, or 48-Position All Splice Tray Route cables into the splice tray as shown in Figure 29. SPLICE TRAY 18540-A Figure 29. Cable Routing for All Splice Tray (12-, 24- or 48-Position) Page 27

7 OPERATION The term operation refers to procedures performed on an ongoing basis after the FMT is installed. The only FMT trays that require operation are those having a termination function. Patch cords may be installed in such trays for use in connecting or testing equipment. When routing patch cords, refer to the routing diagrams provided in Section 6. For instructions on accessing adapters, refer to the following instructions. 7.1 Opening Tray To open the FMT tray, slide the release tabs inward with both hands and pull the drawer straight out as far as it goes. While working in the tray, lock the tray in position using the lock open latches shown in Figure 30. Rotate the latches downward to the lock open position shown in the figure. OPEN LATCH (UNED POSITION) OPEN LATCH (ED POSITION) 18706-A Figure 30. Tray Locked in Open Position Page 28

7.2 Accessing Sliding Adapter Packs Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector. Note: Always inspect connectors and adapters when connecting connectors to adapters. For cleaning procedures, refer to ADCP-90-139. To access a sliding adapter pack (Figure 31): 1. Route the patch cord into the tray as shown in the appropriate diagram in Section 6. 2. Lift up the release tab and slide up the adapter pack. 18541-A Figure 31. Removing Dust Cap From Sliding Adapter 3. Pull the dust cap straight out. 4. Connect the patch cord connector to the adapter. 5. Slide down the adapter back to its home position. 6. Close the tray. Page 29

7.3 Accessing Bulkhead Plate Adapters Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector. Note: Always inspect connectors and adapters when connecting connectors to adapters. For cleaning procedures, refer to ADCP-90-139. Use the following procedure to connect a patch cord to an FMT having bulkhead plate adapters: 1. Route the patch cord into the tray as shown in the appropriate diagram in Section 6. 2. Pull the dust cap straight out. 3. Connect the patch cord connector to the adapter. 4. Close the tray. 18552-A Figure 32. Removing Dust Cap From Bulkhead Plate Adapter Page 30

7.4 Closing the Tray Close the tray using the following procedure: 1. Release the lock open latch ( unlocked position shown in Figure 30 on page 28). 2. If closing a tray with sliding adapter pack, fully lower and seat all adapter packs. 3. Assure that all cables and fibers are properly secured and located below the top surface of the tray. 4. Assure that all unused adapters are covered with dust caps. 5. Slowly close the tray, observing that no fiber kinks or microbends occur as a result of fiber routing. Page 31

8 CUSTOMER INFORMATION AND ASSISTANCE PHONE: EUROPE Sales Administration: +32-2-712-65 00 Technical Assistance: +32-2-712-65 42 U.S.A. OR CANADA Sales: 1-800-366-3891 Extension 73000 Technical Assistance: 1-800-366-3891 Extension 73475 ELSEWHERE Sales Administration: +1-952-938-8080 Technical Assistance: +1-952-917-3475 SYSTEM INTEGRATION DIVISION (SID) +1-952-294-3600 WRITE: U.S.A. ADC TELECOMMUNICATIONS, INC PO BOX 1101, MINNEAPOLIS, MN 55440-1101, USA ADC EUROPEAN CUSTOMER SERVICE, INC BELGICASTRAAT 2, 1930 ZAVENTEM, BRUSSELS, BELGIUM U.S.A. PRODUCT INFORMATION AND TECHNICAL ASSISTANCE: WWW.ADC.COM technical@adc.com 13944-G Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be varified at any time by contacting ADC s Technical Assistance Center. All Rights Reserved Printed in U.S.A Page 32