The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal.

Similar documents
Switch Actuator, 4-fold, 20 A, MDRC AT/S , GH Q R0111

Switch Actuator, 4-fold, 16 A, MDRC AT/S , GH Q R0111

ABB i-bus EIB. Shutter Actuator, 2-fold, 6 A, 230 VAC, MDRC JA/S 2.6.1, GH Q R0111

Line Coupler, MDRC LK/S 2.1, GH Q R0001

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

Line Coupler, MDRC LK/S 3.1, GH Q R0001

ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

IP gateway, MDRC IG/S 1.1, GH Q R0001

Operating voltage Maximum

ABB i-bus KNX Blower/Fan Coil-Actuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

KNX/EIB Intelligent Installation Systems

K-BUS R. Dimming Actuators. User manual-ver. 4 KA/D KA/D KA/D KA/D 04.T1.1 ADTV-04/16.1 KA/D 04.L1.1 ADLD-04/

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

K-BUS Shutter Actuator. User manual-ver. 1

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011

EAE KNX Switch Actuator

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus EIB / KNX Shutter Actuator with Manual Operation, 4-fold, SMI, MDRC JA/S 4.SMI.1M. Product Manual. Intelligent Installation Systems ABB

ABB i-bus KNX Binary Inputs BE/S Product Manual

Product and functional description

Push Button Interface UP 220D31

ABB i-bus KNX Blower Actuator FCL/S x Product Manual

Manual and application description KNX/EIB LED driver V2.0

Product and Applications Description. Application programs. instabus EIB Technical Product Information. February 2012

ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011

EAE KNX Room Control Unit Product Manual RCUXXYY

1 Safety instructions. 2 Device components. 3 Function. Control unit, 1-10 V 3-gang. Order-No. : Operating instructions

Datasheet RCUXXYY EAE KNX Room Control Unit RCUXXYY DT R1.0. General Description. EAE Technology Page 1/10

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

ABB i-bus. KNX JRA/S Blind/Roller Shutter Actuator with Binary Inputs Product Manual

Product Manual V ABB i-bus EIB / KNX DALI-Gateway DG/S 1.1. Intelligent Installation Systems ABB

Product and functional description

Operating instructions only for authorized, skilled electricians with EIB training

1 Safety instructions. 2 Device components. 3 Function. Control unit 1-10 V, 3-gang. Art.-No.: 2193 REG. Operationsmanual

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

ABB i-bus KNX Application Unit Time ABZ/S 2.1 Product Manual

High-performance switching actuators

Product and functional description

Product and functional description

Manual and application description 4 channel 0-10V dimmer V2.0

Datasheet - SLB 200-C04-1R

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

6173 AG GJB A0138

ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

4-gang and 8-gang switch actuator 16A C-load SE

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

Electrical devices may only be mounted and connected by electrically skilled persons.

ABB i-bus KNX Weather Unit, 1-fold, MDRC WZ/S , 2CDG110184R0011

ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

Figure 1: Device components

ABB i-bus KNX HCC/S Heating/cooling circuit controller

ABB i-bus KNX Room Master RM/S 3.1 Product Manual

SeeTool - Solutions for KNX

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 Controls:

Product manual. Mylos KNX 350w Dimmer 2CSYK1205C/S

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

Extension module for lighting control

Operating Instructions. DALI-Gateway

Product and functional description

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Siemens Spares. RL 513D23 Switching actuator (relay), 3 x 6A. Technical Product Information

Use of the application program. Functional description. GAMMA instabus Application program description. April A4 Roller shutter switch

KNX DALI Gateway Plus - User Manual

KNX/EIB KNX Blind actuator. 1 Safety instructions. 2 Device components. Blind actuator 4-gang 24 V DC Order-No. :

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies

Supplementary operating instructions for your air curtain system Controller TMC 500

PRODUCT MANUAL. ABB i-bus KNX DG/S x DALI-Gateway Basic

ABB i-bus KNX Logic Controller ABA/S 1.2.1, 2CDG110192R0011

ABB i-bus KNX Fan Coil Actuator FCA/S 1.1M Product Manual

Product and functional description

Din Rail 8 Input / 8 Output Module

PSR UC/ESAM4/3X1/1X2/B

ABB i-bus KNX BCI/S Boiler/Chiller Interface

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

Operating Instructions

Din Rail 4 Output Module BO04A01KNX

DIN RAIL 12/8/4 OUTPUT MODULE. BOxxB01KNX. Product Handbook

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

The output variables can be force-controlled from a coordinating control system.

The Energy Savers. Universal dimmer switches, capacity enhancer and 1-10V controllers. Selection table for universal dimmer switches,

SK TU4-CAO-C Part number:

Elo-1145-MSS-Zentraleinheit 471 M41 H31.book Page 1 Tuesday, September 6, :10 PM, Datum:

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

Four-channel Venetian blind actuator 230 V Installation Instructions

Push button UP 287, 4 - fold

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

KNX/EIB Product documentation. Issue:

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

The bodyguards. Current relay, mains monitoring relay, currentlimiting relay and mains disconnection relay

SK CU4-CAO Part number:

Transcription:

, GH Q631 0047 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. Using eight floating contacts, it switches eight groups of electrical consumer devices that are independent of each other. It is particularly suitable for switching loads with high switch-on peaks, e.g. shunt compensated fluorescent lamps. The device does not require an additional power supply. In case of bus voltage failure the actuator can switch on the load circuit (e.g. as working or emergency lighting). The output states are displayed at the front. Manual operation is also possible at any time, even without bus voltage. 5 5 SK 0109 B 00 Technical Data Power supply EIB 24 VDC, via the Bus line Outputs 8 floating contacts Switching voltage 230 V AC / 400 V AC Switching current at 230 V AC max. 16 A / AC1, 10 A / AC3 Switching current at 400 V AC max. 10 A / AC1, 6 A / AC3 Switching current at, 5 V AC / DC min. 480 ma Switching current at, 10 V AC / DC min. 240 ma Switching current at 24 V AC / DC min. 100 ma Max. switch-on-current max. 500 A Power of capacitor max. 200 µf Basic time delay typically 20 ms per relay on single operation Time delay on switching operation 1 contact typically 1 s 2 contacts concurrent typically 2 s n contacts concurrent typically n x 1 s 8 contacte concurrent typically 8 s Contact life mechanical contact endurance min. 5 x 10 6 electric contact endurance min. 10 5 at 230 V AC 16 A / AC1 electric contact endurance min. 3 x 10 4 under fluorescent lanp load,c = 200 µf (according to VDE 0632 Teil 1) Operation and display elements red LED and push button for assigning the physical address 8 switch position indicators also used for manual operation Connections Load circuit two screw terminals each, Wire range: 0,2 2,5 mm 2 finely-stranded 0,2 4,0 mm 2 single-core EIB Bus terminal (included with supply) Type of protection IP 20, EN 60 529 Ambient temperature range Operation - 5 C 45 C Storage - 25 C 55 C Transport - 25 C 70 C Design Modular installation device, prom Housing, colour Plastic housing, grey Mounting on 35 mm mounting rail, DIN EN 50022 Dimensions 90 x 144 x 64 mm (H x W x D) Mounting depth/width 68 mm / 8 modules at 18 mm Weight 0,6 kg Certification EIB-certified CE norm in accordance with the EMC guidence and the low voltage guidelinie Page 1 of 8

, GH Q631 0047 R0111 Anwendungsprogramme Anzahl max. Anzahl max. Anzahl Kommunikationsobjekte Gruppenadressen Zuordnungen Switch Logic Status Time /5 24 35 36 5 5 Wiring diagramm 1 2 3 4 SK 0205 Z 00 1 Connecting terminals 3 Programming push button and LED for Outputs A H 4 Bus terminal 2 Marker tags Note Caution: Prior to programming, service release A of ETS2 V1.1 or higher must be installed on the commissioning-pc. If this is not carried out, the device cannot function and can no longer be programmed. In order to avoid the danger of electric shock due to feedback from various external conductors, an all-pole disconnection must be complied with. The basic time delay is extended if the outputs are switched several times in succession. Page 2 of 8

, GH Q631 0047 R0111 Switch Logic Status Time /5 Selection in ETS2 ABB Output The application program makes the same number of parameters and communication objects available for each output. Depending on the settings selected in the individual parameters, various communication objects and parameters are displayed or hidden. Switch In the default setting, the actuator switches the relay on when it receives a 5 Binary output, 8-fold telegram with the value 1 and swit- The parameter Invert object no.... is 5 ches it off on receipt of a telegram with the value 0. If the parameter Switching mode is set to normally closed contact, the actuator switches the relay on when it receives a telegram with the value 0 and switches it off on receipt of a telegram with the value 1. Status The individual outputs can send their status on the bus. The parameter Operation mode must be set to switch with active status feedback in order to do so. In this mode, the current output status is sent via a further communication object Output... / Status telegr.. Depending on the setting selected in the parameter Send status feedback, this object can always send its status on the bus or only if the value changes. In the setting always, if the Switch object receives a telegram that does not cause a change at the output, the status object continues to send, regardless of its status. This status signal is also sent even if the same status has previously been sent. In the setting only if value changes, the output status is only sent after a change in the output value. Logic A logic AND or a logic OR function can be selected with the parameter Logical connection. In both cases, ETS2 displays an additional communication object for the output. The actuator then links the values of communication objects 0 and 8 for output A and objects 1 and 9 for output B etc. and switches the relay according to the result. available to implement for example a logic AND or logic OR function with an inverted input. Normally all communication objects have the value 0 after bus voltage recovery. If a logical connection has been assigned, it is possible to specify a definite value using the parameters Value of object no. 8/.../no. 15 at bus voltage recovery. The logical connection is evaluated immediately after bus voltage recovery. Time A time function can be assigned separately to each output. The parameter Time function must therefore be activated. In case a time function is assigned, it is possible to choose between a staircase lighting function and an ON/OFF delay. If a logical connection has already been assigned, only an ON and/or OFF delay can be assigned. The time for the staircase lighting function and the ON/OFF delay is calculated using a base and factor. The smallest possible base and the largest possible factor should be selected when setting these two values. It is also possible to invert the status response. As a result, a 0 is sent after switching on while a 1 is sent after switching off. The following applies for both time function: after the receipt of each telegram that triggers a time function, the respective time function is restarted. Staircase lighting function The staircase lighting function is activated by a telegram with the value 1 at the Switch communication object. After the set time, the output is automatically switched off again. Page 3 of 8

, GH Q631 0047 R0111 In addition, it is possible to activate or deactivate the staircase lighting function via the communication object Operation mode. The parameter Staircase lighting function can be activated/deactivated by object no. must be set to yes so that the communication object Operation mode can be enabled. If a 0 is sent to this object, the staircase lighting function is activated. If a 1 is sent, it is deactivated. 5 5 If the staircase lighting function is activated and a 1 is sent to the Operation mode object, the staircase lighting function remains active until the set period has elapsed. It is then deactivated and the actuator output can be switched on permanently with a 1 to the Switch communication object or permanently switched off with a 0. If the output is switched on and a 0 is sent to the Operation mode object, the staircase lighting function switches on and the output is switched off after the preset time. With the parameter Invert object no...., it is also possible to invert the Operation mode object. In this case, the staircase lighting function switches on with a 1 and switches off again with a 0. ON/OFF delay If the type of the time function is set to switch ON/OFF delay, the output switches on with the set ON delay after the receipt of a 1 at the Switch communication object. If a 0 is received at the Switch object, the output switches off with the set delay. If a logical connection has been assigned, the ON delay only becomes active once the logical condition has been met. The OFF delay is only active when the logical condition is no longer being met. Default The default position of the relay contact on bus voltage failure and recovery can be set separately for each output. The two parameters Preferred position at... are available for this purpose. This setting refers to the relay contact and is independent of the setting normally opened contact or normally closed contact that has been selected for the switching mode. Bus voltage failure/recovery There is the possibility with the general parameter Inactive waiting time after bus voltage recovery to set the period after which the execution or sending of incoming telegrams shall be triggered again after bus voltage recovery. The behaviour after bus voltage recovery can be set separately for each output with the parameter Value of obj. no.... at bus voltage recovery. Directly after bus voltage recovery, the individual outputs assume the set default positions of the contacts. During the inactive waiting time, incoming telegrams are registered but not evaluated. Once the waiting time has elapsed, the objects assume the value that has been defined in the parameters Value of obj. no.... at bus voltage recovery. If however this parameter has been set to read value via EIB, the actuator sends a read telegram and then assumes the value of the response telegram. If the parameter Preferred position after inactive waiting time is set at depending on obj. no., the output contact is switched according to the value of object no.. If the parameter Preferred position after inactive waiting time is set at unchanged, the output contact remains in the position that has been set for bus voltage recovery until new telegrams are received via the EIB. After the programming of the device the default position of the outputs is open (switched off). In the following inactive waiting time the devices behave as after bus voltage recovery. Page 4 of 8

, GH Q631 0047 R0111 0 1 bit Output A Switch 1 1 bit Output B Switch 2 1 bit Output C Switch 3 1 bit Output D Switch 4 1 bit Output E Switch 5 1 bit Output F Switch 6 1 bit Output G Switch 7 1 bit Output H Switch 5 with status response 5 16 1 bit Output A Status telegr. 17 1 bit Output B Status telegr. 18 1 bit Output C Status telegr. 19 1 bit Output D Status telegr. 20 1 bit Output E Status telegr. 21 1 bit Output F Status telegr. 22 1 bit Output G Status telegr. 23 1 bit Output H Status telegr. with inverted status response 16 1 bit Output A Invert status telegr. 17 1 bit Output B Invert status telegr. 18 1 bit Output C Invert status telegr. 19 1 bit Output D Invert status telegr. 20 1 bit Output E Invert status telegr. 21 1 bit Output F Invert status telegr. 22 1 bit Output G Invert status telegr. 23 1 bit Output H Invert status telegr. with logical OR connection 0 1 bit Output A Logical OR connection 1 1 bit Output B Logical OR connection 2 1 bit Output C Logical OR connection 3 1 bit Output D Logical OR connection 4 1 bit Output E Logical OR connection 5 1 bit Output F Logical OR connection 6 1 bit Output G Logical OR connection 7 1 bit Output H Logical OR connection 8 1 bit Output A Logical OR connection 9 1 bit Output B Logical OR connection 10 1 bit Output C Logical OR connection 11 1 bit Output D Logical OR connection 12 1 bit Output E Logical OR connection 13 1 bit Output F Logical OR connection 14 1 bit Output G Logical OR connection 15 1 bit Output H Logical OR connection Page 5 of 8

, GH Q631 0047 R0111 with logical AND connection 0 1 bit Output A Logical AND connection 1 1 bit Output B Logical AND connection 2 1 bit Output C Logical AND connection 3 1 bit Output D Logical AND connection 4 1 bit Output E Logical AND connection 5 1 bit Output F Logical AND connection 6 1 bit Output G Logical AND connection 7 1 bit Output H Logical AND connection 8 1 bit Output A Logical AND connection 9 1 bit Output B Logical AND connection 10 1 bit Output C Logical AND connection 5 11 1 bit Output D Logical AND connection 5 12 1 bit Output E Logical AND connection 13 1 bit Output F Logical AND connection 14 1 bit Output G Logical AND connection 15 1 bit Output H Logical AND connection with inverted logical connection 8 1 bit Output A Invert logical... connection 9 1 bit Output B Invert logical... connection 10 1 bit Output C Invert logical... connection 11 1 bit Output D Invert logical... connection 12 1 bit Output E Invert logical... connection 13 1 bit Output F Invert logical... connection 14 1 bit Output G Invert logical... connection 15 1 bit Output H Invert logical... connection with activation/deactivation of staircase lighting function 8 1 bit Output A Operation mode 9 1 bit Output B Operation mode 10 1 bit Output C Operation mode 11 1 bit Output D Operation mode 12 1 bit Output E Operation mode 13 1 bit Output F Operation mode 14 1 bit Output G Operation mode 15 1 bit Output H Operation mode with inverted activation/deactivation of staircase lighting function 8 1 bit Output A Invert operation mode 9 1 bit Output B Invert operation mode 10 1 bit Output C Invert operation mode 11 1 bit Output D Invert operation mode 12 1 bit Output E Invert operation mode 13 1 bit Output F Invert operation mode 14 1 bit Output G Invert operation mode 15 1 bit Output H Invert operation mode Page 6 of 8

, GH Q631 0047 R0111 Parameters The default setting for the values is printed in bold type. General: Inactive waiting time after bus 5 s / 10 s / 15 s /... / 60 s voltage recovery: At bus voltage recovery, during this time, no telegrams will be sent and incoming telegrams will not be executed Separate for each output (Output A is used here as an example): Switching mode normally opened contact normally closed contact Operation mode switch 5 switch with active status feedback 5 only if status response is selected: Invert status feedback yes no Send status feedback always only if value changes Logical connection no logical connection logical OR connection logical AND connection only if logical connection is assigned: Invert object no. 8 yes no Value of obj. no. 8 at bus read value via ABB i-bus EIB voltage recovery logic 0 logic 1 Value of obj. no. 0 at bus read value via ABB i-bus EIB voltage recovery logic 0 logic 1 Preferred position at bus voltage contact opened failure contact closed contact unchanged Preferred position at bus voltage contact opened recovery contact closed contact unchanged Preferred position after unchanged inactive waiting time depending on obj. no. 0 Page 7 of 8

, GH Q631 0047 R0111 Parameters The default setting for the values is printed in bold type. Output A - time Time function deactivated activated Note: If a logical function is chosen, no staircase lighting function is available. only if time function is activated: Type of time function staircase lighting switch ON/OFF delay only for staircase lighting function: 5 Time base 130 ms / 260 ms /... / 35 min / 1.2 h 5 Factor for duration of 5 staircase lighting (5...127) Staircase lighting function can yes be activated/deactivated by no object no. 8 only if yes is selected: Invert obj. no. 8 yes no Value of obj. no. 8 at bus read value via ABB i-bus EIB voltage recovery logic 0 logic 1 only for ON/OFF delay: Time base 130 ms / 260 ms /... / 35 min / 1.2 h Factor for switch ON delay 0 (0127) Factor for switch OFF delay 0 (0127) Page 8 of 8