Data Sheet EM3/../ODIN Three Phase Electricity Meters EM3/../ODIN Three Phase Electricity Meters Trend code Supplier's code EM3/230/D/ODIN OD4165 EM3/230/CT/ODIN OD4110 ACC/EM3/ODIN/PANELKIT 09 811 84 Document Attached: ABB ODIN Meter Technical Documentation EM3/../ODIN Three Phase Electricity Meter Data Sheet TA200706 Issue 1/A 14/7/03 1
EM3/CT/N Data Sheet TrendControl Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes. Trend Control Systems Ltd. P.O. Box 34 Horsham Sussex RH12 2YF England Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com 2 EM3/../ODIN Three Phase Electricity Meter Data Sheet TA200706 Issue 1/A 14/7/03
ODIN Meter An electricity energy meter from ABB Technical documentation
ODIN Meter Contents General description... 2 OD4165 direct connection, 3 phase meter up to and including 65 A... 3 OD4110 transformer connection, 3 phase meter... 4 Accessories... 5 Wiring diagrams... 6 Device dimensions... 7 Example of connections... 8
St375010 ODIN Meter General Description ODIN Meter is a compact electricity energy meter made for measuring active electrical energy and designed to be mounted on a DIN rail in distribution boards or in standard cabinets. During the development process creating SIMPLICITY was the number one priority. The ODIN Meter shall be perceived as easy to install, use and distribute. Examples of this can already be seen on the front of the electricity energy meter, clear marking, strong screws in the connecting terminal and an easy to read display. Enclosed in the carton are easy to understand instructions, which use text and diagrams to describe in detail how the installation should be carried out. The ODIN Meter is certified according to the international standard IEC 61036. The standard covers several technical requirements including climate, mechanics, electronics, EMC and accuracy. Furthermore the ODIN Meter has a national approval from Sweden s Test and Research Institute (SP) as a revenue meter. This guarantees the ODIN Meter is highly reliable, has a long life expectancy and maintains its measuring accuracy. ABB 3
St375010 ODIN Meter OD4165 direct connection, 3 phase meter up to and including 65 A Article number Type Voltage (V) Pulse output frequency 2CMA131024R1000 OD4165 230/400V 100 imp./kwh Technical Data Voltage: 3x230/400 V AC Voltage range -20% to +15% Max current 65 A Start current 25 ma Power consumption of current circuits < 3 VA/phase Frequency 50/60 Hz Accuracy of measurement Class 2 (±2%) Standard IEC 61036 Temperature range -25 to +55 o C Material of front cover Polycarbonate Material of back cover Polycarbonate/glass fibre Resistance to heat and fire Equivalent to IEC 695-2-1 Protection against penetration of dust and water IP 20 Connection area in the current connecting terminals 1 16 mm 2 Pulse output Connection area in the connecting terminal 0.5 2.5 mm 2 External pulse voltage 5 40 V DC Max. current 100 ma Pulse length 100 ms ±2.5 ms Pulse frequency 100 imp/kwh Standard IEC 62053-1 (S0) LED Pulse frequency Pulse length Display 100 imp/kwh 40 ms LCD with 7 digits without a decimal place, 6 mm Front view Direct connection Type description Wiring diagram OD4165 LED frequency St375004 Drestromzahler 5(65)A Kl.2 Electricity meter 5(65)A Cl.2 Load indicator Phase indicator Identification No. National approval symbol (SP) Pulse output frequency 4 ABB
St375010 ODIN Meter OD4110 connection via external current transformers, 3 phase meter Article number Type Voltage (V) Pulse output frequency 2CMA1310251000 OD4110 230/400V 1 imp./kwh Technical Data Voltage: 3x230/400 V AC Voltage range -20% to +15% Max. current 10 A Starting current 15 ma Power consumption of current circuits < 0.02 VA/phase Power consumption of voltage circuits < 2 VA/phase Frequency 50/60 Hz Accuracy of measurement Class 2 (±2 %) Standard IEC 61036 Temperature range -25 to +55 o C Programmable transformer ratios 5/5, 75/5, 100/5 150/5, 200/5, 250/5, 300/5, 400/5, 500/5, 600/5, 700/5 750/5, 800/5, 900/5 A/A Material of front cover Polycarbonate Material of back cover Polycarbonate/glass fibre Resistance to heat and fire Equivalent to IEC 695-2-1 Protection against penetration of dust and water IP 20 Connection area in the current connection terminal 1 16 mm 2 Connection area in the voltage connection terminal 0.5 6 mm 2 Pulse output Connection area in the connection terminal 0.5 2.5 mm 2 External pulse voltage 5 40 V DC Max. current 100 ma Pulse length 100 ms ±2.5 ms Pulse frequency 1 imp/kwh Standard IEC 62053-1 (S0) LED Pulse frequency Pulse length Display 1000 imp/kwh 40 ms LCD with 7 whole number digits Front view Connection via current transformer Type description Adjustable transformer ratio Wiring diagram LED frequency St375005 Load indicator Phase indicator Identification No. National approval symbol (SP) Pulse output frequency ABB 5
St375003 St375002 ODIN Meter Accessories Article number Type Use Picture No. 09 809 25 Protective sealable flap When sealing 09 811 84 Front mounting kit For panel mounting 2 09 809 50 Enclosure (6 modules) For wall mounting 3 Picture No. 2 Picture No. 3 160 92 180 175 St375001 45,5 80 106 161 Mt375003 Mt375001 6 ABB
St375009 St375008 St375006 ODIN Meter Wiring diagrams Wiring diagrams Direct connection Connection via current transformer L1 P1 P1 P2 L2 P1 S1 S2 L3 P1 N PE 2 5 8 11 1 4 7 St375007 + - 20 21 11 3 6 9 Pulse output ABB 7
ODIN Meter Device dimensions Device dimensions 4,7 6.6 5.7 7.1 57.4 8.75 O 5.3 O 7.4 17.5 44 85 45 O 4.4 24.8 20 63,4 105 5 5 Mt375002 8 ABB
ODIN Meter Examples of connections Connections with cables The electricity meter will function correctly with the neutral connected to either the upper or lower terminal Connections with cables and busbar ABB 9
ABB Automation Technology Products AB Cewe Box 1005 S-611 29 Nyköping, Sweden Phone Int +46 155-29 50 00 Fax Int +46 155-28 81 10