FX1N-2EYT-BD Output Expansion Board

Similar documents
FX1N-4EX-BD Input Expansion Board

FX2N-4AD-PT SPECIAL FUNCTION BLOCK

FX1N JAPANESE SPECIFICATION UNITS

FX-485PC-IF RS485 Interface Unit Hardware Manual

USER'S GUIDE FX-485ADP COMMUNICATION ADAPTER FX0N-485ADP COMMUNICATION ADAPTER

High Speed Remote I/O Module

FX2NC-ENET-ADP Ethernet adapter USER'S MANUAL

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

V E2B Snap-in I/O Module

USER S MANUAL. FX2N-32ASI-M AS-interface Master Block

The identified danger could cause physical and property damage.

Guidelines for the Safety of the User and Protection of the F940WGOT Series.

V E1B Snap-in I/O Module

Micro-OPLC Installation Guide

User safety and equipment protection guidelines

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

OPLC Installation Guide

Vision OPLC V TR6/V350-J-TR6

EX-RC1 Remote I/O Adapter

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

V E2B Snap-in I/O Module

IO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-DI8-RO4, IO-DI8-RO4-L I/O Expansion Modules 8 Inputs, 4 Outputs

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

Guidelines for the Safety of the User and Protection of the F94*GOT-*WD-E

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

V E1B Snap-in I/O Module

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

IO-DI16, IO-DI16-L I/O Expansion Modules

V E5B Snap-in I/O Module

V E62B Snap-in I/O Module

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs

Vision OPLC. V T38 Installation Guide. General Description

This guide provides basic information for Unitronics controller model V T2.

FX-1HC SPECIAL FUNCTION BLOCK USER'S GUIDE

EX-RC1 Remote I/O Adapter

Vision OPLC V TR20

INTRODUCTION FX2N-1HC SPECIAL FUNCTION BLOCK USER S GUIDE

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

USER S MANUAL. FX2N-32DP-IF Profibus-DP Interface Unit

EX-RC1 Remote I/O Adapter

General Description V TR34/V130-J-TR34 V TR34/V350-J-TR34 V430J-R34 V R34/V130-J-R34 V R34/V350-J-R34

1) Indicates that the identified danger WILL cause physical and property damage.

1) Indicates that the identified danger WILL cause physical and property damage.

HARDWARE MANUAL HCA1 SERIES PROGRAMMABLE CONTROLLERS

Failure to comply with appropriate safety guidelines can cause severe injury or property damage.

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Failure to comply with appropriate safety guidelines can cause severe injury or property damage.

OPERATION MANUAL FX-10P-E

DC I/O Conversion Module

FR-A8AR INSTRUCTION MANUAL

DC I/O Conversion Module FA-TB32XY

Specifications. 2.1 General Specifications. Operating ambient temperature 0 to 40 C Storage ambient temperature -20 to 60 C

HARDWARE MANUAL GRAPHIC FX-50DU-TK(S)-C UNITS

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

Screen 2.4" 3.5" Color Touch 4.3" Color Touch. RS232/485 Yes Yes Yes Yes Yes* USB device, mini-b Com Ports, separate order, user-installed

Conductive Level Controller

Component identification

UniStream HMI Panel. CPU-for-Panel

V TU24 V350-J-TU24

Vision OPLC V TR20

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

Manual name Manual No. Description. When installed to a PLC 2 (0.07) (1.57) (0.35) (1.03) (0.86) 28 (1.1) (0.55) 2.6(0.1) (1.25) 8 (0.31) 8 (0.

USER S MANUAL. FX2N-5A Special function block

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HARDWARE MANUAL HCA2 SERIES PROGRAMMABLE CONTROLLERS

This guide provides basic information for Unitronics controllers V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Vision OPLC V TR20/V350-J-TR20

HARDWARE MANUAL FX1N SERIES PROGRAMMABLE CONTROLLERS

UniStream. Built-in. Installation Guide: US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24

UniStream CPU-for-Panel

Installation Guide V1210-T20BJ This guide provides basic information for Unitronics controllers V1210-T20BJ.

Screen 2.4" 3.5" Color Touch 4.3" Color Touch. RS232/485 Yes Yes Yes* Yes* Yes* USB device, mini-b Com Ports, separate order, user-installed

Operating instructions. Speed monitor D / / 2014

FX3U-1PG USER'S MANUAL

MILLENIUM MASI INSTALLATION MANUAL NTR 748 / E. Simple Automation Control Module (MAS)

Operating instructions. Switching amplifier DN0210 DN / / 2015

USER S MANUAL FX-10DM-E DISPLAY MODULE

ERNT-AQTD61 ERNT-AQTD61 ERNT-AQTD61. User s Manual. Mitsubishi General-Purpose Programmable Controller Renewal Tool Conversion Adapter.

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

VS-P Series. TDK-Lambda INSTRUCTION MANUAL

IO-LC1, IO-LC3 I/O Expansion Modules 1-3 Loadcell Inputs, 1 Digital In, 2 Out

PROGRAMMABLE CONTROLLERS

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Vision OPLC. General Description. Installation Guide V T34.

This manual classifies the safety precautions into two categories: and.

Programmable Controller Analog Terminal Block Conversion Module FA1-TBS40ADGN, FA1-TBS40ADDG, FA1-TBS40DAG User's Manual

MELSEC iq-f FX5 User's Manual (Analog Control)

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Transcription:

FX1N-2EYT-BD Output Expansion Board USER S MANUAL JY992D95201C This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and operation of the FX 1N-2EYT-BD Output Expansion Board and should be read and understood before attempting to install or use the unit. Further information can be found in the associated manuals list below. Specifications are subject to change without notice Guidelines for the Safety of the User and Protection of the FX1N-2EYT-BD. This manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows: a) Any engineer using the product associated with this manual, should be of a competent nature, trained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment. b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards. c) All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices. Note: The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual. Note s on the Symbols Used in this Manual At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment. 1) Indicates that the identified danger WILL cause physical and property damage. 2) Indicates that the identified danger could POSSIBLY cause physical and property damage. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application. Associated manuals Manual name Manual No. Description FX 1S Series Hardware Manual FX 1N Series Hardware Manual FX Programming Manual II JY992D83901 JY992D89301 JY992D88101 Describes contents related to hardware of FX1S Series PLC such as specifications, wiring and installation. Describes contents related to hardware of FX1N Series PLC such as specifications, wiring and installation. Describes instructions in FX1S/FX1N/FX2N/FX2NC Series.

1. Introduction The FX 1N -2EYT-BD output expansion board (hereafter referred to as "FX 1N -2EYT-BD" or "Function expansion board") is a function expansion board to be installed in the FX1S or FX 1N series programmable controller (hereafter referred to as "PLC"), to increase the output of two points. 1.1 Features of the FX1N-2EYT-BD 1) Additional increase of two output points. 2) Internal mounting in the top of the PLC meaning no need for change to the installation area of the PLC. 3) Additional outputs have special auxiliary relays associated to each point, which are turned ON or OFF depending on the required output state of the FX1N-2EYT-BD. As special auxiliary relays are used in the PLC program for the output points, the additional outputs are not included in the regular system I/O count. 1.2 Dimensions and Each Part Name * ; * ; * ; * ; 1.3 System configuration Dimensions: mm (inches) Accessories : Top cover for board 1 M3 screw to mount board 2 M3 screw to fix top cover 1 1) Output terminal. : Unused (Do not wire). BY0+ : + side terminal of output BY0 BY0- : - side terminal of output BY0 BY1+ : + side terminal of output BY1 BY1- : - side terminal of output BY1 The top face of this connector is higher than the top face of the PLC panel cover by approximately 7 mm. 2) Mounting hole (2-φ3.5(0.14")) 3) Output LED BY0 LED : The LED lights when BY0 is turn on. BY1 LED : The LED lights when BY1 is turn on. 4) port for display module FX 1N-5DM or memory cassette FX 1N-EEPROM-8L 5) connector for PLC Only one function expansion board can be used on one FX1S and FX1N series PLC main unit. Do not try to install two or more expansion boards. FX 1N-2EYT-BD can be used together with FX1N-5DM. Refer to the FX1S or FX1N HARDWARE MANUAL when using the FX 1N-2EYT-BD together with an FX1N-5DM. When using with the memory cassette FX1N-EEPROM-8L, only program transfer is possible. (The memory cassette cannot be connected permanently) 1.4 Applicable PLC "! $ '! # "! & # # Series name FX1S FX1N Applicable version V2.0 or later V2.0 or later

2. Installation 1) Do not use the function expansion board in environments that contain excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration. Use in these environment may cause electric shock, fire, malfunction, damage or deterioration of the product. 2) Cut off all phases of power source before installing / removing or performing wiring work on the unit in order to avoid electric shock or damage of product. 3) After the installation wiring etc. replace the PLCs top cover before power ON. 4) Securely install the function expansion board, and fix it to the PLC. Defective contact can cause malfunction. 2.1 Mounting Turn off all power to the PLC before installing the FX 1N-2EYT-BD. a) Top cover for FX 1N-2EYT-BD (supplied as an accessory)) b) M3 screw to fix top cover (supplied as an accessory) c) M3 screw to fix FX 1N-2EYT-BD (2 pieces) (supplied as accessories) d) port for optional equipment e) FX 1N -2EYT-BD (function expansion board) Note: Do not remove this screw on the PLC(FX1S). 1) Remove the top cover of the main unit and keep. 2) Plug FX 1N-2EYT-BD e) in to the external port d). 3) Fix the function expansion board to the main unit with two M3 screws c). (Tightening torque: 0.3 to 0.6 N m) 4) Attach the top cover for FX 1N-2EYT-BD a) in place of the original cover. During attachment, remove a) with a suitable tool, so that the output terminals are exposed. 5) Fix the top cover with an M3 screw b). (Tightening torque: 0.3 to 0.6 N m)

3. Output Wiring Wiring cautions Observe the following cautions to avoid electrical shock, short-circuit, disconnection or damage in the unit. Do not lay signal cable near to high voltage power cable or house them in the same trunking duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of more than 100 mm (4") from these power cables. Where output signal lines are used over an extended distance consideration for voltage drop and noise interference should be made. Twist the end of each stranded cable so that barbed wires are not present. Never solder the end of any cables. Never connect cables of a non permitted size. Make sure that the number of connected cables is not more than the unit has been designed for. Fix cables so that any stress is not directly applied on the terminal block or the cable connection area. Tighten the terminals to a torque of 0.5 to 0.6 N m. Do not tighten terminal screws exceeding the specified torque. Failure to do so may cause equipment failures or malfunctions. Use an interlock circuit for external circuit protection. Do not wire [ ] terminal. 3.1 Applicable cables Use AWG26-16 for the connection with output equipment. Tighten the terminals to a torque of 0.5 to 0.6N m. Do not tighten terminal screws exceeding the specified torque. Failure to do so may cause equipment failures or malfunctions. When using a different type of cable, defective contact of the terminal part is possible. Use a crimp terminal to achieve a good contact. Linear and sectional area Linear Sectional area (mm 2 ) Terminal AWG26 0.1288 AWG16 1.309 Stranded cable: Remove sheath, twist core wires, then connect cable. Single cable: Remove sheath, then connect cable. Terminal processing of wire 6mm(0.2inches) 3.2 Wiring of output Sink Type FX1N-2EYT-BD BY0+ + BY0- BY1+ BY1- Source type FX1N-2EYT-BD BY0+ BY0- + BY1+ BY1-

4. Device allocation and program example Do not turn the special auxiliary relays either side of M8116 and M8117 ON and OFF carelessly. This may cause malfunction. 4.1 Device allocation Each output of FX1N-2EYT-BD is allocated a special auxiliary relay. The ON/OFF state of each output is reflected in its corresponding special auxiliary relay. BY0 output of FX1N-2EYT-BD : M8116 BY1 output of FX1N-2EYT-BD : M8117 4.2 Program example X000 M0 M8116 M8117 Turn the special auxiliary relay allocated to each output ON and OFF by program of PLC. When the END instruction of the program is executed, the output process is completed. The interruption output processing of HSCS (high-speed counter comparison set), and HSCR (high-speed counter comparison reset), etc. are not carried out. Output refreshing by REF instruction can not be done. Do not use the special auxiliary relay for an instruction by which the bit device is of three points or more such as comparison result of the CMP instruction and comparison result of the ZCP instruction is occupied. Do not use the special auxiliary relays for the operand of each application instruction as data. (K1M8116 and K2M8116, etc.) 5. Specifications Do not touch the terminal while power is ON. Electric shock is possible. Cleaning and additional tightening of the terminal should only be done after turning OFF the power supply. Electric shock is possible while the power is ON. For repair please contact a service representative. Incorrect repair can cause malfunction or electric shock Install or uninstall FX1N-2EYT-BD after turning OFF the power supply. Installing and uninstalling while the power supply ON may cause malfunction. Treat as industrial waste when disposing of the product. 5.1 Environmental specifications The environmental specifications are equivalent to those of the PLC main unit. (Refer to the manual of the PLC main unit.) 5.2 Power supply specifications Item Consumption current 5.3 Output specifications 5V DC Supply by PLC. Specification Item power supply Circuit insulation Operation display The maximum resistance The maximum, inductive Open road leakage current Response time OFF to ON Response time ON to OFF Specification Photo coupler LED lighting when photo coupler is driven 0.5A/1 point 12W/24V DC 0.1mA/DC30V 0.2ms or less 0.2ms or less

Attention This product is designed for use in industrial applications. Note Authorized Representative in the European Community: Mitsubishi Electric Europe B.V. Gothaer Str. 8, 40880 Ratingen, Germany Manual number : JY992D95201 Manual revision: C Date : April 2015 HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

FX1N-2EYT-BD Output Expansion Board USER S MANUAL JY992D95201C This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and operation of the FX 1N-2EYT-BD Output Expansion Board and should be read and understood before attempting to install or use the unit. Further information can be found in the associated manuals list below. Specifications are subject to change without notice Guidelines for the Safety of the User and Protection of the FX1N-2EYT-BD. This manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows: a) Any engineer using the product associated with this manual, should be of a competent nature, trained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment. b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards. c) All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices. Note: The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual. Note s on the Symbols Used in this Manual At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment. 1) Indicates that the identified danger WILL cause physical and property damage. 2) Indicates that the identified danger could POSSIBLY cause physical and property damage. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application. 1. Introduction The FX 1N -2EYT-BD output expansion board (hereafter referred to as "FX 1N -2EYT-BD" or "Function expansion board") is a function expansion board to be installed in the FX1S or FX 1N series programmable controller (hereafter referred to as "PLC"), to increase the output of two points. 1.1 Features of the FX1N-2EYT-BD 1) Additional increase of two output points. 2) Internal mounting in the top of the PLC meaning no need for change to the installation area of the PLC. 3) Additional outputs have special auxiliary relays associated to each point, which are turned ON or OFF depending on the required output state of the FX1N-2EYT-BD. As special auxiliary relays are used in the PLC program for the output points, the additional outputs are not included in the regular system I/O count. 1.2 Dimensions and Each Part Name * ; * ; * ; * ; "! $ '! 1.3 System configuration Dimensions: mm (inches) Accessories : Top cover for board 1 M3 screw to mount board 2 M3 screw to fix top cover 1 1) Output terminal. : Unused (Do not wire). BY0+ : + side terminal of output BY0 BY0- : - side terminal of output BY0 BY1+ : + side terminal of output BY1 BY1- : - side terminal of output BY1 The top face of this connector is higher than the top face of the PLC panel cover by approximately 7 mm. 2) Mounting hole (2-φ3.5(0.14")) 3) Output LED BY0 LED : The LED lights when BY0 is turn on. BY1 LED : The LED lights when BY1 is turn on. 4) port for display module FX 1N-5DM or memory cassette FX 1N-EEPROM-8L 5) connector for PLC Only one function expansion board can be used on one FX1S and FX1N series PLC main unit. Do not try to install two or more expansion boards. FX 1N-2EYT-BD can be used together with FX1N-5DM. Refer to the FX1S or FX1N HARDWARE MANUAL when using the FX 1N-2EYT-BD together with an FX1N-5DM. When using with the memory cassette FX1N-EEPROM-8L, only program transfer is possible. (The memory cassette cannot be connected permanently) 1.4 Applicable PLC Series name FX1S FX1N # "! & # # Applicable version V2.0 or later V2.0 or later 2. Installation 1) Do not use the function expansion board in environments that contain excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration. Use in these environment may cause electric shock, fire, malfunction, damage or deterioration of the product. 2) Cut off all phases of power source before installing / removing or performing wiring work on the unit in order to avoid electric shock or damage of product. 3) After the installation wiring etc. replace the PLCs top cover before power ON. 4) Securely install the function expansion board, and fix it to the PLC. Defective contact can cause malfunction. 2.1 Mounting Turn off all power to the PLC before installing the FX 1N-2EYT-BD. a) Top cover for FX 1N-2EYT-BD (supplied as an accessory)) b) M3 screw to fix top cover (supplied as an accessory) c) M3 screw to fix FX 1N-2EYT-BD (2 pieces) (supplied as accessories) d) port for optional equipment e) FX 1N -2EYT-BD (function expansion board) Note: Do not remove this screw on the PLC(FX1S). 1) Remove the top cover of the main unit and keep. 2) Plug FX 1N-2EYT-BD e) in to the external port d). 3) Fix the function expansion board to the main unit with two M3 screws c). (Tightening torque: 0.3 to 0.6 N m) 4) Attach the top cover for FX 1N-2EYT-BD a) in place of the original cover. During attachment, remove a) with a suitable tool, so that the output terminals are exposed. 5) Fix the top cover with an M3 screw b). (Tightening torque: 0.3 to 0.6 N m) Associated manuals Manual name Manual No. Description FX 1S Series Hardware Manual FX 1N Series Hardware Manual FX Programming Manual II JY992D83901 JY992D89301 JY992D88101 Describes contents related to hardware of FX1S Series PLC such as specifications, wiring and installation. Describes contents related to hardware of FX1N Series PLC such as specifications, wiring and installation. Describes instructions in FX1S/FX1N/FX2N/FX2NC Series.

3. Output Wiring Wiring cautions Observe the following cautions to avoid electrical shock, short-circuit, disconnection or damage in the unit. Do not lay signal cable near to high voltage power cable or house them in the same trunking duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of more than 100 mm (4") from these power cables. Where output signal lines are used over an extended distance consideration for voltage drop and noise interference should be made. Twist the end of each stranded cable so that barbed wires are not present. Never solder the end of any cables. Never connect cables of a non permitted size. Make sure that the number of connected cables is not more than the unit has been designed for. Fix cables so that any stress is not directly applied on the terminal block or the cable connection area. Tighten the terminals to a torque of 0.5 to 0.6 N m. Do not tighten terminal screws exceeding the specified torque. Failure to do so may cause equipment failures or malfunctions. Use an interlock circuit for external circuit protection. Do not wire [ ] terminal. 3.1 Applicable cables Use AWG26-16 for the connection with output equipment. Tighten the terminals to a torque of 0.5 to 0.6N m. Do not tighten terminal screws exceeding the specified torque. Failure to do so may cause equipment failures or malfunctions. When using a different type of cable, defective contact of the terminal part is possible. Use a crimp terminal to achieve a good contact. Linear and sectional area Linear Sectional area (mm 2 ) Terminal AWG26 AWG16 0.1288 1.309 Stranded cable: Remove sheath, twist core wires, then connect cable. Single cable: Remove sheath, then connect cable. 6mm(0.2inches) 3.2 Wiring of output Sink Type Source type Terminal processing of wire FX1N-2EYT-BD FX1N-2EYT-BD BY0+ BY1+ BY0+ BY1+ BY0- BY1- BY0- BY1- + + 4. Device allocation and program example Do not turn the special auxiliary relays either side of M8116 and M8117 ON and OFF carelessly. This may cause malfunction. 4.1 Device allocation Each output of FX1N-2EYT-BD is allocated a special auxiliary relay. The ON/OFF state of each output is reflected in its corresponding special auxiliary relay. BY0 output of FX1N-2EYT-BD : M8116 BY1 output of FX1N-2EYT-BD : M8117 4.2 Program example X000 M0 Turn the special auxiliary relay allocated to each output ON and OFF by program of PLC. When the END instruction of the program is executed, the output process is completed. The interruption output processing of HSCS (high-speed counter comparison set), and HSCR (high-speed counter comparison reset), etc. are not carried out. Output refreshing by REF instruction can not be done. Do not use the special auxiliary relay for an instruction by which the bit device is of three points or more such as comparison result of the CMP instruction and comparison result of the ZCP instruction is occupied. Do not use the special auxiliary relays for the operand of each application instruction as data. (K1M8116 and K2M8116, etc.) 5. Specifications Do not touch the terminal while power is ON. Electric shock is possible. Cleaning and additional tightening of the terminal should only be done after turning OFF the power supply. Electric shock is possible while the power is ON. For repair please contact a service representative. Incorrect repair can cause malfunction or electric shock Install or uninstall FX1N-2EYT-BD after turning OFF the power supply. Installing and uninstalling while the power supply ON may cause malfunction. Treat as industrial waste when disposing of the product. 5.1 Environmental specifications The environmental specifications are equivalent to those of the PLC main unit. (Refer to the manual of the PLC main unit.) 5.2 Power supply specifications Item Consumption current M8116 M8117 5.3 Output specifications Item power supply Circuit insulation Operation display The maximum resistance The maximum, inductive Open road leakage current Response time OFF to ON Response time ON to OFF 5V DC Supply by PLC. Specification Specification Photo coupler LED lighting when photo coupler is driven 0.5A/1 point 12W/24V DC 0.1mA/DC30V 0.2ms or less 0.2ms or less Attention This product is designed for use in industrial applications. Note Authorized Representative in the European Community: Mitsubishi Electric Europe B.V. Gothaer Str. 8, 40880 Ratingen, Germany Manual number : JY992D95201 Manual revision: C Date : April 2015 HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN