FIELDBUS TECHNOLOGY ETHERNET- PROFIBUS- INTERFACE PB-XEPI F1144/ 03 INSTALLATION MANUAL

Similar documents
Installation Manual TH LINK PROFINET. Version: EN Copyright 2014 Softing Industrial Automation GmbH

Serial PROFIBUS Interface

Programmable Set for Ethenet/IP in IP67 TI-BL67-PG-EIP-2

Profibus-DPV1 Set in IP67 TI-BL67-DPV1-6

Programmable Set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

BL67 electronic module 8 configurable digital channels, PNP, channel diagnostics, 0.5 A BL67-8XSG-PD

BL67 electronic module 4 analog inputs for current/voltage BL67-4AI-V/I

CODESYS 3 Programmable Gateway for the BL67 I/O System Multiprotocol Ethernet gateway for PROFINET, EtherNet/IP and Modbus TCP BL67-PG-EN-V3

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

Programmable Set for Simple I/O Communication via PROFIBUS-DP in IP67 TI-BL67-PG-DP-S-8

Profibus-DPV1 Set in IP20 TI-BL20-DPV1-2

CAN-Bridge. CAN Communications Module for CAN 2.0 A/B, CAN Layer AA01. Manual. Version 1/ from HW 1 & FW 1.00

Technical Information Fieldgate SFG500

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

CODESYS 3 Programmable Gateway for the BL20 I/O System Multiprotocol Ethernet Gateway for PROFINET, EtherNet/IP and Modbus TCP BL20-PG-EN-V3

Profinet Set in IP20 TI-BL20-E-PN-4

1 Safety instructions. 2 Device components. 3 Function. Smart Control IP. Art. No. SC 1000 IP. Operating instructions

Anybus Communicator STARTUP GUIDE. IIoT. SP en-us ENGLISH

BL compact Multiprotocol Station for Industrial Ethernet 16 Digital PNP Inputs BLCEN-16M8LT-8DI-P-8DI-P

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Kit for Simple I/O Communication via Ethernet Modbus/TCP/ EtherNet/IP / PROFINET in IP67 TI-BL67-EN-S-8

Industrial Serial Device Server

Operating and mounting instructions

Type ME43. Quickstart

DF PROFI II PCIe. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II PCIe KUNBUS

User manual BLCDN-8M12LT-8XSG-PD-8XSGPD

User Manual BLCDP-2M12MT-2RFID-S

User Manual Revision English

CU USB-Extender-Rx (USB and DVI Extender) Version: 0.3 Date:

Expansion Module for I/O Communication BL Ident RFID Module for Connecting 2 Read/Write Heads (HF/UHF) BL20-2RFID-S

Programmable Set for PROFIBUS-DP in IP67 TI-BL67-PG-DP-8

CPU module for zone 2 Series 9442/35

E600 VX01 Installation guide

Operating Manual FPGA-based High-Speed Micro-PLC

BL compact Fieldbus Station for DeviceNet 4 Analog Current Outputs BLCDN-4M12LT-2AO-I-2AO-I

Your Global Automation Partner. Teachable Capacitive Sensors. Operating Instructions

Programmable Set for Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-2

Quick Startup Guide. datafeed uagate SI. Version: EN Copyright 2016 Softing Industrial Automation GmbH

Power Xpert Meter 2000 Gateway Card Kit

Power Xpert Meter 2000 Gateway Card Kit

DF PROFI II CPCI. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II CPCI KUNBUS

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Installation- and Operating instructions for CU Ethernet Controller with USB Input. Version: 1.4 Date:

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

CU Compact-Flash card adapter for USB. Version: 1.0 Date:

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client

Siemens Spares. Preface 1. Scope of Delivery 2 SIPLUS CMS4000. Product Characteristics 3 ION PROFIBUS DP SPY T001 Installation and Maintenance 4

Your Global Automation Partner. excom I/O System

GREENBOX EV. User Guide. Revision 1.3

Quick Start Guide NETL ink Ethernet Gateways

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

PAS 300, PROFIBUS Slave Interface Module

CPCI-PS24 24V-Power Supply

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

Date Revision Change(s) 29/07/ First version

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Your Global Automation Partner. IO-Link Devices Commissioning. User Manual

USER MANUAL. Longo programmable controller LPC-2.MC8 Main module. Version 10

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

RMx621. Appendix to the operating manual

BL compact Multiprotocol Station for Industrial Ethernet 8 Analog Current or Voltage Inputs BLCEN-8M12LT-4AI-VI-4AI-VI

TRIO-DIODE/12-24DC/2X10/1X20

CommDTM ET 200M. User Manual. Doc. Version 4.0. English

Documentation. KM10xx. Terminal Modules with Digital Inputs. Version: Date:

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

RMx621 /FML621. Appendix to the operating manual

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Dynamic-UserCenter 32

Access Terminal IF-800

User Manual Anybus Serial Server

MGate 5111 Quick Installation Guide

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

1. CP430, CP470, CP474, CP770 and CP774

User manual Quick start TSwin.net

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation.

Your Global Automation Partner. Startup. Getting Started Guide

Compact Multiprotocol I/O Module for Ethernet 8 IO-Link Master Channels 4 Universal Digital PNP Channels, 2 A, Channel Diagnostics TBEN-L5-8IOL

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

MGate 5105-MB-EIP Quick Installation Guide

FL MC 2000E (SM40) LC

modunet292: novanet-ethernet interface

DF PROFI II PC/104-Plus

Power Xpert Meter 2000 Gateway Card Kit

IP 69K M12 I/O ports LEDs indicating status and diagnostics

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

Manual Fiber Optic Interfaces

Technical Description

FG-260. Quick Startup Guide. Gateway between EtherNet/IP and PROFINET with PROFINET Controller functionality. Version: MMA-CA EN

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

SGE-3G/GPRS INSTRUCTION MANUAL (M179B A)

PI-EX-ME-2NAM/COC-24VDC

Sauter Systems

SK CU4-PBR-C Part number:

Date Revision Change(s) First version

COMELIT AUDIO PLAYER ART

IO1000. Type designation. Product description I/O module INSTALLATION MANUAL. Catalog no. from software version Document no I/O module 1.

Programmable Set for Simple I/O Communication via Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-S-6

User Manual Gateway component for EtherNet/IP

BL compact Multiprotocol Station for Industrial Ethernet 2 Analog Pt and Ni Sensor Inputs BLCEN-2M12MT-2AI-PT

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Transcription:

FIELDBUS TECHNOLOGY ETHERNET- PROFIBUS- INTERFACE PB-XEPI INSTALLATION MANUAL F1144/ 03

2 Installation PB-XEPI D301144 0509

Content About this "Installation manual"...5 Intended use...5 Explanation of the safety instructions...5 Menu and keyboard commands...5 For your safety...6 Performance and functioning...8 PB-XEPI features...8 Scope of delivery...8 PB-XEPI Configuration requirements...8 Ethernet network presettings...8 Design of the device...9 Connections and indicating elements...10 Mounting...10 Start-up guideline...11 Note regarding the application software...11 Assembling and disassembling the device...12 Assembling the device...12 Disassembling the device...12 Connecting the Ethernet...12 Connecting the power supply...13 Configuring the device in the Ethernet network...14 Connection in a network with DHCP (Dynamic Host Configuration Protocol)...14 Connection in a network with manual IP assignment...15 Determining the network addresses...16 Setting the new IP and network addresses...16 Checking the Ethernet connection to the device...17 Connecting the PROFIBUS...18 Bus terminating resistors...19 D301144 0509 Installation PB-XEPI 3

Content PB-XEPI operation modes PROFIBUS Diagnosis...20 PROFIBUS network access...21 Troubleshooting...22 Technical data...23 4 Installation PB-XEPI D301144 0509

About this "Installation manual" About this "Installation manual" Please read this manual carefully, prior to installation. It facilitates assembly and setup of your system and provides you with important information. Intended use The device is designed to be used as an interface between PROFIBUS and Ethernet networks. Any other use is deemed non-intended use. Explanation of the safety instructions The following symbols and signal words used are intended to draw your attention to special situations: Danger Warning of personal injury from voltage. Warning Warning of damage to device. Note Useful tips. Disposal Notes on disposal. Menu and keyboard commands The following conventions apply to menu and keyboard commands: Courier font <Key> Window names, menu items, fields and descriptions of combo boxes, check boxes, radio buttons and icons. Press the indicated key. D301144 0509 Installation PB-XEPI 5

For your safety For your safety Strictly observe the following safety instructions before connecting the device: Warning Never open the case of the device or carry out any mechanical modifications on the device. Otherwise, this may lead to damages on the device as well as to loss of warranty. Warning The device contains electronic components sensitive to electrostatic discharges. Damages due to electrostatic discharge can lead to premature failure of components or intermittent faults at a later stage. Before installing the device, divert the electrostatic discharge away from your body and the tools used. Warning Small objects or liquids must not enter the case of the device (e.g. through the ventilation slots). This may damage the device. Never cover the ventilation slots on the device. Carefully plan the integration of the device into an existing system and ensure a proper function of the system after installation. The device may only be assembled or disassembled by qualified, trained electrical engineering personnel. When installing the device, observe the regulations for handling electric components in accordance with VDE 0100. In addition, you must also observe the valid safety and accident prevention regulations (UVV) when operating the device within the jurisdiction of the Federal Republic of Germany. Observe the EN 61158 PROFIBUS norm. Always install the device on a suitable DIN-rail (mounting rail). Cables used for the connection must not apply any mechanical forces to the device. High temperature differences between the storage site and installation site can result in condensation within the case, which may cause the device to become damaged. In case of high temperature differences, please wait at least three hours before operating the device. Lock the connected plug (PROFIBUS) using the screw connections intended for this purpose. 6 Installation PB-XEPI D301144 0509

For your safety Disposal The device must be disposed of separately from normal household waste in accordance with the 2002/96/EC (WEEE) Directive. D301144 0509 Installation PB-XEPI 7

Performance and functioning Performance and functioning The Ethernet-PROFIBUS-Interface (PB-XEPI) as a compact gateway enables an easy connection of PROFIBUS networks to the Ethernet. PB-XEPI features Supports 2 operation modes: integrated PROFIBUS diagnosis of the entire PROFIBUS network with alert via email and PROFIBUS network access for other applications like PROFIBUS Scope from Trebing & Himstedt, TH OPC Server DP from Trebing & Himstedt, FDT frame application with CommDTM PROFIBUS DP-V1 from Trebing & Himstedt or Emerson s AMS Suite Supports leading technologies such as FDT, EDD (Emerson s AMS Suite), OPC Supports central field device configuration, calibration and diagnosis, e.g. via configuration tools such as FieldCare of Endress + Hauser, FieldMate from Yokogawa, PACTware or Emerson s AMS Suite Independent of process control system or PLC manufacturers Supports condition monitoring Support smart-devices asset management Scope of delivery Ethenet-PROFIBUS-Interface PB-XEPI Documentation PB-XEPI Configuration requirements (not included in the scope of delivery) PC or notebook with Windows 2000, XP or Server 2003 (operating system dependent on the application software used) Web browser (MS Internet Explorer 6 or 7) for configuration of Ethernet and PROFIBUS diagnosis Application software for PROFIBUS configuration Enabling the ports 80 and 2364 Ethernet network presettings The device is preset to Ethernet network operation with a DHCP server. No Ethernet configuration settings are required in this operating mode. In case of manual allocation of IP addresses the device has the following standard IP: configuration: IP address 169.254.0.1 Subnet mask 255.255.0.0 Standard gateway 0.0.0.0 8 Installation PB-XEPI D301144 0509

Design of the device Design of the device (see Fig. 1) 1 Ethernet interface 5 PROFIBUS interface 2 LED ETH 6 Terminal strip for power supply 3 LED RUN 7 Type label 4 LED PB 8 DIN-rail (not included in the scope of delivery) [1] [2] [3] [4] ETH RUN PB [8] PB-XEPI [5] [6] A B C D [7] PB-XEPI Ident No.: 6905313 HW-Release: 2.0 Serial No.: Temperature: 0...+50 C Current: max. 190 ma Power Supply: 19,2...28,8 VDC + 24 VDC ETH: RUN: PB: Ethernet (GN/RD) OK (GN) Error (RD) PROFIBUS (GN/RD) Made in Germany D-Mülheim/Ruhr Fig. 1: PB-XEPI (front and side view) D301144 0509 Installation PB-XEPI 9

Connections and indicating elements Connections and indicating elements [1] Ethernet interface: RJ45 (10Base-T/100Base-TX) LED lights yellow: Ethernet data communication LED lights green: physical connection available [2] LED ETH ETH lights red: first start phase ETH flashes red: boot procedure ETH lights red or flashes red or green in case of an error: internal failure of the firmware. ETH lights green: connection to application via Ethernet [3] LED RUN RUN lights red: internal failure identified RUN lights green: 24 V power supply is fed [4] LED PB PB lights or flashes green: device communicates via PROFIBUS [5] PROFIBUS interface: D-Sub socket [6] Terminal strip for +24 VDC power supply A: 24 V (+) B: 0 V (-) C: not assigned D: Earth conductor Mounting 35 mm DIN rail [8] (not included in the scope of delivery) 10 Installation PB-XEPI D301144 0509

Start-up guideline Start-up guideline The following steps are required for start-up: 1. Mount the device (see»assembling the device«on page 12). 2. Connect to the Ethernet (see»connecting the Ethernet«on page 12). 3. Connect to the power supply (see»connecting the power supply«on page 13) 4. Configure the Ethernet (see»configuring the device in the Ethernet network«on page 14). Note To set the IP address manually you must connect your computer to the device via a patch cable. 5. Connect the PROFIBUS (see»connecting the PROFIBUS«on page 18). 6. If you use the PB-XEPI in the PROFIBUS network access operation mode you have to configure PROFIBUS parameters of the device using an application software (not included in the scope of delivery). Note regarding the application software An application software with the appropriate drivers is required for operating the device. The COM-DTM for usage of the PB-XEPI in FDT frame applications is on the CD. D301144 0509 Installation PB-XEPI 11

Assembling and disassembling the device Assembling and disassembling the device Warning Warning of damage to device. Above and below the device, a minimum of 5 cm head space for heat dissipation needs to be available. [1] [2] [3] [4] Fig. 2: Assembly and disassembly of the device 1 Device with notch on DIN rail 2 DIN rail 3 Device on DIN rail 4 Stop lever Assembling the device 1. Place the notch of the device on the DIN rail and move the device downward until the stop lever locks into place on the DIN rail. Disassembling the device 1. Disassemble the connected supply and signal lines (Ethernet, PROFIBUS, voltage). 2. Place the screwdriver into the stop lever on the device (see Fig. 2, [3]). 3. Press the screwdriver in the direction of the device and simultaneously swing the device off the DIN rail. Connecting the Ethernet 1. Insert the patch cable plug (RJ45, not included in the scope of delivery) into the Ethernet socket on the device until the plug locks into place. 2. The green LED on the Ethernet socket lights as soon as the device is energized and an Ethernet network is available. 12 Installation PB-XEPI D301144 0509

Connecting the power supply Connecting the power supply Danger Electrical voltage. Only a qualified electrician is allowed to work on the device's electrical equipment. Incorrect device earthing can cause injury to personnel or device damage. Ensure correct and proper earthing of the device. Warning Reverse polarity in the power supply can damage the device. Make sure the power supply is connected with correct polarity. +24 V 0 V not assigned Earth conductor Fig. 3: Terminal strip for power supply on the device 1. Connect the cable of a 24 V power supply and the earth conductor (earth terminal) to the terminal strip on the device. The terminal strip can be plugged and lifted out using a screwdriver for installation. 2. Switch on the power supply. The LED RUN flashes green until the device's initiation procedure is completed. Afterwards the LED RUN lights green. D301144 0509 Installation PB-XEPI 13

Configuring the device in the Ethernet network Configuring the device in the Ethernet network There are two connecting options to choose from, depending on your Ethernet network: Ethernet network with DHCP server automatic and dynamic allocation of IP addresses (connection with patch cable via hub or switch) Ethernet network (Peer-to-Peer) manual allocation of IP addresses (connection via patch cable) Connection in a network with DHCP (Dynamic Host Configuration Protocol) The device is preset to Ethernet network operation with a DHCP server and in this case it is automatically assigned an IP address. This operation mode does not require configuration settings. Note If you connect the Ethernet with the power supply already connected, the DHCP may fail to be identified. The routine for the DHCP identification only runs during device start-up. Briefly switch off the power supply for a new DHCP identification. 14 Installation PB-XEPI D301144 0509

Connection in a network with manual IP assignment Connection in a network with manual IP assignment If you use the device in an Ethernet network without DHCP server, you need the following for configuration: TCP/IP settings for this network. A PC/notebook with a web browser. A patch cable between PC/notebook and device (peer-to-peer connection). Note The computer must be in the same network as the device. Note Always notify your system administrator prior to allocating IP addresses. If you set an address already assigned, other devices in the network may be deactivated and communication may be affected. The device has the following manual default IP addresses (default settings at the time of delivery): IP address 169.254.0.1 Subnet Mask 255.255.0.0 Standard gateway 0.0.0.0 D301144 0509 Installation PB-XEPI 15

Determining the network addresses Determining the network addresses Ask your system administrator for the IP addresses or do the following: 1. Connect your PC/notebook to the Ethernet network into which the device is to be integrated. 2. Start the MS-DOS prompt. 3. Enter ipconfig -all. All settings for your network are displayed. Note down the settings for subnet mask and standard gateway. Setting the new IP and network addresses 1. Connect a patch cable to the device. 2. Connect a PC/notebook to the patch cable. 3. Start a Web browser on your PC/notebook (MS Internet Explorer 6 or 7). 4. Enter the IP address http://169.254.0.1 and press <Enter>. The PB-XEPI web site loads. A pop-up window opens. Please read the information carefully and close the window after that. 5. Then click the Settings tab. Information on the device is displayed in the web browser. Fig. 4: Setting the IP and network addresses 16 Installation PB-XEPI D301144 0509

Determining the network addresses 6. Select as user Admin to login as an administrator. The default password is the sixfigure serial number of the device. We recommend to change the password after login. Click on Change and enter the new password. Repeat the password and click Apply. 7. Select Manual in the Network configuration. 8. Enter the new IP address into the text field. 9. Enter the new addresses for Subnet mask and Default gateway into the text fields. 10. Note down the set IP address. 11. If you do not want to use a DNS-Server, select No, otherwise enter the IP addresses. Click on the diskette to save the settings. The device restarts after this. Checking the Ethernet connection to the device Note The device saves your settings. You can only access the configuration page of the device and modify settings using these addresses. After manual TCP/IP configuration settings, the device always starts with the latest saved configuration - even if the power supply was switched off for a short time. You can check the device in the Ethernet network, if: The device is integrated into the Ethernet network The device is energized The PC/notebook is in the same Ethernet network. Procedure Start a web browser on your PC/notebook (e.g. MS Internet Explorer ). Via DHCP: Enter the default host name (consisting of Turck_+serial number) found on the device's type label (e.g.: Turck_000915) and press <Enter>. Manual IP configuration: Enter the set IP address (basic setting: 169.254.0.1) and press <Enter>. Information on the PROFIBUS network is displayed in the web browser. D301144 0509 Installation PB-XEPI 17

Connecting the PROFIBUS Connecting the PROFIBUS The 9-pin D-Sub socket is used for connection. Only use standard PROFIBUS plugs and cards. Wire the PROFIBUS plug according to the details for pin assignment (see Technical data on page 23). If the device is installed at the beginning or end of the PROFIBUS cable segment, you will need a bus terminating resistor (see page 19). Warning! Do not use branch lines for the connection. If local conditions do not allow a direct connection, use a repeater (connection according to PROFIBUS norm). 1. Attach the PROFIBUS connector onto the PROFIBUS socket on the device. 2. Secure the plug with screws. 3. Switch the switch for the bus terminating resistor on the PROFIBUS connector to the required position (ON/OFF). [1] [2] [3] PROFIBUS Repeater Master Slave Slave Slave Fig. 5: Possibilities for interface connection in the PROFIBUS network 1 Connection at end/start of bus with terminating resistor 2 Connection in the middle of the PROFIBUS segment 1 3 Connection in a seperate PROFIBUS segment behind a repeater. 18 Installation PB-XEPI D301144 0509

Bus terminating resistors Bus terminating resistors Terminations of a PROFIBUS network must each be terminated with a bus terminating resistor. Use standardized plugs containing terminating resistors.. +5 V DC/DC (Pin 6) Data+ (Pin 3) Data (Pin 8) GND DC/DC (Pin 5) [1] [2] [3] Fig. 6: Bus termination configuration for PROFIBUS (see PROFIBUS standard IEC 61185) 1 390 Ω Pull-up resistance from pin 3 to positive supply voltage at pin 6 2 220 Ω Cable terminating resistor between pin 3 and pin 8 3 390 Ω Pull-down resistance from pin 8 to data reference potential at pin 5 Warning The PROFIBUS is shorted if you use the device as a passive terminating resistor (supply voltage from the device) and the device is switched off. This may cause disruption or complete failure of PROFIBUS communication. Use active resistors to avoid this problem. In this case the terminating resistors are fed with +5 V and GND independently from the device. Setting PROFIBUS parameters Depending on the application software (not included in the scope of delivery) used, the device can be a passive station (without an own station address) or an active station (class 2 PROFIBUS master). The setting of the PROFIBUS parameters is only required, if you use the device as a class 2 PROFIBUS master or in the operation mode PROFIBUS network access. The PROFIBUS parameters are given by the class 1 PROFIBUS master. D301144 0509 Installation PB-XEPI 19

PB-XEPI operation modes PB-XEPI operation modes PROFIBUS Diagnosis The default setting at delivery of the device is the PROFIBUS diagnosis mode. It enables monitoring of the entire PROFIBUS network. You can configure the monitoring setup. Procede equal to Checking the Ethernet connection to the device (see»procedure«on page 17). Click on the Settings tab and login as an administrator. Select Admin as user and enter the password (Default is the six-figure serial number of the device). Select View - PROFIBUS diagnosis. Here you can configure the settings of Measurement, Alert and Time Server. If you need help, click on the question mark. Fig. 7: PROFIBUS diagnosis settings 20 Installation PB-XEPI D301144 0509

PROFIBUS network access PROFIBUS network access The PROFIBUS network access operation mode enables use of the PB-XEPI for other applications (PROFIBUS Scope from Trebing & Himstedt, TH OPC Server DP from Trebing & Himstedt, FDT frame application with CommDTM PROFIBUS DP- V1 from Trebing & Himstedt or Emerson s AMS Suite). Procede equal to Checking the Ethernet connection to the device (see»procedure«on page 17). Click on the Settings tab and login as an administrator. Select Admin as user and enter the password (Default is the six-figure serial number of the device). Select View - PROFIBUS diagnosis. Click on Stop to stop the measurement. Cange the view to PB-XEPI. Then select PROFIBUS network access as operation mode and save your settings by clicking on the diskette. Fig. 8: Settings PROFIBUS network access D301144 0509 Installation PB-XEPI 21

Troubleshooting Troubleshooting Device is not found in the Ethernet network Check the power supply (LED RUN must light green). Check for correct connection (RJ-45, see page 12). The device is preset to Ethernet network operation with a DHCP server (IP address for the device is assigned by the DHCP server). If your network server does not support DHCP, you need to set the IP address for the device yourself (see»connection in a network with manual IP assignment«on page 15). When a patch cable is used between PC/notebook and device, both devices must be in the same network. PROFIBUS network is not found PB-XEPI as passive station: Check for proper connection (see»connecting the PROFIBUS«on page 18) and switch at Settings - PROFIBUS diagnosis - Measurement the baud rate on Automatic detection. PB-XEPI as active station (PROFIBUS network access): Check the PROFIBUS parameters for the channel used (see application software, not included in the scope of delivery). Each station has its own station address, which can only be assigned once in the network. LED ETH lights red or flashes red or green in case of failure or LED RUN lights red internal error Internal error or defect: Please contact Technical Support. 22 Installation PB-XEPI D301144 0509

Technical data Technical data Electrical data Nominal supply voltage VDC 24 (19.2...28.8) (limit values) Current consumption ma 190 max. Protection class IP 20 Operating conditions Ambient temperature C 0 +50 range Relative humidity % 20...80 (no condensation) Case data Dimensions W H D mm 22.5 99 114.5 Weight (approx.) g 120 PROFIBUS interface Interface Type RS 485 Transmission rate bps 9,600...12M Sub-D plug pin assignment 5 9 6 1 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 not assigned not assigned B line data+ (RxD/TxD-P) RTS GND (0 V) Potential (+5 VDC) not assigned A line data (RxD/TxD-N) not assigned Other Ethernet connection Type RJ45 (10Base-T/100Base-TX) Certificates CE D301144 0509 Installation PB-XEPI 23

Technical data 24 Installation PB-XEPI D301144 0509

D301144 0509 Installation PB-XEPI 25

TURCK WORLD-WIDE HEADQUARTERS www.turck.com GERMANY Hans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Mülheim an der Ruhr Phone +49 (0) 208 4952-0 Fax +49 (0) 208 4952-2 64 E-Mail more@turck.com D301144 0509 *D301143ßß0509* Subject to change without notice