Liebert Maintenance Bypass Cabinet

Similar documents
Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Liebert Load Bus Sync Extender/Adapter for Dual Bus UPS

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 120 Volt

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 230 Volt

Liebert MicroPOD 230V

Liebert IntelliSlot Relay Card

MONITORING INTELLIRACK USER MANUAL

GXT 2U Configuration Program

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching

Liebert Precision Power Center

THE NEW SHAPE OF NETWORK POWER PROTECTION

SERIES 610 LOAD BUS SYNC

Liebert THE NEW SHAPE OF NETWORK POWER PROTECTION. UPStation GXT 2U. An On-Line UPS With Proven Reliability,

Liebert APM UPS The Industry s Highest Energy Efficiency In A Row-Based, On-line UPS. AC Power For Business-Critical Continuity

300 Series 330/320 Surge Protective Device Installation, Operation and Maintenance Manual

Chloride CROSS Rack 16 A, 32 A and 63 A

Liebert Nfinity. A Powerful UPS Solution For Small To Medium Data Centers. AC Power For Business-Critical Continuity

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Installation. MGE Galaxy 3500 and Smart-UPS VT. Maintenance Bypass, Distribution and Transformer Cabinet

400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual

Liebert : The Right Cooling For IT Environments

Liebert LM Series. Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity

Liebert APS kva Modular UPS. Installer/User Guide

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Liebert NX. UPS For Small And Medium Business. AC Power For Business-Critical Continuity

Surge Protective Devices. STV25K Series. Instruction Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

Model 2380 Rack-Mount Kit

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016.

DC-D2212R / DC-D2212WR

hp uninterruptible power system r12000 xr models installation instructions

Series Amp Pad Mount Quick Connect Input and Output Power Panels

TRC-190 User s Manual

Installation Job Aid for Ethernet Routing Switch 3600 Series

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

UPS READY POWER DISTRIBUTION ASSEMBLY

G5 PDU Installation Guide

PowerLogic High Density Metering System 1-Meter Enclosure

Installing the Tracer MP503 Input/Output Module Ordering number: ,

SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

Dell Networking S4810 Open Networking (ON) Getting Started Guide

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

Model 2380 Rack-Mount Kit

Temperature. Power requirements. Weight. Dimensions

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

Liebert PSI5. Installer/User Guide

DC-D4213RX DC-D4213WRX

OV1000 Part No OV1000 HEIGHT ADJUSTABLE TABLE USER GUIDE

Smart Solutions Intelligent, Integrated Infrastructure for the Data Center

MicroTech II TM Remote I/O Panel Installation Manual

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

Junos WebApp Secure 5.0 Hardware Guide

VFI RTG PDU 6-10K. Installation and user manual. Service and support: Call your local service representative

Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Surge Protective Devices. STV100K Series. Instruction Manual

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

Surge Protective Devices. STV100K Series. Instruction Manual

Installation and Maintenance

Series Amp Quick Connect Input and Output Power Panels

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

ORB TM 4-20 ma Input Box Installation & Operation Manual

OV1001 Part No OV1001 HEIGHT ADJUSTABLE TABLE USER GUIDE

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Avanti HP Series Centrifuges Preinstallation

Liebert NX from 30 to 60 kw. AC Power for Business-Critical Continuity

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

True Sinewave Power Inverter 1000W & 2000W 230V , Owner s Manual

Instruction Manual (Supplementary) Totally-Enclosed Box Type Inverter

Liebert NXr Series 15KVA to 90KVA (208V/220V) AC Power for Business-Critical Continuity

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

MicroTech II Remote I/O Panel Installation Manual

TRC-190 User s Manual

Eaton 9PX PowerPass Distribution Modules and Transformers 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide

Zip12. Charging Desktop Cabinet. User's Guide. Components. Tools Needed ENGLISH. Requires 2 people to remove from box. 6mm. M6 x 35mm Security Screw

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

PanelView Plus/VersaView CE Terminals and Display Modules

3190 Series Touch Screen POS Workstation

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4

5 B&W Rear View System Camera

3 Uninterruptible Power Systems

INSTALLATION INSTRUCTIONS

ICS Entrance Management Sign Installation Guide. Version 1.0

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

HV-CS kv Edge Mount Triaxial Jack

Transcription:

AC Power For Business-Critical Continuity Liebert Maintenance Bypass Cabinet User Manual - Wall-Mountable

TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1 LOSSARY OF SYMBOLS........................................................2 1.0 ENERAL DESCRIPTION...................................................3 1.1 System Description........................................................... 3 1.2 Features................................................................... 3 1.3 Standard Components........................................................ 3 2.0 MODES OF OPERATION....................................................5 2.1 Bypass Switch............................................................... 5 2.2 UPS Mode.................................................................. 5 2.3 Bypass Mode................................................................ 6 3.0 PREPARATION..........................................................7 3.1 Inspection.................................................................. 7 3.2 Environment................................................................ 7 3.3 Required Setup Equipment.................................................... 7 3.4 Site Preparation............................................................. 7 3.5 Mounting the Cabinet........................................................ 8 4.0 CABLE INSTALLATION.....................................................9 4.1 Wiring Preparation........................................................... 9 4.1.1 Preparing Internal Wiring...................................................... 9 4.2 Dual Source Configuration.................................................... 9 4.2.1 Removing the Cover Plates.................................................... 10 4.3 Power Cable Installation..................................................... 10 4.3.1 Input/Output Wiring (TB1).................................................... 11 4.3.2 Connection to XT10000T..................................................... 11 5.0 OPERATIN PROCEDURES................................................16 5.1 Start-Up and Initialization................................................... 16 5.2 Shutting Down the UPS...................................................... 16 5.3 Transferring System from UPS to Maintenance Bypass Operation................... 16 5.4 Transfer of the System from Maintenance Bypass to UPS Operation................. 16 6.0 MAINTENANCE.........................................................17 6.1 Proper Care................................................................ 17 7.0 SPECIFICATIONS........................................................18 i

FIURES Figure 1 Front view...................................................................... 4 Figure 2 Rear view....................................................................... 4 Figure 3 Maintenance Bypass Cabinet in UPS Mode........................................... 5 Figure 4 Maintenance Bypass Cabinet in Bypass Mode......................................... 6 Figure 5 Wall-mount dimensions........................................................... 8 Figure 6 Wiring modifications for dual inputs................................................. 9 Figure 7 Cover plate removal............................................................. 10 Figure 8 Maintenance Bypass Cabinet..................................................... 12 Figure 9 Connecting Maintenance Bypass to XT10000T-208X................................. 13 Figure 10 Connecting Maintenance Bypass to XT10000T-240X................................. 14 Figure 11 Connecting Nfinity to Maintenance Bypass.......................................... 15 TABLES Table 1 Dimensional data................................................................ 7 Table 2 Nfinity power cable and protection ratings........................................... 10 Table 3 XT 10kVA power cable and protection ratings....................................... 11 ii

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be closely followed during installation and maintenance of this wall-mountable Maintenance Bypass Cabinet. This product is designed for commercial/industrial use only. This product is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS and the Maintenance Bypass Cabinet rating label.! WARNIN Lethal voltages may be present within this unit even when it is apparently not operating. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Never work alone. The Maintenance Bypass Cabinet is designed for use on properly grounded (earthed) 208/240 VAC, 50 or 60Hz supply, for installation by qualified personnel. This UPS equipment is intended to be installed by a qualified / certified electrician who must review and approve customer supplied wiring, circuit breakers, intended loads and verify correct input, output and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes. Installation instructions and warning notices are located in 4.0 - Cable Installation.! CAUTION To reduce the risk of fire: The NMBHW4x model must be connected to a circuit provided with 100A maximum branch circuit overcurrent protection in accordance with applicable national and local electrical codes. The NMBHW8x model must be connected to a circuit provided with 125A maximum branch circuit overcurrent protection in accordance with applicable national and local electrical codes. Operate the UPS equipment in an indoor environment only in an ambient temperature range of 32 F to 104 F (0 C to 40 C). Install it in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases, or corrosive substances. Never block or insert any object into the ventilation holes or other openings. 1

LOSSARY OF SYMBOLS Risk of Electrical Shock Indicates Warning or Caution Followed by Important Instructions AC Input AC Output i Requests the user to consult the manual Equipment rounding Conductor ON OFF 2

eneral Description 1.0 ENERAL DESCRIPTION Congratulations on your purchase of Liebert s wall-mountable Maintenance Bypass Cabinet. As with every Liebert product, we stand behind our quality. If you have any questions concerning this wallmountable Maintenance Bypass Cabinet, please feel free to contact your local dealer, Liebert representative, or call the appropriate Technical Support number listed on the back of this manual. To ensure proper installation and operation of this unit, please read this manual thoroughly. Installation must be done by a qualified/certified electrician, but general operation may be performed without special training. 1.1 System Description This wall-mountable Maintenance Bypass Cabinet is intended for use with the Nfinity, UPStation XT 6&10 kva, or any other UPS with equivalent specifications. Typical applications include supporting workstations, servers, network, telecom or other sensitive electronic equipment. The Maintenance Bypass Cabinet was designed to provide maximum system availability to business critical equipment. The Maintenance Bypass Cabinet allows for transfer of connected loads to an alternate power path allowing full isolation of the UPS. The UPS can then be turned OFF and removed from service with no interruption of power to connected loads. 1.2 Features Supports up to 20 kva loads High speed transfer switch Compact design Multiple power path indicators 1.3 Standard Components Easily accessible terminal blocks Wall-mountable Dual-source compatible for increased availability 3

Figure 1 Front view Bypass Mode Indicator Lamp UPS Mode Indicator Lamp eneral Description Lockout/Tagout Door SW1 CB1 SW2 Figure 2 Rear view End cover plate (removable for internal inspection) TB6 Slot for wall-mount arrangement (one of four) Knockout for cable entrance (one of five) rounding lug End plate (remove during cable installation) 4

Modes of Operation 2.0 MODES OF OPERATION The Maintenance Bypass Cabinet is designed to operate in UPS mode and Bypass mode. The mode is selected using the Bypass Switch. 2.1 Bypass Switch The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass source. 2.2 UPS Mode While the Maintenance Bypass Cabinet is in the UPS Mode, the UPS is supplying the connected load with continuous high quality AC power. In this mode of operation, the load is protected by the UPS. The Bypass Switch rotated toward the green lamp indicates this mode. Figure 3 Maintenance Bypass Cabinet in UPS Mode UPS output available (green) 5

2.3 Bypass Mode Modes of Operation When the Maintenance Bypass Cabinet is in the Bypass mode it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the UPS inverter to the bypass source. The amber lamp illuminated in the Maintenance Bypass Switch compartment indicates bypass is available. In this mode of operation the load is NOT protected by the UPS. The Bypass Switch rotated toward the amber lamp indicates this mode. See 5.0 - Operating Procedures for instructions on use. Figure 4 Maintenance Bypass Cabinet in Bypass Mode Bypass available (amber) UPS Input Source (amber): ON = AC power supplied to UPS input OFF= AC power removed from UPS input 6

Preparation 3.0 PREPARATION These installation instructions provide all the information needed for positioning the Maintenance Bypass Cabinet (including environmental requirements) and for connecting the input and output power cables. 3.1 Inspection Upon receiving the Maintenance Bypass Cabinet, examine the packaging for any signs of mishandling or damage. If any damage is noted, contact your local dealer or Liebert representative and notify your carrier. 3.2 Environment The Maintenance Bypass Cabinet environment must be free of conductive contaminants and excessive moisture (water condensation), flammable vapors, chemical fumes, or corrosive gases and liquids. 3.3 Required Setup Equipment The tools below are required in order to properly set up your Maintenance Bypass Cabinet: torque wrench flat-head screwdriver 3/16" (5 mm) Allen wrench T-20 Torx driver 3.4 Site Preparation When deciding where to locate your Maintenance Bypass Cabinet, consider the weight and size of the unit. Make sure that the structural integrity of the wall can withstand the weight. Refer to Table 1 for dimensional considerations: Table 1 Dimensional data Model NMBHWxx W x D x H in. (mm) 21 x 8 x 18 (533 x 203 x 457) Weight lb. (kg) 45 (20.5) 7

3.5 Mounting the Cabinet Preparation This Maintenance Bypass Cabinet may be placed on the floor or mounted on a wall. In both cases, ensure that the unit is in a well-ventilated area with at least 12 inches (305 mm) clearance for access to the switches and cable connections. When placing the cabinet on the floor, install the four rubber feet provided with the unit. One rubber foot goes on each corner of the unit on the side where keyhole slots have been cut. If the Maintenance Bypass Cabinet is to be mounted on a wall, you must install hardware to support the unit. Depending on the type of wall, you may need to install special anchors. The Maintenance Bypass Cabinet has four keyhole-shaped slots to support it when mounted on a wall. To mount the unit: 1. Mark the wall where you will install the mounting hardware, either screws, anchors or bolts strong enough to support the unit (see Figure 5 for layout dimensions). 2. Insert the mounting screws, anchors or bolts, leaving enough clearance between the bolt heads and the wall to accommodate the Maintenance Bypass Cabinet s metal case. 3. Tighten the mounting bolts until they are snug, holding the Maintenance Bypass Cabinet firmly against the wall. Figure 5 Wall-mount dimensions 1/2" (13mm) 21" (533mm) 19" (483mm) 0.281" (7mm) 18" (457mm) 14" (356mm) 2" (51mm) 8

Cable Installation 4.0 CABLE INSTALLATION 4.1 Wiring Preparation! WARNIN Please read this section thoroughly before attempting to install wiring to this unit. Be sure that the unit is not connected to any AC mains power source or UPS before installing any wiring to this unit. This Maintenance Bypass Cabinet should be installed by a qualified / certified electrician. 4.1.1 Preparing Internal Wiring The Maintenance Bypass Cabinet is factory-configured for single-source installations. If your installation requires dual-source capabilities, the Maintenance Bypass Cabinet s wiring must be modified. 4.2 Dual Source Configuration Modifying the wiring consists of removing the jumpers between TB1 and TB2 as described below: 1. Remove cover plates. 2. Identify TB1 and TB2. 3. Using a 3/16" Allen wrench, loosen terminal mounting jumpers between TB1 and TB2. 4. Remove jumpers and retighten terminals to 22-26 in-lb (2.5 to 3.0 Nm). 5. Connect primary source to TB2 and secondary source to TB1. Figure 6 Wiring modifications for dual inputs FRONT VIEW TB2 SIDE VIEW TB2 Remove these three cables TB1 TB1 9

4.2.1 Removing the Cover Plates Cable Installation Plates cover the input and output terminals on the back of the Maintenance Bypass Cabinet (see illustration below). Remove these using a T-20 Torx screwdriver. Keep screws and plates to one side. Figure 7 Cover plate removal Remove these screws to open end plate and cover plate. This screw and a second screw underneath unit serve as hinges to open end plate. Remove these screws to open end plate and cover plate (fourth screw is underneath unit). 4.3 Power Cable Installation Refer to Table 2 when selecting cables: Table 2 Nfinity power cable and protection ratings Model NMBHW4x Max Input Current 100 A Input Protection 100 A Max Output Current 100 A Input/ Output Terminal Details Max Input Current Input Protection Max Output Current Input/ Output Terminal Details Max: 2/0 (70 mm 2 ) Min: 6 AW (16 mm 2 ) Model NMBHW8x 125 A 125 A 125 A Max: 2/0 (70 mm 2 ) Min: 6 AW (16 mm 2 ) NOTE Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices, as these will carry the earth leakage currents of both the UPS equipment and the load. 10

Cable Installation 4.3.1 Input/Output Wiring (TB1) Follow the steps below to connect the input wiring: NOTE Input wiring must be installed using conduit. 208 input voltage jumper if only the connections for 208 VAC are made between the UPS and the Maintenance Bypass, the 208 input voltage jumper must be installed for proper operation. To install this jumper, place the jumper wire provided in the accessory kit between Pin 1 and Pin 2 on TB4. 1. Locate the input wiring access, remove the knockout and pull the three/four input wires through it, allowing some slack for installation. 2. Secure the conduit to the rear panel of the Maintenance Bypass Cabinet. 3. Input power cables connect to hex terminals on the input terminal block. 4. Insert the ground (earth) wire through the earth lug and tighten it to the proper torque value (22-26 in-lb). Then connect the wires to the block connections as shown below. Using a torque wrench, turn the screws clockwise until tightened to the proper torque value (22-26 in-lb). 4.3.2 Connection to XT10000T Wiring Preparation! WARNIN Please read these instructions thoroughly before attempting to connect any wiring to this unit. Ensure that the unit is not connected to any AC utility power source or UPS before connecting any wiring to this unit. Wiring connections should be performed only by a qualified/certified electrician. Power Cable Installation Refer to Table 3 and subsequent illustrations when selecting cables. Table 3 XT 10kVA power cable and protection ratings 208V 240V Max Input Current 45A 44A Input Protection 60A 60A Max Output Current 43A 42A Terminal Block Details Max: 35 mm 2 (2/0 AW) Min: 16 mm 2 (6 AW) NOTE Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices, as these will carry the earth leakage currents of both the UPS equipment and the load. 11

Cable Installation Figure 8 Maintenance Bypass Cabinet Input 2 TB2 TB5 Output Single input jumper (remove for dual input feeds) SW1 Bypass Switch CB1 Output Breaker Input 1 TB1 SW2 UPS Input Switch SW1 Bypass Switch TB3 TB6 TB4 UPS Input N/C C N/0 UPS Output 12

Cable Installation Figure 9 Connecting Maintenance Bypass to XT10000T-208X 120V 120V TB2 L1 NFINITY MAINTENANCE BYPASS CABINET WITHOUT TRANSFORMER TB5 1 208V Input 2 L2 N 2 3 Input 1 TB1 L1 L2 N TB3 L1 Remove these three wires for dual source (see NOTE below) L2 1 TB4 2 3 4 4 TB6 NO Common NC Flexible conduit EC Flexible conduit XT10000T-208X L1 L2 N L1 L2 L2A Input Output External Battery! CAUTION It is mandatory to connect exactly as shown. NOTE 1. SINLE-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2. 2. DUAL-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must be made to TB1 and the bypass input supply connection must be made to TB2. The jumpers between TB1 and TB2 must be removed. 3. If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to the output terminal TB5. 4. TB6 provides Normally Open and Normally Closed contacts to indicate operation of the bypass switch. Maintenance Bypass Switch Position TB6 Contacts Bypass NO - Common: Open NC - Common: Closed UPS NO - Common: Closed NC - Common: Open 13

Cable Installation Figure 10 Connecting Maintenance Bypass to XT10000T-240X TB2 L1 NFINITY MAINTENANCE BYPASS CABINET WITHOUT TRANSFORMER TB5 1 120V 120V 240V Input 2 L2 N 2 3 Input 1 TB1 L1 L2 N L1 TB3 L2 Remove these three wires for dual source (see NOTE below) 1 2 TB4 3 4 4 TB6 NO Common NC Flexible conduit EC Flexible conduit L1 L2 N L1 L2 XT10000T-240X Input Output External Battery NOTE 1. SINLE-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2. 2. DUAL-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must be made to TB1 and the bypass input supply connection must be made to TB2. The jumpers between TB1 and TB2 must be removed. 3. TB6 provides Normally Open and Normally Closed contacts to indicate operation of the bypass switch. Maintenance Bypass Switch Position TB6 Contacts Bypass NO - Common: Open NC - Common: Closed UPS NO - Common: Closed NC - Common: Open 14

Cable Installation Figure 11 Connecting Nfinity to Maintenance Bypass Input 2 Input 1 TB2 L1 L2 N TB1 L1 L2 N NFINITY MAINTENANCE BYPASS CABINET WITHOUT TRANSFORMER Remove these three wires for dual source (see NOTE below) TB3 TB4 L1 L2 1 2 3 4 TB5 1 2 3 4 TB6 NO Common NC 120 120 208 240 Flexible conduit L1 L2 1 2 3 1 2 3 4 5 TB1 TB2 TB3 EC See Nfinity user manual for details on connecting EC. Ensure that the tap selector is set to the correct input voltage NFINITY UPS NOTE 1. SINLE-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2. 2. DUAL-SOURCE FEED If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must be made to TB1 and the bypass input supply connection must be made to TB2. The jumpers between TB1 and TB2 must be removed. 3. If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to the output terminal TB5. 4. TB6 provides Normally Open and Normally Closed contacts to indicate operation of the bypass switch. Maintenance Bypass Switch Position TB6 Contacts Bypass NO - Common: Open NC - Common: Closed UPS NO - Common: Closed NC - Common: Open 15

Operating Procedures 5.0 OPERATIN PROCEDURES 5.1 Start-Up and Initialization Follow these steps to start up the UPS while connected to the Maintenance Bypass. 1. Set the bypass switch (SW1) to the UPS position on the Maintenance Bypass Cabinet. 2. Close the UPS source switch (SW2). 3. Close the output circuit breaker (CB1). 4. Close the UPS input circuit breaker. 5. On XT UPS models: Close the UPS output circuit breaker. On Nfinity UPS models: Close the control enable switch. After the UPS has initialized, turn the UPS output on by pushing the standby button. 5.2 Shutting Down the UPS Use the following procedure to power down the system. 1. On XT UPS models: Open the UPS output circuit breaker. On Nfinity UPS models: Turn the UPS output off through the User Interface display. Open the control enable switch. 2. Open the UPS input circuit breaker. 3. Open the UPS source switch (SW2) on the Maintenance Bypass Cabinet. 4. Open the output circuit breaker (CB1) on the Maintenance Bypass Cabinet. 5.3 Transferring System from UPS to Maintenance Bypass Operation 1. Verify the amber bypass lamp is illuminated. 2. Turn the bypass switch (SW1) to the bypass position on the Maintenance Bypass Cabinet. The connected equipment is now powered from the bypass source and is not protected by the UPS. 5.4 Transfer of the System from Maintenance Bypass to UPS Operation 1. Close the UPS source switch (SW2) on the Maintenance Bypass Cabinet. 2. Close the UPS input circuit breaker. 3. On XT UPS models: Close the UPS output circuit breaker. On Nfinity UPS models: Close the control enable switch. After the UPS has initialized, turn the UPS output on by pushing the standby button. 4. Verify the green UPS lamp is illuminated on the Maintenance Bypass Cabinet. 5. Turn the bypass switch (SW1) to the UPS position on the Maintenance Bypass Cabinet. 16

Maintenance 6.0 MAINTENANCE 6.1 Proper Care Keeping your Liebert Maintenance Bypass Cabinet operating properly is imperative to optimal performance and life of the unit. It is recommended that a certified technician perform preventive and corrective maintenance. Liebert lobal Services (LS) is dedicated to ensuring the highest level of performance and unmatched support for your Maintenance Bypass Cabinet. Contact an LS representative for services to guarantee maximum reliability and system availability. 17

Specifications 7.0 SPECIFICATIONS eneral & Environmental NMBHW4x = 16kVA Unit Rating NMBHW8x = 20kVA NMBHW4x = 100A max NMBHW8x = 125A max Compliant Safety Standards UL 1778, c-ul Mechanical Dimensions - W x D x H, in. (mm) 21 x 8 x 18 (533 x 203 x 457) Weight, lb. (kg) 45 (20.5) Environmental Operating Temperature, maximum, F ( C) 32-104 (0-40 ) Relative Humidity 5-95% noncondensing Operating Altitude, maximum, ft. (m) 10,000 (3,000) Input Data Nominal Input Voltage 208 or 240VAC Input Frequency, nominal 50 or 60Hz Input Frequency Range 45-55Hz or 55-65Hz Output Data 208/240 240 208 Output Voltage, VAC 120/120/208/240 120/120/240 120/120/208 Transfer Time <4 msec typical Output Frequency 50 or 60Hz (same as input) TB6 Contacts Maximum Voltage 120VAC Maximum Current 5A 18

Ensuring The High Availability 0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies including Liebert power and cooling technologies that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs. While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Technical Support / Service Web Site www.liebert.com Monitoring 800-222-5877 monitoring@emersonnetworkpower.com Outside the US: 614-841-6755 Single-Phase UPS 800-222-5877 upstech@emersonnetworkpower.com Outside the US: 614-841-6755 Three-Phase UPS 800-543-2378 powertech@emersonnetworkpower.com Environmental Systems 800-543-2778 Outside the United States 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 7/F, Dah Sing Financial Centre 108 loucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250 SL-23967_REV3_08-06 Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Systems Embedded Computing Connectivity Embedded Power DC Power Systems Integrated Cabinet Solutions EmersonNetworkPower.com Outside Plant Services Power Switching & Control Site Monitoring Precision Cooling Surge Protection Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2006 Emerson Electric Co.