Surgelogic Surge Protective Device I-Line Plug-On Unit Series Catalog 1310CT0201R5/07 2007 Class 1310 CONTENTS Description Page Product Description.................................................. 2 Application Information................................................ 3 Selection and Specifications............................................ 4 Replacement Parts................................................... 6 Dimensions and Weights.............................................. 7
Description Description I-Line Plug-On Unit with Surgelogic TVSS Surge protective device (SPD) units protect electronic equipment from transients. The I-Line Plug-On Unit with Surgelogic Transient Voltage Surge Suppressor (TVSS) is a modular parallel TVSS device designed for service entrance, distribution, or branch panel applications. The device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused. The I-Line plug-on unit with Surgelogic TVSS device is a high performance surge suppressor package incorporating individual modules for each phase. Modes of protection include: Line-to-Neutral (L N) Line-to-Ground (L G) Neutral-to-Ground (N G) Line-to-Line (L L) A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL Recognized thermosetting epoxy material another performance element that provides additional protection. Each surge suppression mode is individually fused and uses circuitry with thermal cutouts to isolate the TVSS and ensure shutdown in the event of MOV damage during severe overvoltages even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package. Design Features Same easy installation as I-Line circuit breaker Requires 13.50 in. (343 mm) of mounting space FC units mount in the same mounting slots as FA circuit breakers. FI units mount in the same mounting slots as KA circuit breakers Can be applied in a six-disconnect panel or switchboard (TVSS counts as one disconnect) High-energy parallel design for ANSI/IEEE C62.41 and C62.45 category B and C3 applications. 2 2007 Schneider Electric All Rights Reserved 05/2007
Application Information Application Information The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients. Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction. A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors. Protection should also be provided for critical areas with equipment essential to the company. Square D brand TVSS products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include: Banking Transportation Retail Education Wastewater/Sanitation Utility Government Medical Insurance Petrochemical Financial Data Processing Military Telecommunications Publishing Automated Manufacturing 05/2007 2007 Schneider Electric All Rights Reserved 3
Selection and Specifications Selection and Specifications Model Number Format FC 4 IMA 16 C The model number format consists of: Device Type, Voltage Code, TVSS Model, Surge Current Rating Code, and Option Code. The possible device types and codes are shown in the tables below. Option Code Surge Current Rating Code TVSS Model (IMA only) Voltage Code Device Type In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac 3-phase, 4-wire, 160 ka surge capacity with surge counter. Specifications Device Types, Interrupting Ratings, and Continuous Current Ratings Device Type Interrupting Rating @ 240 Vac @ 480 Vac @ 600Y/347 Vac Continuous Current Rating FC 100 ka 65 ka 60 A FI 200 ka 200 ka 100 ka 60 A Voltage Codes and Systems Voltage Code Voltage System 1 120/240 Vac 1-phase, 3-wire 2 208Y/120 Vac 3-phase, 3-wire or 4-wire 3 240/120 Vac 3-phase, 4-wire (high leg Delta) 4 480Y/277 Vac, 3-phase, 3-wire or 4-wire 7 380Y/220 Vac, 3-phase, 3-wire or 4-wire 8 600Y/347 Vac, 3-phase, 3-wire or 4-wire Surge Current Rating Codes and Surge Capacities Surge Current Rating Code Per Phase Per Mode L N L G N G 12 120 ka 60 ka 60 ka 120 ka 16 160 ka 80 ka 80 ka 120 ka 24 240 ka 120 ka 120 ka 120 ka Surge Suppressor Options, Descriptions, and Option Codes Option Description Option Code Surge counter Displays the combined total number of transient voltage surges detected from L N, L G, N G, and L L since the counter was last reset. C Remote monitor Displays the alarm status of the surge protective device up to 1000 ft (305 m) away from the unit. This option uses the dry contacts. Order catalog number TVS12RMU Dry contacts Provides available Form C type contacts. Standard Audible alarm with enable/disable switch Provides audible indication that there is a loss of protection. Standard 4 2007 Schneider Electric All Rights Reserved 05/2007
Selection and Specifications UL Suppression Voltage Ratings IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR) Partial Catalog Number Voltage Service L N L G N G L L MCOV Surgelogic I-Line Plug-on TVSS Unit FC1IMA FI1IMA FC2IMA FI2IMA FC3IMA FI3IMA FC4IMA FI4IMA FC7IMA FI7IMA 120/240 Vac, 1-phase, 3-wire 208Y/120 Vac, 3-phase, 3-wire or 4-wire 240/120 Vac, 3-phase, 4-wire (high leg Delta) 480Y/277 Vac, 3-phase, 3-wire or 4-wire 380Y/220 Vac 3-phase, 3-wire or 4-wire 400 400 400 800 150 400 400 400 800 150 800/400 800/400 400 1500/800 275/150 800 800 800 1600 320 800 800 800 1600 320 600Y/347 Vac, FI8IMA 1200 1200 1200 2000 420 3-phase, 3-wire or 4-wire MCOV = Maximum Continuous Operating Voltage Not available as FC device Standard Features and Descriptions Feature Description Environmental Relative humidity: 0 to 95% non condensing Operating frequency: 47 63 Hz Surge suppression operating temperature: -40 +65 C (-40 +149 F) Storage temperature: -40 +65 C (-40 +149 F) UL 1449, Second Edition, UL 1283 Compliance standards culus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5 (TVSS unit only) Meets 2002 NEC Article 285.6 Fused suppression Fused with individual surge-rated fuses (200 kair) paths Thermal Thermal cutout for low current faults protection On-line test functions Diagnostics Indication per phase Service indicator shown on the front panel of each TVSS unit Replaceable Separate, replaceable modules for each phase modules Self-contained suppression circuits and filtering for each module LED indicators Indication of loss of protection Suppression Individually-fused modules Solid state Bi-directional Front panel alarm Includes an enable/disable switch High-energy Category A, B, and C3 applications parallel design EMI/RFI Filtering Up to -50 db (100 khz to 100 MHz) Short-circuit 200 ka (TVSS modules only) current rating Duty cycle tested ANSI C62.41 C3, Minimum 5000 impulses 10 ka 20 kv Warranty Five years Surge counter liquid crystal display may not indicate at temperatures less than -20 C (-4 F) 05/2007 2007 Schneider Electric All Rights Reserved 5
Replacement Parts Replacement Parts MA Module Replacements Voltage System 120/240 Vac, 1-phase, 3-wire 208Y/120 Vac, 3-phase, 3 wire or 4-wire 240/120 Vac, 3-phase, 4-wire (high leg Delta) 480Y/277 Vac, 3-phase, 3-wire or 4-wire 380Y/ 220 Vac, 3-phase, 3-wire or 4-wire 600Y/347 Vac, 3-Phase, 3-wire or 4-wire Peak Surge Current Rating Catalog Number Phase A Phase B Phase C 120 ka MA1IMA12 Empty MA1IMA12 160 ka MA1IMA16 Empty MA1IMA16 240 ka MA1IMA24 Empty MA1IMA24 120 ka MA1IMA12 MA1IMA12 MA1IMA12 160 ka MA1IMA16 MA1IMA16 MA1IMA16 240 ka MA1IMA24 MA1IMA24 MA1IMA24 120 ka MA1IMA12 MA3IMA12 MA1IMA12 160 ka MA1IMA16 MA3IMA16 MA1IMA16 240 ka MA1IMA24 MA3IMA24 MA1IMA24 120 ka MA4IMA12 MA4IMA12 MA4IMA12 160 ka MA4IMA16 MA4IMA16 MA4IMA16 240 ka MA4IMA24 MA4IMA24 MA4IMA24 120 ka MA7IMA12 MA7IMA12 MA7IMA12 160 ka MA7IMA16 MA7IMA16 MA7IMA16 240 ka MA7IMA24 MA7IMA24 MA7IMA24 120 ka MA8IMA12 MA8IMA12 MA8IMA12 160 ka MA8IMA16 MA8IMA16 MA8IMA16 240 ka MA8IMA24 MA8IMA24 MA8IMA24 With all system voltages, TVSS devices must be grounded in accordance with all applicable standards. Phase B modules are different than Phase A and Phase C modules. Surgelogic Device Mounted in Panel with 4-Piece Trim Installed 6 2007 Schneider Electric All Rights Reserved 05/2007
Dimensions and Weights Dimensions and Weights 5.07 [129] 12.16 [309] 13.50 [345] Weight: 18.90 lb (8.60 kg) in. Dimensions: [mm] FC I-Line Plug-On Unit (Front View) 5.07 [129] 12.16 [309] 13.50 [345] Weight: 23.30 lb (10.60 kg) in. Dimensions: [mm] FI I-Line Plug-On Unit (Front View) 05/2007 2007 Schneider Electric All Rights Reserved 7
Schneider Electric USA 1601 Mercer Road Lexington, KY 40511 USA 1-888-SquareD (1-888-778-2733) www.us.squared.com Schneider Electric Canada 19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca 1310CT0201R5/07 2007 Schneider Electric All Rights Reserved Replaces 1310CT0201R3/03 April 2003. 05/2007