Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Similar documents
INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Relion 611 series. 611 series Type Test Certificate

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

Type VRLTC tap changer

satech TSB-14 MAIN FEATURES

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

GRD130 - FEATURES APPLICATION

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

REYROLLE 2RMLG. Operating Recommendations

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

Arc protection relay. Features Three-phase overcurrent function. Application

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

MMLG 01, 02, 03, 04 MMLB01

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

RM4JA01F current measurement relay RM4-J - range ma V AC

Feeder protection relay SPAA 121 C. Product Guide

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

02/11/2015

Solid-state Timer H3YN

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

Solid-state Timer. Ordering Information. Specifications. Miniature Timer Compatible with the MY Relay. Accessories. Time Ranges

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

02/11/2015

Remote I/O RIO600 Product Guide

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

RM4TA32 three-phase network control relay RM4-T - range V

For Transmission, Distribution and Machinery protection.

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

RE9RA21MW7 off-delay timing relay s V AC -

RT4B-110V/12A RECTIFIER

Arc protection relay. Features Three-phase overcurrent function. Application

RM4TR31 three-phase network control relay RM4-T - range V

Protection and control. Sepam range Sepam 100 RT. Merlin Gerin Square D Telemecanique

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

Electronic timer CT-ARS.11

Communication Gateway COM 610. Product Guide

High impedance protection relay

Earth-fault Relay SPAJ 110 C. Product Guide

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Residual overvoltage relay

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

Synchro-check relay. Application

Datasheet - SRB 402EM-24V

RE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz

Table 1 Relay Model and Function

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Zelio Control-modular measurement and control relays 1

Electronic timer CT-ERS.21

Model Number Structure

MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

EM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

POWERSOLVE ELECTRONICS LTD PSL400-XX series Conduction Cooled Power Supply Engineering Specification

Electronic timer CT-ERD.12

Universal Power Supplies

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

Voltage Transducer UMT516 / MT516

08/07/2015

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

efo Series Wide range AC/DC Single Output 1000W Rugged Power Supply Electrical Specification for: Telkoor Part Number:

RM4UA33M voltage measurement relay RM4-U - range V V AC

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

GRE130. Protection and Control for MV Systems

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

RM4LA32M liquid level control relay RM4-L V AC

02/11/2015

Protection Relays PHASE & RESIDUAL OVERCURRENT

Features. Applications and Benefits TRC ELECTRONICS, INC

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

Model Number Structure

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

RT4F-110V/25A RECTIFIER

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

Transcription:

Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction Non-volatile trip indication (MVTT 4 only) Application This range of static time delay relays is particularly suitable for use in protection and control schemes and industrial process plant. The relays can perform with consistent accuracy over a large number of operations, with little or no maintenance over long periods. Furthermore, the static have been designed to perform with complete reliability in the electrically hostile environments often ened in electrical power stations and substations and also over a very wide range of ambient temperature. Type variations Model for time delayed operation on Pick-up MVTT 4 Drop-off MVTT 5 Auxiliary supplies: Five dc supply ranges are available Timing ranges: Five standard timing ranges are available Figure Type MVTT 4 relay removed from case 506

Description Type MVTT 4 with timedelayed pick-up As shown in Figure 2, the MVTT 4 relay is initiated by an external contact which connects the dc supply to relay terminal 3. The dc supply is permanently connected to relay terminals 2 and 4. The closure of the external contact causes the to be reset immediately and starts the CMOS oscillator which generates a square wave output to the binary coded decimal. The required time delay is preset by adjusting the three binary coded decimal thumbwheel switches. Each thumbwheel switch output to the associated provides a successive decade setting of between 0 and. When the comparator detects that the accumulated count has reached the set count determined by the thumbwheel settings, then the output element is energised and the internal oscillator inhibited. The relay resets instantaneously when the external contact is reopened. Type MVTT 5 with time delayed drop-off As shown in Figure 3 the MVTT 5 versions have similar to the MVTT 4. The dc supply is continuously applied to the relay. Closing the external initiating contact causes the relay output element to pick-up instantaneously. The drop-off time delay is initiated by opening this contact which starts the CMOS oscillator. The output element remains in the energised state until the comparator detects that the accumulated count has reached the set count, determined by the thumbwheel settings. At this instant the output element is de-energised, thus removing the dc to the dc regulator circuit by opening the internal hold-on contact (RL 6-). Power supplies Relays designed for power supplies of 220/250V dc are supplied with an external assembly for connection in series with the dc auxiliary supply to the relay. 2 3 4 5 6 7 8 0 2 3 4 + Vx in 0v Close to start timer R ext(2) See Note 4 2 3 4 Power supply See Note 2 Oscillator Counter reset Inhibit oscillator Binary coded decimal Comparator secs Binary coded decimal switches OP RL5 RL3 RL3 2 8 0 5 3 7 6 2 4 2 22 Module terminal block viewed from rear Notes (a) (b) (c) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals 2 Earthing connections as shown are typical only 3 Connections are applicable for 24/27, 30/34, 48/54 7 0/25V 4 Rext(2) is required for MVTT4 to meet ES48 4 class 2. (Not applicable to 24/27V version) Figure 2 Application diagram: digital time delay relay type MVTT 4 (dc version) 507

Vxin + 0V 2 3 4 5 6 7 8 0 2 3 4 Open to start timer R ext(2) See Note 4 2 22 3 4 Power supply RL6 Inhibit reset circuit Inhibit oscillator Oscillator Binary coded decimal Comparator secs Binary coded decimal switches RL3 RL6 RL3 2 8 0 5 3 7 6 2 4 2 22 Notes (a) CT shorting links make 2 Earthing connections as shown are typical only before (b) & (c) disconnect 3 Connections are applicable for 24/27, 30/34, (b) Short terminals break before (c) 48/54 7 0/25V 4 Rext(2) is required for MVTT5 to meet (c) Long terminals ES48 4 class. Module terminal block viewed from rear (Not applicable to 24/27V version) Figure 3 Application diagram: digital time delay relay type MVTT 5 (dc version) + Vx in _ 0V 2 3 4 5 6 7 8 0 2 3 4 V start HN007 Close to start timer Vx out See Note 2 3 2 4 Power supply Oscillator Counter reset circuit Inhibit oscillator Binary coded decimal Comparator secs Binary coded decimal switches OP RL5 RL3 RL3 2 8 0 5 3 7 6 2 4 2 22 Module terminal block viewed from rear Notes (a) (b) (c) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals 2 Earthing connections as shown are typical only Figure 4 Application diagram: digital time delay relay type MVTT 4 220V (dc version) 508

Figure 5 Application diagram: digital time delay relay, type MVTT 5 220V (dc version) Standard setting ranges Technical Data Voltage rating Rating (Vx) Operating range Vdc 24/27 to 32 30/34 24 to 37.5 48/54 38 to 60 0/25 87 to 50 220/250 75 to 300 Burdens DC Burden (ma) Rated Elements Unoperated Elements Operated Voltage Vx MVTT 4 MVTT 5 MVTT 4 MVTT 5 24 5 5 20 0 30 25 25 25 20 48 25 25 85 75 0 0 0 40 35 220 65 65 65 65 ms to s in ms steps 0ms to 0s in 0ms steps 0.s to 00s in 0.s steps s to 000s in s steps 0s to 0000s in 0s steps Accuracy ±2% of setting or +20ms -0ms, whichever is the greater Consistency ±0.5% or 5ms, whichever is the greater Disengaging time <0ms ting time <20ms Contacts MVTT 4 element : Miniature relay Contacts: 4 change-over MVTT 5 element : Miniature relay Contacts: 4 change-over 50

Contact ratings Make and carry for 0.2s ac 7500VA with maxima of 30A or 300V Make and carry continuously ac 5A dc 5A Break ac 250VA with maxima of 5A and 300V dc 50W (resistive) 25W (inductive) L/R =0.04s with maxima of 5A or 300V Durability Loaded contact 0,000 operations minimum Unloaded contact 00,000 operations minimum Operation indicator A non-volatile, hand-reset led trip indicator is supplied as standard on the MVTT 4 (delay on pick-up) only. High voltage withstand Dielectric withstand IEC 255-5:77 2kV rms for minute between all terminals and case earth. 2kV rms for minute between all terminals of independent, with terminals on each independent circuit connected together. kv rms for minute across normally open. High voltage impulse IEC 255-5:77 Three positive and three negative impulses of 5kV peak,.2/50ms, 0.5J between all terminals of the same circuit (except output ), independent, and all terminals connected together and case earth. Electrical environment DC supply interruption IEC 255-:7 The unit will withstand a 0ms interruption in the auxiliary supply, under normal operating conditions, without de-energising. AC ripple on dc supply IEC 255-:7 The unit will withstand 2% ac ripple on the dc supply. High frequency disturbance IEC 255-22-:88 Class III 2.5kV peak between independent and between independent and case earth.0kv peak across terminals of the same circuit (except metallic ). Under the conditions created by this test an additional tolerance of ± 3% is allowed. Electrostatic discharge IEC 255-22-2:8 Class II 4kV discharge in air with cover in place IEC 80-2: Level 2 4kV point contact discharge with cover removed Fast transient disturbance IEC 255-22-4:2 Class IV 4kV, 2.5 khz applied directly to auxiliary supply IEC 80-4:88 Level 4 4kV, 2.5 khz applied directly to all inputs Surge immunity IEC 000-4-5:5 Level 3 2kV peak.2/50µs between all groups and case earth 2kV peak,.2/50µs between terminals of each group EMC compliance 8/336/EEC Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route EN 5008-2:4 EN 50082-2:5 Generic Standards were used to establish conformity Product safety 73/23/EEC Compliance with the European Commission low voltage directive EN 600-:3/A2:5 EN 6050:2/A3:5 Compliance is demonstrated by reference to generic safety standards Atmospheric environment Temperature IEC 255-6:88 Storage and transit -25 to +70 C Operating -25 C to 55 C IEC 68-2-:0 Cold IEC 68-2-2:74 Dry heat Under the conditions created by this test an additional tolerance of ±3% is allowed. Humidity IEC 68-2-3:6 56 days at 3% RH and 40 C Under the conditions created by this test an additional tolerance of ±3% is allowed. Enclosure Protection IEC 52:8 IP50 (dust protected) Mechanical environment Vibration IEC 255-2-2:88 Response Class 2 Endurance Class 2 Shock and bump IEC 255-2:88 Shock response Class 2 Shock withstand Class Bump Class Seismic IEC 255-2:3 Class 2 50

Environmental withstand Temperature IEC 68 2 /IEC 68 2 2 Storage and transport 25 C to +70 C Operating 25 C to +55 C Humidity IEC 68 2 3 56 days (at 3% RH and 40 C) Enclosure protection IEC52 IP50 (dust protected) Vibration IEC 255 2 0.5g between 0 and 300Hz Push button projection 0 max 77 45 4 holes 4.4ø 68 3 24 5 48 Panel cut-out: Flush mounting fixing details 32 22 25 min. 57 max. Cases MVTT 4 and MVTT 5 relays are housed in size 2 cases as shown in Figure 6 5 All dimensions in mm Flush mounting Figure 6 Case outline size 2 Information Required with Order Relay type Voltage rating Timing range required 5