Service & Support. How do I configure extended PROFIsafe on the CU240E-2?

Similar documents
Service & Support. How can the Safety Functions of SINAMICS S120 be activated in an existing STEP 7 Project? Technology CPU.

Service & Support. MODBUS/TCP Communication over Integrated PROFINET Interface of S7-300 and S7-400 CPU. Modbus/TCP PN CPU.

FAQ about Drive Technology

Application for Process Automation

Changeover SINAMICS CU240E to CU240E-2 (as from Firmware V4.4) SINAMICS G120. FAQ October Service & Support. Answers for industry.

SINAMICS S120 Safety Integrated Extended Functions

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

ID Title Description of the restriction Solutions for the restriction

Applications & Tools. Controlling distributed I/Os and drives from two controllers via PROFINET (Shared Device via Object Manager) SIMATIC & SINAMICS

Applications & Tools. Controlling distributed I/Os and drives from two controllers via PROFINET (Shared Device via GSD file) SIMATIC & SINAMICS S

ISO SINAMICS G110D FAQ

FAQ 03/2014. How do I go online? SIMOTION & SINAMICS.

SIMOTION with SINAMICS S120 Safety Integrated Extended Functions Fail-safe drives connected to SIMOTION D435 Controlled with PROFIsafe via PROFIBUS

Upgrade instructions for the SIMOTION I-Device (PROFINET) SIMOTION V4.1 V4.2 or higher. FAQ March Service & Support. Answers for industry.

Service & Support. How do you create a communication of with an Industrial Thin Client SIMATIC ITC? Thin Client.

Applications & Tools. Controlling the CU320-2 via PROFIsafe with PROFIBUS SINAMICS S120. Application example July Answers for industry.

FAQ about Drive Technology

SIMATIC/SINAMICS. Getting started with SINAMICS V90 PN on S Motion Control. Fundamental safety instructions 1. Introduction

Applications & Tools. Control of the Safety Integrated Extended Functions for the CU320-2 (with FW V4.4) in conjunction with EPOS SINAMICS S120

Drive System Application

Configuration of a Measuring Probe on a SINAMICS S120 CU3x0 / CU3x0-2 for Use in a Technology CPU 31xT

How Do You Replace a CPU 41x with the CPU 410-5H Process Automation? SIMATIC PCS 7 FAQ 01/2016

Applications & Tools. SINAMICS S120: Control of the Safety Integrated Basic Functions via onboard terminals SINAMICS S120

PROFIsafe modules V2 ipar 75x-66x/ WAGO Safety-Editor-75x Quickstart

SINAMICS S120 Safety Integrated Extended Functions

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

SIMATIC. Function modules FM 351 First Steps in Commissioning. Purpose of the Getting Started. Requirements 2

Applications & Tools. Application to support the acceptance test of the Safety Integrated Functions of SINAMICS G120 SINAMICS G120

Cover sheet. Help for Planning Plants with PCS 7 OPC DA SIMATIC PCS 7 OPC DA. FAQ March Service & Support. Answers for industry.

Introduction to the TIA Portal V13, S7-1500, and Startdrive

Applications & Tools. SINAMICS S110 EPOS via FB283. Control via PROFIBUS Safety via F-DI. Application Description February Answers for industry.

Storage Concept and Data Backup Mechanisms for SIMATIC S7-300

Applications & Tools. Controlling Safety Integrated Extended Functions and transferring the F-DIs of the CU310-2 PN via PROFIsafe with PROFINET

SINAMICS SINAMICS G120. Frequency inverter with Control Units CU240E-2 CU240E-2 DP CU240E-2 F CU240E-2 DP-F. Function Manual Safety Integrated 07/2010

PROFIsafe SITRANS. Pressure transmitter SITRANS P, DS III PROFIsafe series. Product Information 7MF4*34 04/2008 A5E

Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

SIMATIC. Automation Systems S7-300 CPU 317T-2 DP: Controlling a SINAMICS S120. Introduction. Preparation 2. Learning units 3. Further Information 4

Service & Support. Which options exist for reading hardware limit switch signals into a technology CPU? Technology CPU.

How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ

FAQ about Drive Technology

Applications & Tools. Controlling distributed I/Os and drives from two controllers via PROFINET (Shared Device via Object Manager) SIMATIC & SINAMICS

SINAMICS S110 EPOS via FB283 Control via PROFIBUS Safety via PROFIsafe Application Description

Why can you not transfer the HMI configuration to the panel? - PROFIBUS Connection - FAQ 03/2014

SINAMICS G120 / G120C / G120D / G120P (with FW >= 4.6) SIMATIC S7-300/400. Short-Documentation 04/2014


Applications & Tools. Controlling the CU320-2 via TM54F and F-CPU with PROFIBUS in conjunction with EPOS SINAMICS S120

Applications & Tools. Control of the Safety Integrated Extended Functions of the SINAMICS S110 via the fail-safe inputs of the CU305 SINAMICS S110

Service & Support. How can you transfer a WinCC (TIA Portal) project to an operator panel using Ethernet? WinCC (TIA Portal) FAQ February 2012

Applications & Tools. Entering limit values for safely limited speed (SLS) into a SINAMICS S120 via PROFIsafe with PROFINET SINAMICS S120

Application Edition 03/05 ET200S FC. Start-up ET200S FC


SINAMICS G120 SINAMICS G120C

Using PROFIsafe modules in combination with PROFIBUS-DP and PROFINET Application note

Aotewell SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St

Connecting MGB-L1B-PN to Siemens S7 315F (TIA Portal V13)


First Steps with S7-PDIAG and ProAgent

Bumpless Media Redundancy with PROFINET IRT (MRPD) SIMOTION & SINAMICS. Application description July Applications & Tools. Answers for industry.

Display of SINAMICS Fault Messages in WinCC V7.4

SCE Training Curriculum for the end-to-end automation solution Totally Integrated Automation (TIA)

Communication between HMI and Frequency Converter. Basic Panel, Comfort Panel, Runtime Advanced, SINAMICS G120. Application Example 04/2016

Application example 03/2017. PROFINET-system redundancy with SINAMICS drives.

Drive System Application

Function Example No. MC-FE-I-011-V10-DE

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

SCE Training Curriculum for Integrated Automation Solutions Totally Integrated Automation (TIA)

Cover. SINAMICS G120 with CU240S DP (FW3.2) Control via PROFIBUS. Application July Applikationen & Tools. Answers for industry.

Application description 08/2014

What's new? New functions for. SIMOTION V5.2 SP1 Edition 04/2018 siemens.com/simotion

Welcome Guideline D435 training case with SIMOTION 4.1 SP1

Connecting a PC Station to an S using OPC

Industrial Controls. SIMOCODE pro SIMOCODE pro PCS 7 Library. Preface. Security information. Product specific security. information.

SIMATIC. Process Control System PCS 7 V7.0 SP1 Software Update With Utilization of New Functions (PCS 7 V6.x to V7.0 SP1) Preface.

SIMOTION V4.1 SP2 HF3/HF4

Display of SINAMICS Error Messages in Runtime Professional

CDN Series Displays with Profibus-DP ELEN UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE

Applications & Tools. Configuring RT communication between SIMATIC and SIMOTION (I-Device) SIMATIC & SIMOTION. Application Example June 2012

TIA Portal Workshop. Unrestricted. Siemens AG All rights reserved.

DX200 OPTIONS INSTRUCTIONS


SINAMICS G: Speed Control for G110, G120, G120C or G120D using S7-300/400F (in STEP 7 V5) via PROFIBUS with Safety Integrated and HMI

Spring Training Atlanta, GA

Block for SIMOTION SCOUT for Monitoring 24V-Branches

Description of the Simotion D4xx Firmware update

Migration of STL Programs to S7-1500

AS-Interface. Safety Integrated Application Manual

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE D14


Service & Support. Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server SIMATIC S7. Function description March 2013


SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

Siemens Drives & PLCs


SIEMENS. General conditions and function limitations, notes for configuration and operation

SIMOTION. New functions of version V4.1 SP2

DVPPF02-SL PROFIBUS DP Slave Communication Module

Setting up a secure VPN Connection between SCALANCE S and CP x43-1 Adv. Using a static IP Address. SCALANCE S, CP Advanced, CP Advanced

Applications & Tools. Time-of-Day Synchronization between WinCC Runtime Professional and S7 Controllers. WinCC Runtime Professional

SIMOTION with SINAMICS S120 Safety Integrated Extended Functions Fail-safe drives Controlling a D435 via TM54F and F-CPU

Transcription:

How do I configure extended PROFIsafe on the CU240E-2? SINAMICS G120 CU240E-2, CU240E-2 F, CU240E-2 DP, CU240E-2 DP-F, CU240E-2 PN, CU240E-2 PN-F, FAQ March 2013 Service & Support Answers for industry.

Question This entry is from the Siemens Industry Online Support. The general terms of use (http://www.siemens.com/terms_of_use) apply. Clicking the link below directly displays the download page of this document. http://support.automation.siemens.com/ww/view/en/68188133 Caution The functions and solutions described in this article confine themselves to the realization of the automation task predominantly. Please take into account furthermore that corresponding protective measures have to be taken up in the context of Industrial Security when connecting your equipment to other parts of the plant, the enterprise network or the Internet. Further information can be found under the Content-ID 50203404. http://support.automation.siemens.com/ww/view/en/50203404 Question Answer The instructions and notes listed in this document provide a detailed answer to this question. 2 1.0, Item-ID: 68188133

Table of content Table of content 1 Configuring Extended PROFIsafe...4 1.1 Prerequisites...4 1.2 Configuring the devices...5 1.3 Configuring the drive for safety in STARTER software...10 1.0, Item-ID: 68188133 3

1 Configuring Extended PROFIsafe 1.1 Prerequisites In the following explanation of configuring extended PROFIsafe functions the devices used during the configuration are a CU240E-2 PN Control Module with an S7-315F PN/DP V3.2 Prior to starting the setup process for safety, the Name and IP address of the control unit should be set. This name and IP must match the Name and IP that is set in the hardware configuration of the S7 project. Two options exist; telegram 30 and telegram 900. Both telegrams provide support for extended safety, but telegram 900 offers one higher level option. Telegram 900 provides feedback to the master control on the status of the F-DI digital inputs. Even if the F-DI inputs are not being used in the drive safety configuration, the status of the inputs will be returned to the master control, allowing them to be used in the higher level logic. Telegram 900 will only work with a CU240E-2 XX-F (DP or PN) safety control unit. If you are going to evaluate the status of the Drive unit fail-safe inputs at the master control level, and if you are using a F safety CU, Profi-safe telegram 900 will be the correct choice. For all other applications, telegram 30 should be used. NOTE When using telegram 900, the safety inputs in the drive must be set to enable to prevent a configuration fault (F1653). This will be explained in a later step. Likewise, if using telegram 30, the safety inputs must be set to Inhibit in the drive or a configuration fault will be generated. Again, telegram 900 can only be used in the F safety control units.. 4 1.0, Item-ID: 68188133

1.2 Configuring the devices To configure the PROFIsafe functions the following procedure should be performed: 1. Configure the Hardware configuration with the appropriate CPU and drive. For this example, we will use telegram 20 for control of the drive and PROFIsafe telegram 900 for safety. Add the telegrams for the device. 2. Double click on the safety telegram and select the profisafe tab. 3. Record the HEX value for F_DEST_ADD to be used later (in this case it is C8). Figure 1-1 4. Double click on the CPU to open the properties. 5. Select the cyclic interrupts tab. 6. Set OB35 = 75. 7. Select the Protection tab and select level 3. 8. Set the password (make sure you record it for future use) and select the box CPU contains safety program. 9. Click OK. 10. Record the input and output addresses for the profisafe telegram and standard telegram for use later. 11. Record the address of the input module being used for the safety inputs. 12. Save and compile the hardware config download it to the CPU and close the HW Config window. 13. In the Simatic Manager add the F_CALL and F_LAD blocks. 1.0, Item-ID: 68188133 5

Figure 1-2 14. Insert OB35, OB82, OB86, and OB122. NOTE OB35 is a cyclic OB that runs every 200 milliseconds. 15. Double click on FC1, set and confirm password (siemens for our example). 16. Define new F-runtime group window will open. 17. Verify FC1 is the F-CALL block and FC2 is the F-Program block. 18. Click OK. Figure 1-3 19. The Edit F-Runtime Groups window will open. 20. Click OK to accept. 6 1.0, Item-ID: 68188133

Figure 1-4 21. The safety program window will open. 22. Compile the safety parameter and verify they compile with no errors. 23. Select download and download the safety program to the CPU. 24. After downloading, close the safety program window. Figure 1-5 25. Open FC 2 and add 4 rungs to connect inputs to bits in the safety telegram. In our example, the safety telegram 900 started at 1.0, so we will connect switches to set bits 1.0, 1.1, 1.4, and DB546.DBX0.2, which is the acknowledge for reintegration bit. DB546 was automatically generated when we added the safety function to the CPU. This DB address may be different depending on your CPU type. NOTE our input addresses are in red because I am not using a safety input module (F- DI). 1.0, Item-ID: 68188133 7

Figure 1-6 26. Save and close the editor window. 27. Double click on OB35 to open it in the editor. 28. Add FC1 to the first network. Save and close. Figure 1-7 29. Select Options - edit safety program 8 1.0, Item-ID: 68188133

Figure 1-8 30. If prompted enter the password. 31. Compile the safety program and verify it compiles with no errors. Figure 1-9 32. Select Download to load the safety program into the CPU. 33. Close the safety program window. This now has our PLC configured for extended safety for the G120 drive. Now we need to configure the drive for safety with Starter software. 1.0, Item-ID: 68188133 9

1.3 Configuring the drive for safety in STARTER software 1. In the Simatic Manager highlight the project name. 2. Select insert Sinamics. A window will open to allow you to select your drive. We are using a CU240E-2 PN-F Firmware 4.5. 3. Set the IP address and click OK to insert the selected drive into the project. Figure 1-10 4. Now select the drive and click on commissioning. Starter should launch. Figure 1-11 5. In starter, click the icon connect to selected target devices. If the IP was set correctly, starter should connect to the drive, and the following window will appear. 10 1.0, Item-ID: 68188133

Figure 1-12 6. Select load hardware configuration to PG and the Power module type will be uploaded to the project. Next, the online/offline comparison window will open. If your starter project has default values. 7. Select load to PG to upload the current parameters from the drive to the project. 8. Acknowledge the upload then close the comparison window. Figure 1-13 We are now online with our drive, and can confirm this by the green coupling at the left of the drive name. 1.0, Item-ID: 68188133 11

Figure 1-14 9. Expand the control unit tab, and the functions tab. 10. Double click on safety integrated. Figure 1-15 11. Select Change settings. For this example we are going to use Extended functions VIA PROFIsafe. Although we used telegram 900, we will not utilize the F-DI inputs on the drive in this example. Figure 1-16 When using Profisafe telegram 900, Click on the Safety inputs tab, and click all switches that you wish to monitor. Since we are not going to connect the inputs, we 12 1.0, Item-ID: 68188133

will leave all 3 switches OPEN, but we will set the selection dropdown to enable and click close. Failure to match this step with the selected telegram will result in a F01653 and/or a F01711 fault (profisafe configuration error). WARNING When using telegram 30, make sure the safety inputs are set to inhibit. When using telegram 900, make sure they are enabled to prevent a configuration error on the drive. Figure 1-18 12. Click on Configuration and enter the PROFIsafe address. This address is the value we recorded from F_DEST_ADD in the safety telegram earlier. Figure 1-19 13. Click STO tab and set the forced checking procedure time (default t=8 hours max is 9000 hours) 1.0, Item-ID: 68188133 13

Figure 1-20 14. Click on the Safe Limited Speed (SLS) tab and enter the desired velocity allowed when SLS is active. Figure 1-21 15. Set the safety functions to enable. Figure 1-22 16. Click on copy parameters then activate settings. You will be prompted to change the safety password. The default is 0, and you can either leave it at 0 or change it. NOTE If it is changed, the password must be documented for future reference. If the password is lost, it can not be recovered and safety cannot be modified or disabled. 14 1.0, Item-ID: 68188133

17. You will be prompted to save to rom. Click okay, and after this completes, go offline and cycle power on drive to enable the modified safety settings. After a power cycle, if the safety light is blinking, an acceptance may be required. Cycle each of the inputs for each safety input to perform the safety acceptance. When all inputs are active, the Yellow safety indicator should be on steady. When any of the inputs are turned off, the yellow safety indicator should be blinking, indicating a safety condition. When the safety light is blinking, the drive will be inhibited from normal operation. If SLS (safe limited speed) is active, the drive will only run at the speed programmed in the SLS tab above. Figure 1-23 Any other safety input will inhibit the drive from running. If the red BF light is blinking, then you do not have communications between your PLC and the drive. Verify the name and IP of the control unit match the name and IP programmed into the hardware configuration and that the project has been downloaded correctly. If you verify the IP and hardware configuration is correct and a bus fault is generated when you enable safety, default the drive back to factory settings and reconfigure. Occasionally the drive configuration will get corrupted preventing the safety telegram from communicating correctly with the drive. Reset both the safety setup and the drive back to factory defaults, the reconfigure. 1.0, Item-ID: 68188133 15