Instruction Manual CTC-1

Similar documents
Instruction Manual HID-2

Instruction Manual HPH-8

TOXALERT MODEL AIR 2000

CO2 Controller Operating Instructions Models: RAD-0501, RAD-0501A, RAD-0501E 1. Product Description

CDD4 Duct Carbon Dioxide Transmitter

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

Schneider Electric s SCD series of duct mount sensors measure the levels of CO 2. , RH (if equipped) and temperature of air inside a duct.

CDD Carbon Dioxide Transmitter

HWS Series Wall Mount with Relay Setpoints, LCD, and Humidistat Control

OVEN INDUSTRIES, INC.

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

HT Series Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control

CDD4 Series Room CO2 Transmitter Installation Instructions

HT Series Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

C7110C1001A / C7110D1009A WALL MODULES

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

LC3 LIGHTING CONTROLLER OPERATIONS & MAINTENANCE MANUAL 2013 Dec

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS

Model CD-AW. Infrared Environmental CO2 Sensor. Operator's manual

NSGV Series "90DM3" Carbon Dioxide Detector

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide

NSI DIGITAL DIMMING SYSTEM DDS 5300 / 5600 DIMMER PACK

MICRO GROW GREENHOUSE SYSTEMS, INC

OZONE SWITCH Model OS-6. OS-6 Features

Carbon Monoxide (CO) Gas Detection and Control System

ES-600 Ozone Controller Operation Manual

AirTest Model CN9000 Series Sensor Controller

Model 305e OEM CO 2 concentration sensor

Switched Mode Power Supply Operating manual PAP800

Thermometer / Barometer System

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Andover ContinuumTM Infinet II

AGROWtEK Technology to Help You Grow

FRICK QUANTUM HD UNITY SYSTEM CONTROLLER

SP6R Level Controller Operation Manual

MOD-RI Room Interface Modules with Modbus

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Dim levels for each system output may be controlled by any of the following methods:

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

LC8 CONTROLLER BOARD INSTALLATION AND MAINTENANCE MANUAL (IMM) p/n 52280T rev 11/08/05

TPE 1464 Series Pressure Transducer

Gavita Master Controller EL1F

Section 11. Electrical System. 42--CF200--MA--09 (formerly 42-65) Issued 5/96 P/N B. E 1996 Nordson Corporation All rights reserved

FCU (FREE COOLING UNIT)

User Manual. PolyGard AT Infrared Carbon Dioxide transmitter Serial No. AT December, PolyGard is a registered trademark of MSR

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812

Andover ContinuumTM Infinet II

Multi-Point Gas Detection and Control System

2001VT Temp & CO 2. - air quality sensor/controller NOTE!!! Manual for Installation. General. SenseAir AB

Indoor Air Quality Meter/Datalogger

Multi-Point Gas Detection and Control System

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

KCD-HP. KCD-HP200x, 300X. [Figures] Top : 1% Sensor probe Bottom left : 10% / 20% Sensor probe Bottom right : Holding bracket(optional) Measurement

User's Guide. Model W 3-in-1 Switching DC Power Supply

Multi-Point Gas Detection and Control System

TC-9102 Series Surface Mount Temperature Controllers

Output signal active note. Output signal. temperature DC V, DC V DC V, DC V DC V

Product User Guide PR2000. PR2000 Pressure Data Logger with LCD

Application. Types Available. Duct sensor for air quality, temperature and humidity (optional) Datasheet

Installation & Operation and Maintenance

ETM-2050/ETM-2051 Service Manual

Manual Control Unit GFC 32

BACnet. b3810 Series Local Controllers

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

FEATURES AND BENEFITS. Installation and operation. Controller

T7560A1036 Digital Wall Module

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

Measure & Control Temperature & CO2 levels with analog & digital I/O

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

RXTP ROOM TEMPERATURE

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

FCU-MULTI Modbus Fan Coil Unit Controller

User s Guide TG Series C. Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008

Installation Manual. 65 Interactive LED/LCD. Model: HILF65101 (64.56 )

Under the Table Interconnect Solutions

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S

PDS100 Programmable Dispensing System SAFETY INSTRUCTIONS

Zenith DS9000 Dispensing System

INSTALLATION INSTRUCTIONS

Model OI x22 ProSafe

AQS51/61-KAM COMBINED CO 2 -/TEMPERATURE DUCT SENSOR/CONTROLLER

MH-Z16 Intelligent Infrared Gas Module

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

Manual Simatek Control Unit GFC 32

MAC3 Wind Speed Alarm & Controller. Installation Instructions

LAUREL ELECTRONICS, INC.

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

QUICK START. Installation & Programming Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

User Guide. Indoor Air Quality Meter/Datalogger. Model EA80

Transcription:

Troubleshooting & Specs CTC-1 Amps / Volts requirements Min / Max operating temperature Min / Max operating Humidity Temperature Measurement range Temperature Accuracy CO2 sensor type CO2 Measurement range CO2 Accuracy CO2 sensor warm-up time Temp analog output signal type 15 amps @ 120 volts 32 to 120 F 0-99% RH 32-122 F +/- 1.8 F NDIR 0-3000 PPM +/- 85 PPM Less than 15 minutes 0-10 volt Instruction Manual CTC-1 CO 2 & Temperature Controller CO2 analog output signal type 0-10 volt Analog resolution 10mv Computer Interface *Optional RS 232 / 9-pin D-sub Baud Rate 4800 Weight / Dimensions 7lbs / 8 x 6.5 x 3.1 Life Expectancy > 10 years All Sentinel Timers and controllers offer a 3-year warranty. Ask your retailer for details. Sentinel products are distributed by: GPS / Global Product Solutions LLC. www.growgps.com

Welcome to the future... Controlling temperature and CO 2 PPM levels has never been easier. The CTC-1 combines an accurate digital temperature sensor and a state of the art NDIR CO 2 sensor in one reliable and easy to use controller. By controlling supplemental CO 2 with PPM (part-per-million) accuracy, plant growth can be accelerated by as much as 30%. CONTENTS A quick look at the CTC-1 Installation of the CTC-1 Operating the CTC-1 Calibrating the CTC-1 Computer Interface Analog Output Connection Examples Troubleshooting & Specs The CTC-1 has been designed to maintain a specific temperature and CO 2 level within an area. It can operate any 120 volt CO 2 device and any 120 volt cooling or heating device. There are multiple modes of operation that allow it s use for more than one application. Because of it s built-in flexibility, the CTC-1 is equally at home controlling a variety of agricultural applications OR controlling a mushroom farming operation. Agricultural applications involve increasing the CO 2 level to between 1000 and 1500 PPM by using either compressed CO 2 or operating a combustible gas CO 2 generator. Mushroom farmers need to reduce the CO 2 level because mushrooms produce CO 2. An exhaust fan can be connected to the CTC-1 to keep the CO 2 level at the desired level. Troubleshooting & Specs Problem: The unit does not power up at all. Check and reset the circuit breaker. A small red button will pop out at the bottom of the unit, press it in to reset. If the problem continues, reduce the number of devices connected to the unit. Problem: The CO2 outlet does not turn on. 1) There are different modes that can be selected. Refer to Page 6 to fully understand how the modes affect the CO2 function. 2) The Photocell on the front face may affect the CO2 function. If it is selected to operate, during the Day, ensure the photocell is receiving enough light to activate it. (Green LED will be ON) Problem: The CO2 reading does not seem to be accurate. A quick check of the calibration of the CO2 sensor can be performed. Refer to page #9 to check and recalibrate the sensor. Problem: The unit reads Warm Up for more than 10 minutes. Turn the power switch Off for 5 seconds, then turn the switch On. After 10 minutes, the unit should complete the start-up and begin to display the temp and CO2. If it does not, contact the factory. Problem: The device I have connected to the Temperature receptacle, cycles On & Off too much. The CO2 and temperature deadband can be increased to reduce cycling of the device. Refer to setting dead bands on page #7 Problem: The unit does seem to react as quickly to changes. The internal fan is designed to draw in through the bottom and out the top on the enclosure. The internal sensors then sense the air flowing across them. If the vents in the bottom or top of the enclosure are blocked, the unit may not react as quickly to changes. Disconnect the unit and use low pressure compressed air to blow out any debris accumulated in the vent areas. Problem: I would like to return the unit to is default settings. The Restore Factory Setpoints button will allow the unit to be returned to it s original state. Only use this function if all other attempts to resolve an issue have failed. *Note: you may need to recalibrate the CO2 sensor Refer to page #9 Problem: The digital display is frozen or changing rapidly. Certain devices such as Electronic (Digital) Ballasts and Ozone generators produce a huge amount of electronic noise. If you are operating these other devices, locate them as far away from the controller as possible.

Connection examples For indoor growing, Cooling devices connect to the Temperature receptacle. A quick look at the CTC-1 LCD displays temperature and CO2 PPM levels The optional 12 volt DC adapter allows the CTC-1 to be coordinated with other controllers like the EVC-2. Heaters can be connected to the Temperature receptacle OR 12 button keypad to change settings Optional 12 VDC CO2 disable jack (2) 120V receptacles to connect cooling or heating device and CO2 equipment up to 15-amps. Photocell allows CO2 use only during the Day OR 24-hours. Mushroom farmers need to reduce CO2 levels. Connect you ventilation fan to the CO2 receptacle to remove excess CO2. OR OR Plants require increased CO2 levels Connect your 120 volt CO2 generator to the CO2 receptacle. Built-in fan samples the air for quicker and more accurate measurements. Plants require increased CO2 levels Connect your 120 volt compressed CO2 solenoid / regulator assembly to the CO2 receptacle. 15-amp @ 120V Circuit breaker Heavy-duty Power switch

Installing the CTC-1 1) Locate a suitable location. The unit should be at plant height. The photocell on the front of the unit can operate with indirect to full light. 2) First secure the provided bracket to the wall. Next snap the controller into place and tighten the (2) thumb-screw.s top & bottom. NOTE: Make sure the thumb-screws are in place before attempting to use the controller. The sensor is VERY fragile treat it with care. 3) The internal CO2 PPM sensor and the temperature probe will measure the level of CO2 and the temperature of the air. The built-in fan ensures accurate readings by sampling the air flowing through the enclosure. 4) The unit requires a 120 volt, 15-amp power supply. Plug the power cable into a standard Nema 5-15 wall outlet. 5) The devices that will be controlled must be 120 volt & 15-amps or less. 6) If you are using a cooling or heating device, connect the device s power cable into the receptacle marked Temperature. NOTE: In order for the CTC-1 to work correctly for YOUR application, you may need to first check and change some factory setpoints. Refer to Operating the CTC-1 section of this manual. Analog Output An additional built-in function on the CTC-1 is the ability to drive (2) linear analog devices such as a chart recorder or any other device that requires a 0-10 volt or 0-20 ma signal. There are 2 separate outputs for both the temperature and CO2. The outputs can be configured for ma or mv by positioning (2) blue jumpers on the control PC board. *Note: The factory setting is for ma output. The wires connected to the analog terminals can be routed out of the unit through the blank receptacle covers on the left side of the unit. NOTE: Make sure the unit is unplugged before attempting to open the unit. Connections to the analog outputs must be made correctly. RS 232 interface (3) terminal Red Yellow Brown Temperature Analog output (2) terminals CO2 Analog output (2) terminals on right side 7) Connect the CO2 device to the receptacle marked CO2 Device. You can operate a CO2 generator, a compressed CO2 regulator or ventilation device. (For mushroom farming) 8) Turn the power switch to the ON position and you are ready to go. NOTE: Pressing any of the buttons on the CTC-1 activates, wakes-up the keypad and displays Keypad Test O.K. Then you can select the desired setpoint button to change the setting. There are 12 buttons on the unit that control all the functions. CO2 Setpoint: Press this button for 1 second to display and change the current CO2 Part-Per-Million setting Factory setpoint 1250 PPM. Temperature Analog output selection jumper CO2 Analog output selection jumper

Computer interface Advanced user and researchers will appreciate the CTC-1s ability to be connected to a computer. The computer interface and software allows the user direct access to the CTC-1 control board. Once connected via a RS 232 / 9-pin serial connection, the software will chart and record the temperature or CO2 levels. The current measurements are displayed clearly on your laptop or computer. Users can also change settings and recalibrate the unit from the software. You can even select an automatic SAVE function to save the results directly to an Excel spreadsheet. The optional interface kit consists of a 9-pin interface cable that is hard-wired into the control board, a CD ROM and instructions. Installing the CTC-1 (Continued) CO2 Dead-band: Press this button for 1 second to display and change the current CO2 Dead-band. Factory setpoint 50 PPM. CO2 Calibrate: Press this button for 1 second to re-calibrate the CO2 sensor. * Refer to the Calibration section. Factory setpoint 375 PPM. Temp Setpoint: Press this button for 1 second to display and change the current Temperature setting. Factory setpoint 78 F. Temp Dead-band: Press this button for 1 second to display the current temperature Dead-band setting. Factory setpoint 2 F. NOTE: Make sure the unit is unplugged before attempting to open the unit. Connections to the computer interface must be made correctly. Temp Calibrate: Press this button for 1 second to display the re-calibrate the temperature sensor. * Refer to the Calibration section. Factory setpoint 1250 PPM. Screenshot of computer running optional software Relay Mode: Press this button for 1 second to select one of the three available modes of operation. * Refer to the Operating the CTC-1 section of this manual. Factory setpoint Mode #1. Restore Factory Settings: Press this button for 1 second to restore the originally programmed factory setpoints. This will revert the unit to its original state. UP: Press this button to display to increase the setting. Down: Press this button to display to increase the setting. Enter/Reset: Press this button accept and enter the new setpoint. Clear / Back: Pressing this button will cancel the previous selection.

Operating the CTC-1 The CTC-1 has been designed to be simple to set-up and program. Separate buttons for each setting make changes easy. Selecting the desired Relay Mode: There are (3) available modes of operation that control the function of the control relays and the CO2 and Temperature control devices connected to the unit. * Most hydroponic, indoor or greenhouse operators. Mode #1 / Temperature COOLING and CO 2 Increase mode. The temperature control will over-ride the CO 2 control. * Indoor mushroom farmers. Mode #2 / Temperature HEATING and CO 2 Decrease mode. Both the temperature and CO 2 output are controlled independently. * Optional mode for greenhouse operators. Mode #3 / Temperature HEATING and CO 2 Increase mode. Both the temperature and CO 2 output are controlled independently. NOTE: The relay mode will affect how the Temperature and CO2 receptacles will operate. If mode #1 is selected, the CO2 receptacle will be disabled when the Temperature receptacle is turned ON. To change the Relay Mode setting: press the Relay Mode button on the keypad. Keypad Test OK is displayed. Pressing it again will display the current setpoint. Use the Up or Down button to change the setting. Press Enter to accept the new setpoint. To cancel and go back, press the Clear / Back button. Factory setpoint Mode #1. To select the photocell operation: The photocell can be used to ensure the CO2 is only activated during the day. (Agricultural users) But the photocell can also be bypassed for people growing mushrooms. (Mushroom farmers select relay mode #2 to decrease CO2 levels) Moving the 2 position switch to the 24-hour mode will force the CO2 controller to function 24-hours a day regardless of whether it is light out or not. People using the CTC-1 for agricultural purposes other than mushroom farming should set the photocell selector switch to the Daytime setting. Factory setpoint Daytime. Connecting to external controllers For some agricultural users, it is best to coordinate the Temperature and CO2 functions. This is done when the temperature control receptacle is connected to an exhaust fan and the CO2 is connected to a compressed CO2 system. If the functions are not coordinated, the exhaust fan can pull the compressed CO2 out of the growing area as fast as it is being released which is very wasteful and expensive. The CTC-1 already has the ability to coordinate the two functions by selecting mode #1 which will disable the CO2 function whenever the exhaust fan is activated. However some users may choose to interface an additional device to the CTC-1. For instance, the EVC-2 which has separate Day and Night temperature setpoints. Connecting the EVC-2 to the CTC-1 gives you Day / Night temp control with coordinated CO2 use during the day. Optional 12 VDC CO2 disable jack The CO2 Disable function is an optional feature which allows the user to connect a low-voltage 12 volt DC power supply to the CTC-1. The power supply (shown below) is plugged into a device like the EVC-2 Temperature receptacle. When the Temperature receptacle on the EVC-2 is turned ON, the 12-vdc power supply connected to the side of the CTC-1 will disable the CO2 receptacle on the CTC-1 while the temperature control device is activated reducing the amount of CO2 being used. 12 volt DC power supply (Optional)

Calibrating the CTC-1 (Continued) Temperature Calibration: Under normal conditions, the Temperature sensor should not need to be calibrated. If the unit appears to not be measuring the temperature levels correctly or if the unit has been dropped or jarred severely, you can recalibrate the unit. 1) You will need another accurate temperature measurement device to compare the reading to. Place the units side by side. 2) To activate the automatic calibration sequence, press the Temp Calibration button, the display will read Keypad Test OK. 3) Pressing the Temp Calibration button again will display the new temperature calibration point. (Factory set at 75 F) 4) The calibration level can be changed by using the UP and Down buttons. Change the display to the correct calibration point. 5) Pressing Enter will start the calibration process. The process is almost instantaneous. When complete, the display returns to normal operation. The unit can now be returned to service. Warning!!! Some electronic devices such as Electronic (Digital) HID ballasts and Ozone generators produce large amounts of electronic noise, which can affect other equipment. The Sentinel line of controllers and timers have been hardened by using shielded cable and shielded enclosures however some EBs do not have proper shielding. For best results it is highly recommended to position your controller at least 8 ft away from any EBs (Electronic Ballasts). It is also a good idea to route the cables going from the EB to the HID lamp away from the controller and the remote temperature probe cable attached to the controller. 8 ft minimum Keep Electronic ballast at least 8 ft away from other electronic equipment. Operating the CTC-1 (Continued) Setting the CO2 level: Setting the desired CO2 PPM level is simple. Most users can use the factory setpoint of 1250 PPM. To change the setting, press the CO2 Setpoint button on the keypad. Keypad Test OK is displayed. Pressing it again will display the current setpoint. Use the Up or Down button to change the setting. Press Enter to accept the new setpoint. To cancel and go back, press the Clear / Back button. Factory setpoint 1250 PPM. NOTE: The built-in photocell has a 30 second time delay. The photocell can be used to control the CO2 function. See page 6 Setting the Temperature level: Setting the desired Temperature level is simple. Most users can use the factory setpoint of 78 F. To change the setting, press the Temp Setpoint button on the keypad. Keypad Test OK is displayed. Pressing it again will display the current setpoint. Use the Up or Down button to change the setting. Press Enter to accept the new setpoint. To cancel and go back, press the Clear / Back button. Factory setpoint 78 F. Setting the CO2 Dead-band: The CO2 Dead-band can be set by the user. The dead-band is the range of measurement that the control will allow the CO2 level to vary by. The higher the setting, the less often the CO2 device will turn ON and OFF. Lower settings will cause the CO2 device to turn ON and OFF more frequently. Press the CO2 Dead-band button on the keypad. Keypad Test OK is displayed. Pressing it again will display the current setpoint. Use the Up or Down buttons to change the display to the desired mode. Press Enter to accept the change. Factory setpoint 50 PPM Setting the Temperature Dead-band: The Temperature Deadband can be set by the user. The dead-band is the range of measurement that the control will allow the Temp level to vary by. The higher the setting, the less often the temperature control device will turn ON and OFF. Lower settings will cause the Temp device to turn ON and OFF more frequently. Press the Temp Dead-band button on the keypad. Keypad Test OK is displayed. Pressing it again will display the current setpoint. Use the Up or Down buttons to change the display to the desired mode. Press Enter to accept the change. Factory setpoint 2 F.

Operating the CTC-1 (Continued) NOTE: The CO2 and Temp Dead-band settings should only be changed by experienced users. Dead-band is the maximum amount of deviation from the setpoint allowed. For example. the factory default for the Temp Dead-band is 2 F. Let s assume the unit is set to Cool mode, and the temperature is set at 78. When the temperature rises to 78, the cooling device will be activated. With a 2 degree F dead-band, the cooling device will continue to run until the temperature is reduced by 2 degrees, down to 76 degrees. Setting the Dead-band lower than 2 degrees will control the temperature more accurately, but it may also cause the cooling device to start and stop too often. Increasing the hysteresis will stop the rapid cycling On/Off of the control output. Restoring factory settings: If the user wants to quickly return the unit to the original settings, they can use the Restore Factory Settings button. Press the Restore Factory Settings button on the keypad. Keypad Test OK is displayed. Pressing it again will display the Restore Factory message. Press Enter to accept the change or the Clear / Back button to exit. Calibrating the CTC-1 Even though the CTC-1 has been designed for many years of trouble-free operation, occasional the need arises to re-calibrate the sensors. Recalibrating the unit will restore the sensors ability to accurately measure the Temperature and CO2 levels. NOTE: Recalibration of the CO2 sensor must be completed away from all animals and people OUTDOORS! Follow the procedure exactly. CO2 Calibration: The CO2 sensor has a lifetime of over 10 years. Over the life of the sensor however, dust and other contaminants can accumulate on the inner optical surfaces of the sensor cell itself. To adjust for the contamination, the calibration feature is provided. If the unit appears to not be measuring the CO2 levels correctly or if the unit has been dropped or jarred severely, you should recalibrate the unit. 1) Locate an area outdoors away from people, animals and high traffic areas. The unit must be shaded and NOT placed in direct sunlight. 2) Plug in the unit in and allow the unit to warm up for approximately 20 minutes. Note: Waiting longer (1+ hours) provides more accurate calibration. 3) Try not to exhale or breath on the unit while activating the calibration function. Once activated, leave the unit alone for 10 minutes. 4) To activate the automatic calibration sequence, press the CO2 Calibration button, the display will read Keypad Test OK. 5) Pressing the CO2 Calibration button again will display the new ambient CO2 level. (Factory set at Ambient 375 PPM) If the unit will be calibrated in an area of high vehicular traffic, or near people, a slightly higher calibration point should be selected. 6) The calibration level can be changed by using the UP and Down buttons. Only change this setting if you are sure the background (ambient) CO2 level is higher then normal atmospheric levels of 375 PPM. If you live in a highly populated city, you may increase the calibration level to 400-475 PPM. 7) Pressing Enter will start the calibration process. LEAVE THE UNIT ALONE! The process takes about 7-10 minutes. When complete, the display returns to normal operation. 8) The unit can now be returned to service.