Estates & Facilities Utilities Meters - Performance Specification

Similar documents
t-mac hardware a solution for all applications

Project Briefing Document. Section X Metering guide and specifications

QUICK-START EMU M-BUS CENTER ENGLISH

Mini Energy Web Server

INTRODUCTION - DISPLAYS, DATA LOGGERS AND SOFTWARE

WattmonMEGA Remote Monitoring & Control Platform

How to monitor M-Bus and wireless M-Bus systems

Version 1.0c May 6, 2010 ATK3

WE CONNECT REAL WORLD STRUCTURAL MONITORING SMART SENSORS SOFTWARE CLOUD WIRELESS INTERFACE TO THE

2 CLASS AMR READY INVONIC H DATA APPLICATION HEAT METERING. approved ULTRASOUND HEAT AND COOLING METERS DN15, DN20, DN25, DN40, DN50

Energy Client. Version Feb Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel:

M-Bus Central Unit. Use

1.2. All new meters will be one of the following meter forms: 2S for single-phase, and 9S for multi-phase.

Modbus Server - M-Bus (EN ) Gateway for the integration of M-BUS meters with Modbus RTU and TCP based control systems.

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

AB Axis Industries. Use

DISPLAYS, DATA LOGGERS AND SOFTWARE

VMU-C/Y, Em 2 CARLO GAVAZZI. The evolution in Energy Management. Monitoring system for Energy Management. A u t o m a t i o n C o m p o n e n t s

Measurement Systems Datascan Installation and User Guide

Flamma BIOMASS COMBUSTION SYSTEM CONTROLLER. Preliminary Description V.1 Santi Moroño / Jose Caldelas / Juan R. Regueiro / 26/02/ :34

User guide. SonoMeter 30. Ultrasonic energy meter for heating and cooling applications. Danfoss VUIGI102 1

ProData DATA LOGGER. Chapter 03 ProData data logger. Ethernet. Pulse inputs and Pulse outputs. Modbus-Ethernet gateway. Thermistor input.

Communication Interface

ProData data logger. Ethernet. Pulse inputs and Pulse outputs. Thermistor input. Modbus-Ethernet gateway. Memory 32 MB. Threshold value monitoring

Pembina Lake Erie Datalogger Requirements. Preliminary Specification

Web-enabled DAQ System

mark150s mark150/485s DDC controllers Summary

How to connect ABB Ethernet inverters with VSN700 Data Logger over Ethernet

Power and accuracy. Versatile. One display can monitor up to 32 measuring modules information

Meter Connection Manual V Solar-Log

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID

SonoSelect and SonoSafe energy meters

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

Smart Energy & Power Quality Solutions. ProData datalogger. Datalogger and Gateway

MID approval no. DE-08-MI004-PTB004 Date of release

ENERGY METER AND DATA MANAGEMENT

DIRIS Digiware Measurement and monitoring system for electrical installations multi-circuit plug & play

Using ECOpartner results in cost saving, energy savings, energy-use awareness, enhanced patterns of energy use, and conservation.

IN-LINE. vpinstruments.com

GE Intelligent Platforms PAC8000 RTU

M-Bus Master. Data sheet. MultiPort 250D/L

MIC-2 MKII, Multi-instrument DATA SHEET

M-Bus Master MultiPort 250D/L

AUDIN - 8, avenue de la malle Saint Brice Courcelles - Tel : Fax : Web : http:

Meter Bus. Intelligent Communication

DS 350/330 display and data logger

AP25-1DO METER (MID CERTIFIED) User Manual - Issue 1.0

OB735 Smart Energy Meter

AIAS. Technical description

POWERWISE INDAC SETUP MANUAL

MIC-2 Multi-instrument DATA SHEET

with Backlight Graphic LCD Screen

SB2WEB24. SB2WEB BACnet Controller. Benefits. Description

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

IntesisBox BACnet IP Server - M-Bus

Designed for commercial, residential and industrial applications, guarantee rapid installation with few and easy connections.

ECOWISE EM100 THE MULTI-FUNCTIONAL DEVICE SERVER

GEN II Wireless GSM/GPRS Data Acquisition System

KS5 SYNCHRONIZATION METER

Automation System TROVIS 5400 District Heating Controller TROVIS 5476

Smart Energy & Power Quality Solutions. ProData data logger. Data collection and recording

Hot pluggable communication modules

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

AEW Pulse Adapter. Building Technologies

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

ENERGY MANAGER INSTALLATION & USER GUIDE

Mercury Emissions Stack Monitor

Orbit 3 built on proven performance and reliability

A1700 CT Metering. The Power to Change...

H3G-TA ENGINEERING MANUAL

Pulse concentrator, 12 inputs, 4 mod. DIN, with RS485 port

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

Daikin HVAC Controls Guide Specification

METERSUK. SmartLink D Y N A M i T E. 3 MOD CT Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION.

IIM Warwick Court. Williamsburg VA REV 5

IDS 500 mobile Intelligent mobile chart recorder

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Dew point. Dew point set DS 400. Special features: Dew point set DS 400. Technical data DS 400. Technical data FA 410

Energy Web Server. Viale Borri 231, Varese - Italy. Cat. no: PM1WS255

84 kw, Tier 3, Direct Expansion, 937 ft 2

the easy solution for Smart Metering

Chart recorder. DS 500 mobile Intelligent mobile chart recorder

PN DN FIG. 660D-BATT+670D-BATT 661D-BATT+670D-BATT SISTEMI DI MISURA / SYSTEM MEASURE / SYSTEMES DE KAT KAT-06...

Documentation. M-Bus 130-mbx

Gateways & Energy Servers

BUILDING MANAGEMENT. OpenBAS-HV-NX10 SERIES CATALOG NUMBER. Description. Features

The SF-586b Insertion Flow Meter For Compressed Air, Gases And Exhaust Air (up to 400 C) In Pipe Diameters From 25mm to 5000mm

WM20. Power analyzer for three-phase systems. Benefits. Description

Product startup: G-30 + DIGIWARE C31 - U30-3xI35

NF770 Temperature Compensation Liquid Flow Computer

for M-Bus, Modbus and 1-Wire devices

SH2WEB24. Central unit module. Benefits. Description

ELECTRONIC CONTROLS & SENSORS. AK-SC255 Fact Sheet Version R Software Software version 02_085

CALEC energy master The benchmark in energy measurement

EEG CC1260 icap Interface Card

Webinar Energy Analyzer QA/S 3.x.1

4 Is this model available for special primary current and special primary voltage?

HEIDELBERG, SEPTEMBER 2018 EQmatic Energy Analyzer QA/S x.yy.1 M-Bus and Modbus. Jürgen Schilder Competence Center Europe Building Automation

PI 500 Hand-held instrument for industry

Econair. An advanced energy saving technology

Transcription:

Estates & Facilities Utilities s - Performance Specification Overview The specifications provided below are generic and not related to any specific manufacturer. The details included will support the evaluation of alternative models and include all parameters which may materially affect the ability of the equipment and its installation to provide the data required for effective metering. This specification is intended to provide consistency in the approach to utilities meter installations, to improve the ability to manage utilities consumption effectively and efficiently. In summary, the installed meters should provide MODBUS outputs and be hard-wired to a LAN point via a RS485 to gateway, where necessary or piggybacked on another suitable meter connected to the LAN point over via a suitable gateway device. In turn, data loggers will be connected to the LAN via an connection for the purpose of collating and transmitting all meter data. These data loggers will be addressable over the LAN. Historically, utilities consumption data has been sent to the BMS system, however this has proved an unreliable way of recording utilities data. Electrical metering The specification will cater for three key scenarios: 1. Building with existing whole building metering which includes telemetry. This should include a main meter at the building level in addition to sub-meters for individual circuits and/or equipment. The electrical meters should have MODBUS outputs as standard, though with the agreement of the Sustainability Team, they may also be of pulse output type, in which case a MODBUS gateway device would be required to convert pulse counts to MODBUS signal. The meter should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device, or piggybacked on another suitable meter connected to the LAN point over either directly or via a suitable gateway device. 2. Building without metering or with metering which does not have telemetry. In cases where there are no meters in a building or any existing meter has no Automatic Reading (AMR) device, steps must be taken to install one or more sub-meters on circuits with significant energy consumption or at a very minimum install a single meter to measure the total electrical consumption for that building. See electrical meter specification. All meters within the building should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device, or piggybacked on another suitable meter connected to the LAN point over either directly or via a suitable gateway device. See data logger specification. 3. Sub-metering of building areas or systems To sub-meter a stand-alone system or any areas within a building, an electric meter should be installed on the circuit feeding that area or system. An estimate of the maximum current on that circuit is required to size the Current Transformer (CT) (one on each phase). The output from the electrical sub-meter should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device, or piggybacked on another suitable meter connected to the LAN point over either directly or via a suitable gateway device. See electrical meter specification. Electrical Specifications The following performance parameters must be met for all electrical meters provided for energy management purposes. Support single or 3-Phase (3 or 4 wire) network Must provide at least one output as electricity consumption (Active Power kwh) measurement Support for MODBUS outputs. Pulsed output may be considered with prior agreement by the Sustainability Team, in which case they will require a MODBUS gateway. If pulse meter is selected, configurable pulse value and width Programmable current transformer ratios (support for up to 1000A/5) Display measurement (consumption kwh, Voltage and Current) Must meet Class 2 accuracy requirements of one of the following standards: o BS EN62053-21:2003 o BS 8431:2010 s must be capable of connection to a LAN point over or be accompanied by a suitable gateway device.

Data should be at least half hourly. Gas metering The specification will cater for three key scenarios: 1. Building with existing whole building metering which includes telemetry. In this scenario, the pulse output from the existing gas meter on the main feed to the building as well as other sub-meters, should be connected to the data logger in that building via a MODBUS gateway. The meter should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device capable of transmitting MODBUS data via a LAN point, or piggybacked on another suitable meter connected to the LAN point over via a suitable gateway. See gas meter specifications. 2. Building without metering or with metering which does not have telemetry. In a building where gas is supplied but no gas meters installed or the meters have no pulse outputs, then steps should be taken to ensure that at a very least a main gas meter is fitted on the main feed to the building. This main meter as well as other gas sub-meters in this building must be fitted with a pulse generator. For those older gas meters which do not support any kind of pulse generator, the options are; replace existing gas meter with a modern meter with pulse output (same max flow rate) or, a secondary gas meter with pulse output should be installed just downstream from the existing meter (same max flow rate). The pulse output from each gas meter should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device, or piggybacked on another suitable meter connected to the LAN point over either directly or via a suitable gateway device. See gas meter specifications. 3. Sub-metering of building areas or systems To sub-meter a stand-alone system or any areas within a building with significant gas consumption, a gas sub-meter (sized to match the max flow rate) should be installed on the feed pipe to that area or the system. Any gas sub-meter fitted for this purpose must have a pulse output which should be connected to the LAN and associated with a data logger, either directly or via a suitable gateway device, or piggybacked on another suitable meter connected to the LAN point over either directly or via a suitable gateway device. See gas meter specifications. Gas Specifications The following performance parameters must be met for all gas meters provided for energy management purposes. Diaphragm meters flow rate of up to 60 m 3 per hour Rotary displacement meter flow rate 25 to 1000 m 3 per hour Turbine meter flow rate 80 to 1600 m 3 per hour Pulse output ( 1 pulse = 0.01, 0.1, 1.0 m 3 /h) Must meet the accuracy requirements of one of the following standards: o BS EN1359:1999 Gas s - Diaphragm gas meters o BS EN12480:2002 Gas s - Rotary displacement gas meters o BS EN12261:2002 Gas s - Turbine gas meters s must be capable of connection to a LAN point over or be accompanied by a suitable gateway device. Data should be at least half hourly.

Heat (energy) metering Where a building/area is supplied with heat rather than gas, heat meters will be required, which should comply with the following performance standards: Heat meters shall meet the Class 2 requirements in Annex MI-004 of the EU Measuring Instruments Directive (MID) 2004 and shall consist of: o a flow sensor (or meter) rated for continuous flows and suitable for the anticipated flow and return temperatures o a matched pair of temperature sensors (such as two thermocouples) the two temperature sensors shall have been calibrated together as a pair to make sure the temperature difference between the input and output of the system is measured to the stated accuracy level, and; o a calculator/digital integrator the integrator shall be provided with MODBUS output, capable of connection to a LAN point over or be accompanied by a suitable gateway device or piggybacked on another suitable meter connected to the LAN point over and associated with a data logger via a suitable gateway device. Digital integrators shall have an integral display which allows recorded parameters to be viewed locally. Digital integrators shall also be provided with MODBUS outputs, capable of connection to a LAN point over or be accompanied by a suitable gateway device. Data should be at least half hourly. Flow meters being provided in new installations shall in all cases be fitted within pipework rather than being clamp on types. Where flow meters are fitted to existing installations, clamp on types may be acceptable if agreed with the Sustainability Team prior to installation. In all cases, flow meters shall be sized to ensure all flows (including periods of low volume flows) will be captured accurately. In particular, flow meters shall be installed within pipework such that they are a suitable distance from fittings (such as bends, junctions and so on) to prevent excessively turbulent flow and oriented to ensure correct operation. The installation shall be in full accordance with the manufacturer s installation instructions. In every case, the heat meter installation shall be capable of recording and transmitting the following data at a minimum regularity of every 30 minutes: Heat (energy) consumed (kwh) Flow temperature Return temperature Flow rate (m 3 /hr)

Water metering The specification will cater for three key scenarios: 1. Building with existing whole building metering which includes telemetry. In this scenario, the pulse output from the existing water meter on the main feed to the building as well as other sub-meters, should be connected, via a MODBUS gateway to the LAN point over and associated with a data logger via either a suitable gateway device or piggybacked on another suitable meter connected to the LAN point over via a suitable gateway device. 2. Building without metering or with metering which does not have telemetry. In a building where water is supplied but no water meters installed or the meters have no pulse outputs, then steps should be taken to ensure that at a very least a main water meter is fitted on the main feed to the building. This main meter as well as other water sub-meters in this building must be fitted with a pulse generator. For those older water meters which do not support any kind of pulse generator, the options are; replace existing water meter with a modern meter with pulse output (same max flow rate) or, a secondary water meter with pulse output should be installed just downstream from the existing meter (same max flow rate). The pulse output from each water meter should be connected, via a MODBUS gateway to the LAN point over and associated with a data logger via either a suitable gateway device or piggybacked on another suitable meter connected to the LAN point over via a suitable gateway device. 3. Sub-metering of building areas or systems To sub-meter a stand-alone system or any areas within a building with significant water consumption, a water sub-meter (sized to match the max flow rate) should be installed on the feed pipe to that area or the system. Any water sub-meter fitted for this purpose must have a pulse output which should be wired via a MODBUS gateway to the LAN point over and to a data logger via either a suitable gateway device or piggybacked on another suitable meter connected to the LAN point over via a suitable gateway device. Data loggers The following performance parameters must be met for all data loggers provided. Data loggers should be connected directly to the LAN and should have sufficient port capacity to service the installed meter points and provide capacity to limit the number of installed data loggers. RJ45 output for connection to local ICT network Internal clock with date/time stamp Internal memory for storage of data samples Battery backup for memory storage Optional Pulse and Analogue input channels Data upload to server every 30 minutes Interrogation of meters over LAN at least every 30 minutes Open source outputs not restricted to use with specific software

Building A (with as well as meters) Belden () - Converter Belden () - Converter Generic UoR ing Schematic Drawn by: William Box, Carnego Systems Version: 3 Date : 9 th May 2014 UoR IT Network / Internet Database (internal or external) over IP Gateway Master Device Optional 2 nd i/f Building B (with wireless link to remote meter) VLAN over IP Gateway Building C (remote meter) Wireless Device Building wireless protocol (e.g. Zigbee) not WiFi Wireless Device

Building A This shows a generic building with a mixture of and metering equipment. A meter can be electricity, gas, heat etc. These can be mixed as required / convenient for the project. meter outputs are converted to using the device shown in BLUE. These devices can support multiple devices on daisy-chained bus wiring. The recommended devices is the RESI--MODBUS. The devices can either support up to 8 devices or 24 devices. This must be specified at the time of ordering. meters (together with the to converters) are supported in a daisy-chain arrangement into the Over IP Gateway device shown in orange. The recommended device is Perle IOLAN SDS2. This device has two input ports and can therefore support two separate chains of meters / converters as shown in the schematic. There is no requirement to split meters over the two ports (subject the limitations set out below) but is shown in the diagram as it may be convenient either due to the physical layout of the meters in the building or project structure. (For example, if a building has meters for both the main electrical metering project and the new heating system then using separate ports for each project may be useful in providing a clear demarcation point.) Each Over IP Gateway can support a large number of devices (theorectically up 248) as long as the communication settings are set on each device correctly (see point c) under Configuration to provide the required level of data throughput. Building B This shows a building with a mix of and meters together with a wireless link to a remote building. Building C This shows a remote site connected back to building B with a wireless link. Configuration a) Static IP address information (IP address, subnet mask, host name) for each Over IP gateway must be provided in advance by UoR ITS and the VLAN configured correctly on their network switches to the correct physical ethernet port. The IP pathway should be checked via a ping to the master device using a known device before connecting the Over IP gateway. b) daisy-chain cabling should be terminated in the last device in the chain to standards. c) All meters must be correct configured with communication settings (baud rate, parity, bit structure etc.) and the settings recorded. The highest possible common baud rate across all of the connected devices should be used. d) All meters connected through a single Over IP gateway must have unique / addresses correctly configured and recorded. e) Any to converters must be correctly configured and a backup taken. f) All Over IP gateway devices must be correctly configured and a backup taken. g) Modus / cabling connection to devices must observed the correct polarity o these interfaces. h) While the specification supports a large number of device addresses (>100) some devices will only allow a certain range to be set on the device. (e.g. some meters only allow 1 9). Care must be taken to ensure that all devices in a building can be assigned addresses in line with d) above. If this is not possible then an additional gateway device may be required. i) The central master can support a large number of devices and metering points. If required the central master can be upgraded etc. without any impact on the configuration of equipment within the buildings / plant rooms.