E1 Plus Electronic Overload Relay

Similar documents
Power Meter PowerMonitor 500

E1 Plus Overload Relay Specifications

PRODUCT PROFILE BULLETIN 193 & 592 E1 PLUS ELECTRONIC OVER LOAD RELAYS

I/O Modules with EtherNet/IP Architecture

Programmable Logic Controllers Micro850

PanelView 5500 Operator Interface. 7-inch to 19-inch Displays

Motor protection relays

Bulletin 817 Thermistor Protection Relay

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

02/11/2015

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

K1B004TLH cam switch - 1 pole A - screw mounting

RPM13F7 power plug-in relay - Zelio RPM - 1 C/O V AC - 15 A - with LED

K1D012ULH cam changeover switch - 2-pole A - screw mounting

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

Motor Protection Solutions. Bulletins 193, 592, 809S, 813S, 814S, 817S and 825-P

K1C024B body for BCD encoded output switch - 1 pole A - for Ø 22 mm

K1D004ACH cam switch - 4-pole A - for Ø 22 mm

XCKS141H29 limit switch XCKS - th.plastic roller lever var. length - 1NC+1NO - snap - M20

RM35LM33MW liquid level control relay RM35-L V AC/DC

K1D011B body for BCD encoded output switch - 1 pole A - for Ø 22 mm

K1F003MCH cam ammeter switch - 3 circuits A - for Ø 22 mm

K1F037MCH cam voltmeter switch - 3L and 3L-N A - for Ø 22 mm

RXM4AB3BD Miniature Plug-in relay - Zelio RXM 4 C/O 24 V DC 6 A with LED

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

PowerFlex 400 AC Drive Guide Specification

K1K015NZ4 cam stepping switch - 2-pole A - screw mounting

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

PGR-3200 MANUAL INSULATION MONITOR

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

Electronic Motor Protection Relays Bulletin 193-E

STBEHC3020KC counter kit STB - 1 CH Hz - 2 I

RXM4AB1MD Miniature Plug-in relay - Zelio RXM 4 C/O 220 V DC 6 A

XCKS131 limit switch XCKS - thermoplastic roller lever - 1NC+1NO - snap action - Pg13

XCKN2118G11 limit switch XCKN - thermoplastic roller lever - 1NC+1NO - snap - Pg11

TeSys IEC Contactors and Overload Relays

K1F006ALH cam switch - 6-pole A - screw mounting

XCKJ10511 limit switch XCKJ - thermoplastic roller lever - 1NC+1NO - snap action - Pg13

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

Zener Barriers Bulletin 937Z

XCKP2110G11 limit switch XCKP - metal end plunger - 1NC+1NO - snap - Pg11

RPM42P7 power plug-in relay - Zelio RPM - 4 C/O V AC - 15 A - with LED

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

XCKJ10541H29 limit switch XCKJ - th.plastic roller lever var. length - 1NC+1NO - snap - M20

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

XCKM102 limit switch XCKM - steel roller plunger - 1NC +1NO - snap action - Pg11

XCKN2110P20 limit switch XCKN - metal end plunger - 1NC +1NO - snap - M20

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

XCMN2102L2 limit switch XCMN - steel roller plunger - 1NC +1NO - snap - 2 m

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

XCKJ10541H29 limit switch XCKJ - th.plastic roller lever var. length - 1NC+1NO - snap - M20

SECTION ( ) LIGHTING CONTROL PANELBOARD

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

Bulletin 825-P Modular Protection System

RE9RA21MW7 off-delay timing relay s V AC -

Power Quality Monitor PowerMonitor 5000 M8

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

ZB5FG09 flush mounted selector switch head key pos stay put

Rated operational Control Voltage Uc Supply Voltage Connection Rated operational current 40 C voltage Ue Us 25A AC-53a 32A AC-53a

RM35TF V AC

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI

Data sheet ACT20P ACT20P-CMT-10-AO-RC-S. Phone: Fax: Web: - [!

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

Long-time range model (0.1 min to 10 h) 24 VAC; SPDT H3RN-1 H3RN-11 12, 24 VDC DPST-NO H3RN-2 H3RN-21

Ordering Key. Type Rated Operational Rated operational Control Voltage Uc Options

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

XCKP2110N12 limit switch XCKP - metal end plunger - 1NC +1NO - snap - 1/2NPT

1510 MOTOR CONTROLLERS

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

Line A. Inverse parallel scrs. Load a FUSION. Line B SCR POWER. O delta CONTROLLERS. Line c. inverse parallel scrs. Load C. FUSION Brochure Rev 3.

Mini Contactors & Overloads

RSB1A160JD interface plug-in relay - Zelio RSB - 1 C/O - 12 V DC - 16 A

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

RE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

CompactBlock Guard I/O EtherNet/IP Safety Modules

PanelView Plus/VersaView CE Terminals and Display Modules

XCKL115 limit switch XCKL - thermoplastic roller lever - 1NC+1NO - snap - Cable gland

NF44E-.. / NFZ44E-.. Contactor Relays AC / DC Operated - with Screw Terminals

XCKJ10559H7 limit switch XCKJ - thermoplastic round rod lever 6 mm - 1NC+1NO - snap - 1/2NPT

XCMD2110L1 limit switch XCMD - metal end plunger - 1NC +1NO - snap - 1 m

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Digital ac/dc (24V) Input Module

Transcription:

ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION E1 Plus NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific installations have specific requirements, and does not recommend or intend any specific application based solely upon the guidelines provided here. Because of the variety of uses for this information, the user of, and those responsible for applying this information, are responsible for ensuring the acceptability of each application and appropriate use of the guidelines. In no event will be liable for misuse, misapplication or reliance on these guidelines in connection with any specific application. also disclaims indirect or consequential damages resulting from the use or application of this information. Note: To download or view a.doc file version of this procurement specification, please visit: www.rockwellautomation.com/industries/procurement-specifications 193-SR002-EN-P 1

TABLE OF CONTENTS PART 1 GENERAL... 3 1.01 QUALIFICATIONS... 3 1.02 REFERENCES... 3 1.03 ENVIRONMENTAL REQUIREMENTS... 4 1.04 PRE-MANUFACTURE SUBMITTALS... 4 1.05 FINAL SUBMITTALS... 4 PART 2 PRODUCTS... 5 2.01 RATINGS... 5 2.02 CONSTRUCTION... 6 2.03 OVERLOAD RELAY... 6 2.04 OPTIONAL PROTECTIVE, REMOTE RESET AND COMMUNICATION MODULES (LIMIT 1)... 7 2.05 ACCESSORIES... 12 PART 3 EXECUTION... 13 3.01 DELIVERY, STORAGE, AND HANDLING... 13 3.02 INSTALLATION... 13 3.03 SPARE MATERIALS... 13 3.04 WARRANTY... 13 2 193-SR002-EN-P

PART 1 GENERAL 1.01 QUALIFICATIONS A. Manufacturer 1. The manufacturer shall have a minimum of 25 years of experience in the manufacture of electronic overload relays. 2. The approved manufacturers are: B. Support a) Allen-Bradley b) Substitutions: None permitted 1. The manufacturer shall maintain factory trained and authorized service facilities within 100 miles of the project and shall have a demonstrated record of service for at least the previous ten years. 2. Support personnel are to be direct employees of the manufacturer and be available 24 hours per day through a toll-free number. 3. The manufacturer shall provide all required start-up and training services. 4. The approved manufacturers are: C. Certification a) Customer Support & Maintenance b) Substitutions: None permitted 1. To ensure all quality and corrective action procedures are documented and implemented, all manufacturing locations shall be certified to the ISO-9001 Series of Quality Standards. 2. Third-party manufacturers and brand labeling shall not be allowed. 1.02 REFERENCES A. The electronic overload relay shall be certified: 1. CE 2. culus Listed 3. C-Tick 4. CCC B. The following standards shall be met: 1. EN 60947-4-1 2. EN 60947-5-1 3. UL508 4. CSA C22.2 No. 14 (cul) 5. NEMA ICS 2-1993 Part 4 C. Terminal markings shall comply with CENELEC and EN 50012. 193-SR002-EN-P 3

1.03 ENVIRONMENTAL REQUIREMENTS A. The supplier shall confirm specified service conditions during and after installation of products. B. The supplier shall maintain the area free of dirt and dust during and after installation of products. 1.04 PRE-MANUFACTURE SUBMITTALS A. Refer to Section for submittal procedures. B. Product Data 1. Publications on electronic overload relay. 2. Data sheets on the expansion module and accessories, when applicable. C. Specification Response 1. Detailed response to this specification showing where in the literature each requirement is satisfied. 2. Clearly identified clarifications and exceptions. D. Installation Instructions 1. A copy of the manufacturer s installation instructions, including receiving, handling and storage instructions. E. Testing and Test Reports 1. Testing per manufacturer s standard. 2. A copy of the test reports, if available, shall be provided as part of the final documentation. 1.05 FINAL SUBMITTALS A. Refer to Section for procedure on submittal of final documentation. B. Supplier Certification 1. The supplier shall provide certification that the electronic overload relay has been installed in accordance with the manufacturer s instructions. 2. The supplier shall provide certification that the electronic overload relay settings have been properly adjusted. C. Final Drawings 1. The manufacturer shall provide final drawings reflecting the As-Shipped state of the installed equipment. 2. Manufacturer drawings shall be provided in DWG format. 3. Manufacturer drawings do not need to be stamped if a drawing schedule is provided that lists the drawing numbers, revision levels, and status of drawings (Preliminary, Approval, Final, etc.) 4. The supplier shall be responsible for making any changes to the As-Shipped drawings from the manufacturer to reflect any field modifications. 4 193-SR002-EN-P

D. Maintenance Data 1. Electronic overload relay installation instructions and User Manual. 2. Field service report from start-up service. 3. Name and phone number for a local distributor for the spare parts. PART 2 PRODUCTS 2.01 RATINGS A. The electronic overload relay shall have a current operating range of: 1. 0.1 to 600 A (for NEMA models) 2. 0.1 to 800 A (for IEC selectable motor protection models) 3. 0.1 to 45 A (for IEC fixed motor protection models) B. All relay contacts shall be rated AC15/B600. C. The electronic overload relay main circuits shall be rated: Insulation Voltage (Ui) 690 VAC [or 1000 VAC, D contactor models] Impulse Strength (Uimp) 6 kv AC Operating Voltage (Ue) IEC/UL 690 VAC/600 VAC [or 1000 VAC/600 VAC, D contactor models] Operating Frequency 50/60 Hz (sinusoidal) A. The electronic overload relay control circuits shall be rated: Insulation Voltage (Ui) Impulse Strength (Uimp) Operating Voltage (Ue) IEC/UL Operating Current (I e) 690 VAC 6 kv AC 690 VAC/600 VAC N.O./N.C. 12 120V 3/2 220 240V 1.5/1.5 380 480V 0.75/0.75 500 600V 0.6/0.6 Thermal Current (I the) 5 A Contact Reliability 17V, 5 ma B. Environmental Specifications The electronic overload relay shall be: 1. Capable of operating in an environment with a relative humidity range of 0 to 95%, non-condensing. 2. Able to withstand a shock of 30 G (per IEC 68-2-27). 3. Able to operate without disruption for vibration levels up to 3 G (per IEC 68-2-6). 4. Able to operate without de-rating to an elevation of 2000 m. 5. Rated for an operating environment of -20 to +60 C (-4 to +140 F). 6. Rated for application in Pollution Degree 3 environments. 193-SR002-EN-P 5

2.02 CONSTRUCTION A. The electronic overload relay shall be a self-powered, low energy consumption (150 mw) device and shall consist of: 1. Overload relay 2. One side-mount expansion module (optional) 3. Accessories (optional) B. The electronic overload relay shall be direct mounting style or compact, pass-through style with integrated DIN rail and panel mount. The direct mounting style shall be capable of being separate-mounted through a DIN rail/panel mount adapter accessory. 2.03 OVERLOAD RELAY A. The electronic overload relay shall be NEMA or IEC configuration, providing current measurement-based protection. 1. Motor current shall be monitored through 3 integral current transformers, secured separately in the housing, that power the overload protection circuitry. 2. Performance of the electronic overload relay shall not be impacted by ambient temperature over the specified temperature operating range. B. The electronic overload relay shall perform thermal modeling electronically with precision solid-state components and shall have: 1. An application-specific integrated circuit (ASIC), which continually processes motor current data to accurately maintain the time-current status of the motor thermal capacity utilization value. 2. A thermal memory circuit, which allows the relay to model the heating and cooling effects of motor on and off periods, ensuring accurate protection of both hot and cold motors. 3. A separate phase loss detection circuit, which allows the relay to quickly respond to phase loss conditions, typically within 3 seconds. C. The electronic overload relay s trip class shall be: 1. Fixed Trip Class 10, or, 2. Selectable Trip Class 10, 15, 20 or 30, through means of a DIP switch setting. D. The electronic overload relay s reset mode shall be: 1. Manual, or, 2. Selectable Manual/Automatic, through means of a DIP switch setting. E. The face of the electronic overload relay shall provide: 1. A potentiometer that can be set to a wide 5:1 adjustment range. 2. A trip indicator flag for visual trip status indication. 3. A reset button. 4. A test button that momentarily actuates the N.C. contact. 5. A mechanical trip cam for operating both sets of contacts. 6 193-SR002-EN-P

F. Electrical connections: 1. The electronic overload relay shall work with three-phase or single-phase applications. 2. The electronic overload relay shall be capable of direct connection and mounting to contactors in low voltage applications. 3. The electronic overload relay shall provide 1 N.O. and 1 N.C. isolated auxiliary contacts. The isolated configuration allows them to be applied in circuits operating at different voltage levels and without polarity restrictions. 4. The electronic overload relay shall have line-side over-molded connections. 5. Wiring terminals shall provide IP20 finger protection. 2.04 OPTIONAL PROTECTIVE, REMOTE RESET AND COMMUNICATION MODULES (LIMIT 1) A. Remote Reset Module Power at U e 24 VAC Impulse Withstand Voltage 300V 24 to /VDC, 50/60 Hz 1.0 W 2.5 kv 2. The remote reset module shall provide remote reset of the electronic overload relay after a trip occurs. 18 mm to the overall width. B. Jam Protection Module with Remote Reset Power at U e 24 VAC Impulse Withstand Voltage 300V 24 to /VDC, 50/60 Hz 0.3 W 0.3 W 0.5 W 2.5 kv 2. The jam protection module with remote reset shall provide flexible jam protection. 18 mm to the overall width. 3. The jam protection module with remote reset shall provide front-accessible DIP switches that offer jam protection settings to match application requirements. 193-SR002-EN-P 7

a) Enabling/disabling of jam protection function and remote reset operation. b) Jam trip level settings at 150%, 200%, 300% and 400% of full load current setting. c) Trip delay settings of 1/2, 1, 2 and 4 seconds to minimize nuisance tripping. C. Ground Fault Protection Module with Remote Reset Power at U e 24 VAC Impulse Withstand Voltage 300V 24 to /VDC, 50/60 Hz 1.0 W 2.5 kv 2. The ground fault protection module with remote reset shall provide flexible ground fault protection. 18 mm to the overall width. 3. The ground fault protection module with remote reset shall provide front-accessible DIP switches that offer ground fault protection settings to match application requirements. a) Enabling/disabling of ground fault protection function and remote reset operation. b) Ground fault trip level settings in 4 ranges: 20 to 100 ma (resistive loads); 100 to 500 ma; 0.2 to 1 A; 1 to 5 A. Within each range, specific percentages of maximum ground fault can be set. c) Trip delay fixed at 50 ms ± 20 ms. D. Ground Fault/Jam Protection Module with Remote Reset Insulation Voltage (Ui) Operating Voltage (Ue) Power at Ue 24 VAC Impulse Withstand Voltage 300V 24 to /VDC, 50/60 Hz 1.0 W 2.5 kv 2. The ground fault/jam protection module with remote reset shall provide flexible ground fault and jam protection. 18 mm to the overall width. 8 193-SR002-EN-P

3. The ground fault/jam protection module with remote reset shall provide frontaccessible DIP switches that offer ground fault and jam protection settings to match application requirements. a) Enabling/disabling of ground fault protection and jam protection functions and remote reset operation. b) Ground fault trip level settings in 4 ranges: 20 to 100 ma (resistive loads); 100 to 500 ma; 0.2 to 1 A; 1 to 5 A. Within each range, specific percentages of maximum ground fault can be set. c) Ground fault trip delay fixed at 50 ms ± 20 ms. d) Jam protection fixed at 400% of full load current setting with a 0.5 second trip delay. E. PTC Module with Remote Reset Insulation Voltage (Ui) Operating Voltage (Ue) Power at Ue 24 VAC Impulse Withstand Voltage 300V 24 to /VDC, 50/60 Hz 1.0 W 2.5 kv 2. The PTC module with remote reset shall provide enhanced motor protection based on actual temperature. 18 mm to the overall width. 3. The PTC module with remote reset shall provide 2 terminals for the connection of positive temperature coefficient (PTC) thermistor sensors. a) PTC sensors shall be able to directly monitor the temperature of motor stator windings. b) Conditions such as obstructed cooling and high ambient temperature shall be addressed. F. EtherNet/IP and Protection Module 1. Power Supply Ratings Supply Voltage (Us) 24 VDC Operating Range (Ue) 20.4 to 26.4V Supply Current (I e) 0.11 A Max Surge @ Power-Up 2.5 A Max Power Consumption 2.7 W 2. Output Relay Ratings: Thermal Current (I the) 5 A 300 VAC 193-SR002-EN-P 9

Operating Current (I e) 240V 110 VDC 220 VDC Minimum Operating Current Designation/Utiliz. Category 3 A 1.5 A 0.25 A 0.1 A 10 ma at 5 VDC B300/AC15 3. The EtherNet/IP and protection module shall provide seamless control and direct access to motor performance and diagnostic data on an Ethernet-based network. 22 mm to the overall width. 4. The EtherNet/IP and protection module shall enhance communication. a) Supports I/O and explicit messaging for data access by a PAC and contains compatible tags for direct software access. b) Has integrated web and email server so information can be read and parameters can be configured via a web browser. c) Uses a simple mail transfer protocol (SMTP) to send email or text messages in the event of a warning or trip condition. 5. The EtherNet/IP and protection module shall include integrated I/O: 2 inputs, 1 output. 6. The EtherNet/IP and protection module shall provide operational and diagnostic data: a) Average motor current b) Percentage of thermal capacity usage c) Device status d) Trip and warning identification e) Trip history (5 previous trips) 7. The EtherNet/IP and protection module shall expand protective functions: a) Overload warning b) Jam protection c) Underload warning G. PROFIBUS and Protection Module 1. Power Supply Ratings Supply Voltage (Us) 24 VDC Operating Range (Ue) 20.4 to 26.4V Supply Current (I e) 0.11 A Max Surge @ Power-Up 2.5 A Max Power Consumption 2.7 W 10 193-SR002-EN-P

2. Output Relay Ratings: Thermal Current (I the) Operating Current (I e) 240V 110 VDC 220 VDC Minimum Operating Current Designation/Utiliz. Category 5 A 300 VAC 3 A 1.5 A 0.25 A 0.1 A 10 ma at 5 VDC B300/AC15 3. The PROFIBUS and protection module shall provide seamless control and direct access to motor performance and diagnostic data on a field bus-based network. 22 mm to the overall width. 4. The PROFIBUS and protection module shall support both PROFIBUS DP-V0 and DP-V1. 5. The PROFIBUS and protection module shall include integrated I/O: 2 inputs, 1 output. 6. The PROFIBUS and protection module shall provide operational and diagnostic data: a) Average motor current b) Percentage of thermal capacity usage c) Device status d) Trip and warning identification e) Trip history (5 previous trips) 7. The PROFIBUS and protection module shall expand protective functions: a) Overload warning b) Jam protection c) Underload warning H. DeviceNet and Protection Module Terminals 13 & 14 Terminals 1, 2, 3 DeviceNet Terminals Terminals 13 & 14 Terminals 1, 2, 3 DeviceNet Terminals Power at U e 24 VDC 300 VAC 30 VDC 30 VDC 250 VAC 24 VDC 24 VDC 2.0 W 193-SR002-EN-P 11

Impulse Withstand Voltage Designation 2.5 kv B300 2. The DeviceNet and protection module shall provide seamless deployment of motor starters onto the Integrated Architecture. 18 mm to the overall width. 3. The DeviceNet and protection module shall enhance communication. a) ODVA tested b) Unconnected Message Manager (UCMM) support c) Get/set single attribute explicit messaging d) Autobaud network rate detection 4. The DeviceNet and protection module shall include integrated I/O: 2 inputs, 1 output. 5. The DeviceNet and protection module shall provide operational and diagnostic data: a) Average motor current b) Percentage of thermal capacity usage c) Device status d) Trip and warning identification e) Trip history (5 previous trips) 6. The DeviceNet and protection module shall expand protective functions: a) Overload warning b) Jam protection c) Underload warning I. Remote Indication Display Degree of Protection 300V 24 VDC IP 65/66 (Type 4/4X/12/13) 2. The remote indication display shall display the status of the electronic overload relay from the front of a panel. 2.05 ACCESSORIES a) Features status indicators and a reset button. b) Mounts in a standard 22 mm push button cutout. A. A DIN rail/panel adapter shall be available from the manufacturer for separate mounting of direct mounting style models. B. A current adjustment shield shall be available from the manufacturer to provide protection from inadvertent adjustment of the FLA setting. 12 193-SR002-EN-P

C. External reset buttons and adapters shall be available from the manufacturer for enclosed applications. D. A core balanced ground fault sensor shall be available from the manufacturer for use with the ground fault modules. PART 3 EXECUTION 3.01 DELIVERY, STORAGE, AND HANDLING A. The supplier shall coordinate the shipping of equipment. B. The supplier shall store the equipment in a clean and dry space. C. The supplier shall protect the units from dirt, water, construction debris and traffic. 3.02 INSTALLATION A. The supplier shall verify all electronic overload relay settings have been properly adjusted prior to energizing. B. The supplier shall ensure accessibility to diagnostic lights, communication ports and optional modules. These components shall be free from obstruction at all times. 3.03 SPARE MATERIALS A. Provide one (1) spare overload relay of each size utilized, including options. 3.04 WARRANTY A. The manufacturer shall provide their standard parts warranty for eighteen (18) months from the date of shipment or twelve (12) months from the date of being energized, whichever occurs first. B. The manufacturer shall confirm this warranty as part of the submittal. END OF SECTION, Rockwell Software, Allen-Bradley, are trademarks of, Inc. Trademarks not belonging to are property of their respective companies. 193-SR002-EN-P 13