Honeywell Trendview Recorder & Acromag 967EN Modbus/TCP Module as Remote I/O

Similar documents
Honeywell HC-900 with Acromag 967EN Modbus/TCP Module as Remote I/O

X Series Application Note 34 Using Acromag 967 Modbus/TCP module as Remote I-O with the X-Series Recorder

X-Series Recorder Application Note OneWireless R200 Modbus Interface

Interfacing Acromag Ethernet I/O Modules to an ABB AC500 PLC with Modbus TCP/IP

X-Series Application Note 41 Remote Wireless Data Acquisition

Application Note Modbus/TCP

Configuring LabVIEW 2009 to Communicate with Acromag Busworks and Etherstax Modbus I/O Modules via an OPC Server

Knowledge Base Article. Facility Monitoring & Automation. Using a ISONAS PowerNet and a Acromag Modbus/TCP Module

Paperless Recorders & Data Acquisition Solutions SEE, STORE, SEND DATA SECURELY. Honeywell Solutions for Data Acquisition and Batch Recording

How to Build a Rugged COM Express System

900EN Series. Acromag RUN ST DIO STATUS ACT LINK DFT RST ETHERNET TB1

Communicating To Acromag Series 9xxEN-6xxx Ethernet Modules In An Allen Bradley CLX5555 Control System

Configuring LabVIEW for Communications with Acromag Busworks Modbus I/O Modules via an OPC Server

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

ezeio Controller and the 2400-A16 input expansion.

Communicating To Acromag Series 9xxEN-60xx Ethernet Modules From Legacy Allen Bradley or Rockwell Automation Devices

P2 Configuration Guide

Communicating To Acromag Series 9xxEN-6xxx and XTxxx2-xxx Ethernet Modules In An Allen Bradley ControlLogix System

PWR. Power Module Slots

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

SP Series Signal Splitters

HRM-0800 Instruction Manual

TrendView Credits Option Code Instruction Sheet

Intrinsically Safe Temperature Concentrator System

HI 6600 series Quick Start Guide

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series

R6-NE1 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL ETHERNET INTERFACE MODULE MODEL. (Modbus/TCP, for 32-point analog signals)

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020

Write Message to Trendview recorder via Modbus. Dan Weise, Lesman Instrument Co rev2a

AW Flow Meters HART Summary for RT-Ex15

PC CONFIGURATOR Model: 27HUCFG. Users Manual , Minamitsumori, Nishinari-ku, Osaka JAPAN Tel: Fax:

R3-GE1 BEFORE USE... INSTALLATION POINTS OF CAUTION INSTRUCTION MANUAL ETHERNET INTERFACE MODULE MODEL. (Modbus/TCP)

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

Configuration Software Manual

Paperless Recorders and Data Acquisition Solutions

Paperless Recorders and Data Acquisition Solutions

info.txt Acromag, Inc S.Wixom Road P.O. Box 437 Wixom, Michigan Phone: (248) FAX: (248)

CII: Current Input, Isolated

THM501 PT100 MODBUS TEMPERATURE TRANSMITTER

Product Brochure PMA KS Multi-function Controller.

HI 6600 series Quick Start Guide

Isolated, Process Current Output 7B39 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Micro-Modular Programmable Controller

Modbus TCP/IP Option Instruction Manual

West Instruments. The MLC compact multi-loop controller... MLC ends the control or integration compromise

HART. Actuator Control. Redefining Flow Control

Using the MODBUS Protocol with Athena Series C (1ZC, 16C, 18C, and 25C) Controllers

Remote I/O Modules EH-RIO2 Series

eztrend QXe eztrend QXe Features Typical Applications Description Representative photograph, actual product appearance may vary.

SE-330 SERIES (NEW REVISION) MODBUS/TCP INTERFACE

Temperature-Humidity Sensor Configuration Tool Rev. A 1/25/

Using the WAGO as Remote I/O with an Omron SYSMAC CJ2 Series PLC. Application note. A116700, English Version 1.1.0

4.6 PT8AIIS ISOLATED ANALOG CURRENT INPUTS Description

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

Trident and Trident X2 Digital Process and Temperature Panel Meter

/8 DIN Universal Process Indicator

Operating a Power Xpert C445 Global Motor Management Relay with a Rockwell PLC via Ethernet/IP

Commissioning Benefits

For 2-wire Universal Temperature Transmitter B6U. PC CONFIGURATOR Model: B6UCFG. Users Manual

Trident & Trident X2 PD765

Plus-X 600. Installation and Operation Manual

Isolated Process Current Input with Loop Power 7B35

Flammable Gas Smart Sensing Module

Operating a PowerXL DC1/DE1 Drive with a Rockwell PLC on Ethernet/IP

Cube20. Application-oriented. Installation-friendly. Efficient

Isolated Process Current Input 7B32 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

HART UNIVERSAL TEMPERATURE TRANSMITTER

Model B3HU. PC CONFIGURATOR Model: B3HUCFG. Users Manual

MODCELL 2050R Single Loop Controllers

Application Note. Configuring a Phoenix Bus Coupler to communicate Modbus/TCP with an MPiec Controller

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

MOD-MUX MODBUS TCP I/O PRODUCTS

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

KL4001, KL4002 and KL4004

PIECAL CALIBRATORS. Milliamp Thermocouple RTD Voltage Frequency.

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

4110 HART Level Encoder

Isolated Voltage Input 7B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

BL67 electronic module 4 analog inputs for current/voltage BL67-4AI-V/I

Gateway 1400 Reference Manual

Serial Connection of HC900 Hybrid Controller to 900CS Control Station

- SELF-TUNING PID ALGORITHM - INTUITIVE COLOR DISPLAY WITH TEXT MESSAGING - UNIVERSAL PROCESS AND TC/RTD INPUTS - MULTI- FUNCTION RAMP- DWELL/PROCESS

ADAM-5511 Quick Start

Supply Voltage V dc Supply is fully isolated internally, and protected against transients. Internal power modules are CE certified.

HART UNIVERSAL TEMPERATURE TRANSMITTER

SMART / INTELLIGENT TRANSMITTERS AND ACTUATORS

SP Series Signal Splitters

Wall-/Pipe Mounted Universal Process Indicator

TEMPERATURE CALIBRATOR TC305

Precision Digital Modbus Register Tables Serial Communication

LAUREL ELECTRONICS, INC.

Smart Energy & Power Quality Solutions. ProData datalogger. Datalogger and Gateway

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

Modbus Communications Board

microblox I/O Modules w/ Bluetooth Wireless Technology Introduction to the microblox Module Family

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM100(1402)

GFC111-MB. Flow Computer With RS485 MODBUS FEATURES 1. DESCRIPTION APPLICATIONS

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

Manual. MegaTron Controller Supplemental. Modbus / TCP Communications Manual

Transcription:

Acromag, Incorporated 30765 S Wixom Rd, PO Box 437, Wixom, MI 48393-7037 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com Honeywell Trendview Recorder & Acromag 967EN Modbus/TCP Module as Remote I/O Contents: page Summary 2 Assumptions 3 Requirements 3 Overview of Trendview Functions 3 Acromag setup 4 Trendview setup 7 Testing 14 Notes 17 Acromag manual s Modbus maps 18 Copyright Acromag, Inc. Rev 1c, August 2011 8400 641 30765 S. Wixom Rd., Wixom, MI 48393 Tel: 248 295 0880 Trademarks are the property of their respective owners.

Honeywell Trendview recorder & Acromag 967EN Modbus-TCP module as remote I-O Summary: The Acromag 967EN has 8 analog 4-20mA inputs. It is a Modbus/TCP slave, ideal for use as remote I/O with a Honeywell paperless Trendview recorder that runs as a Modbus/TCP master over a standard Ethernet network connection. The Acromag 967EN provides data in either floating point or signed integer formats. Signed integers values range 1 to 20,000 counts across the 4-20mA input span, so scaling to user friendly engineering units has to be done on the recorder. Floating point values can be scaled to engineering units in the Acromag and read directly as scaled values. If the scaling in the Acromag is correct, no scaling is needed in the recorder's pen math. Acromag setup is done via web browser, no software is needed. Typical input and scaling setup changes made in the web browser are downloaded and executed quickly, on the order of seconds. An ON-OFF power cycle is not required for input configuration changes. Acromag's sample time is 8mS, so the Acromag data tends to be noisier than the same signal wired into a recorder. The solution is to let the Acromag average multiple samples. Start with 20 as a number to average with. The 200 ohm 4-20mA analog input resistance will not unduly load a loop powered circuit, but will inhibit HART communications (HART requires 230 ohms, minimum). Acromags i2o remote messaging function writes values only to other Acromag products. Hence, i2o is not applicable for use with Trendview. 2

Assumptions: The implementer has - familiarity navigating the Trendview X series recorder setup menus - familiarity with ethernet network connections (devices on the same subnet) - familiarity with engineering unit scaling of industrial signals Requirements: The Trendview needs sufficient credits to enable the Modbus master, including - 10 credits for Modbus master - 4 credits for full function math (script math is acceptable, standard math is not) - as many credits as needed to enable a 'pen' for each Modbus value read from the Acromag and used by the Trendview. Unused analog input pens can be used for Modbus data. Extra or virtual pens are enabled by credits. 1 credit enables 2 extra/virtual pens. Additional credits can be purchased from a Honeywell distributor, if need be. This application note applies only to Honeywell X Series Trendview recorder with firmware versions FK or above, (latest firmware version is strongly recommended). Versions CU to FK were buggy. Earlier V4 or V5 Trendview recorders did not have a Modbus Master option and cannot be used with Acromag Modbus slaves. Overview of Trendview functions: All Trendview recorders have an Ethernet port that can be enabled to run as a Modbus master. When configured, the Trendview s Modbus master will issue a Modbus request to the Acromag Modbus slave for data. The Acromag s response can provide from 1 to as many as 62 Modbus values in one Modbus message (967EN handles only 8 analog signals). The recorder assigns each received Modbus value an SCV math value; math statement SCV[x,y,z]. This math statement is used in configuring pen 'math' as the source for the pen's data. As pen data, the Modbus value can be used in any useable Trendview form. All the configuration parameters done in the Acromag s web browser can be done via Modbus, but this app note only addresses the critical function of fetching the data. Trendview uses Acromag s published Modbus decimal register values 3

Acromag Setup: Power the Acromag (24Vdc). Plug in an Ethernet cable, straight CAT5 cable to PC works OK (crossover not needed). Assign the Acromag a working static IP address - The Acromag default IP address is 128.1.1.100 - Get your PC s ethernet port onto the same subnet: 128.1.1.x - Launch a web browser (Internet Explorer) - open 128.1.1.100 - log-in default user: User (capital U) default password: password00 (lower case,.... zero zero) - Browse to the Network Configuration web page - Enter the working IP address (192.168.1.99 in this example) and click submit button - Change PC s IP address to get it back to its working subnet (192.168.1.xx in this example) 4

- Log back into the Acromag on its new working IP address/subnet via browser User: User password: password00 - Navigate to the Input Configuration web page - Select a channel (each channel is independently configured) - Select input type (typically 4-20mA) - If reading floating point, Acromag s scaling can be used. The values are IEEE 754 formatted, perfect for either Honeywell FPLB or FP B byte order formats. Enter the zero and span range scale values. 5

- If reading integer formatted values, Acromag s scaling has no effect. The Acromag s integer values are 0-20,000 ranged over 4-20mA range. So, for reading integer format, skip the ranging. - then submit: click Channel Configuration Submit Average: - average 20 samples, submit Floating Point Control: (do not enable if reading integer format) - Select Enable Floating Point Support; submit - Select floating point byte order B1,B0,B3,B2, submit (corresponds with Trendview s Modbus-X, FP B format and byte order) - be sure to fill in the scaling values for the input range (example 0-500 gpm), submit Conclude by submitting latest or all changes: 6

Trendview setup: Screen shots shown below are from a QX recorder. This same setup applies to all model Trendviews (SX, QX, QXe). 1) Confirm that recorder is on the same subnet (xxx.xxx.xxx.yyy) as the Acromag. Ethernet port setup: 2) Enable credits for Modbus master, full or scripting math, and extra pens for each Modbus value that will be polled and used. (16 pens uses 8 credits; 8 pens use 4 credits) 7

Enable Modbus master as shown below: Open and configure Slave 1 (or whichever Slave is available) as shown below: Give Slave x an appropriate Friendly Name (Acromag 967EN is example). network name = Acromag IP address There are four separate Trendview transaction setups in this app note. Pick only one. 1) Floating point format, Modbus-X FP B read Input register function code 04 * 2) Floating point format, Modbus FPLB read Holding register function code 03 3) Integer format, read Input register function code 04 4) Integer format, read Holding register function code 03 * recommended Note: Selecting integer format mandates (requires) Trendview scaling of the 0-20,000 count data value provided by the Acromag. 8

1) Floating Point Format, Read Input Register function code 04 Open a Transaction. Unassigned Transactions show up as red X, pick one. Select: Green check mark enables the transaction In selects a read operation (reads data into the recorder) Input Registers(4) selects function code 04 IEEE float selects the floating point format under Protocol on Slave X screen 3018 is the indexed decimal starting address 43018 for first of 8 analog values 8 as the number of integer registers to be read in a single transaction First value uses math statement SCV[1,1,1] Second value uses math statement SCV[1,1,2] Third value uses math statement SCV[1,1,3] Use Acromag s Input Configuration web page to configure scaling for the data value. The protocol selection (on Trendview s Slave x screen) must match Acromag s Floating Point byte order choice Bw,Bx,By,Bz. A mismatch produces unusable results. matches Acromag matches Acromag 9

2) Floating Point Format, Read Holding Register function code 03 Open a Transaction. Unassigned Transactions show up as red X, pick one. Select: Green check mark enables the transaction In selects a read operation (reads data into the recorder) Holding Registers(3) selects function code 03 IEEE float selects the floating point format under Protocol on Slave X screen 3034 is the indexed decimal starting address 43034 for first of 8 analog values 8 as the number of integer registers to be read in a single transaction First value uses math statement SCV[1,1,1] Second value uses math statement SCV[1,1,2] Third value uses math statement SCV[1,1,3], etc Use Acromag s Input Configuration web page to configure scaling for the data value. The protocol selection (on Trendview s Slave x screen) must match Acromag s Floating Point byte order choice, Bw,Bx,By,Bz. matches Acromag A mismatch produces unusable results. matches Acromag 10

3) Integer Format, Read Input Register function code 04 Open a Transaction. Unassigned Transactions show up as red X, pick one. Select: Green check mark enables the transaction In selects a read operation (reads data into the recorder) Input Registers(4) selects function code 04 Signed 16 bit int selects the compatible integer format for data in the Acromag 18 is the indexed decimal starting address 30018 for first of 8 analog values 8 as the number of integer registers to be read in a single transaction First value uses math statement SCV[1,1,1] Second value uses math statement SCV[1,1,2] Third value uses math statement SCV[1,1,3], etc Scaling Example: the 0-20,000 count is scaled 0-500 gpm (divide SCV value by 40): 11

4) Integer Format, Read Holding Register function code 03 Open a Transaction. Unassigned Transactions show up as red X, pick one. Select: Green check mark enables the transaction In selects a read operation (reads data into the recorder) Holding Registers(3) selects function code 03 Signed 16 bit int selects the compatible integer format for data in the Acromag 34 is the indexed decimal starting address 30034 for first of 8 analog values 8 as the number of integer registers to be read in a single transaction First value uses math statement SCV[1,1,1] Second value uses math statement SCV[1,1,2] Third value uses math statement SCV[1,1,3] Scaling Example: the 0-20,000 count is scaled 0-500 gpm (divide SCV value by 40): 12

Testing Acromag s Test page shows real-time, live updates of the analog input signals and the scaled conversion values, which are the values that should appear when reading floating point values in the Trendview. Trendview Trendview pen values will appear as DPM (digital) values, trend graph or bar graph values, as selected on screen layouts: 13

Communications diagnostics Path: Menu > Status > Diagnostics > Comms > Modbus 14

Modscan32: A generic Modbus master application, like Modscan32 reads Acromag Function Code 04, read Input Registers: Note that the integer value at 30018 is 10002 counts, equivalent to 12.0mA. The floating point register at 30034 is scaled to engineering units in gpm 15

Function Code 03, read Holding Registers: Note that the integer value at 30018 is 10002 counts, equivalent to 12.0mA. The floating point register at 30034 is scaled to engineering units in gpm: 16

Notes: 1) The Acromag 967EN is a Modbus/TCP slave in a desktop test easily supported two Modbus/TCP connections from two Modbus masters (Trendview and Modscan32, each at one second polling rates). 2) The Trendview can read up to 62 floating point (124 integer) values in a single Modbus master transaction, when located in contiguous registers. The recommendation is to read all of the Acromag 967EN s 8 values in a single transaction. The internal memory allocated for Modbus registers is fixed so there is no downside to fetching multiple values in a single read transaction. 3) Analog calibration can be done on the Acromag, or a 'loop calibration' can be done with Trendview's single point (offset) or dual point compensation (y=mx+b). 4) Differences between commercial and industrial Acromag modules: 5) References to Trendview s Modbus maps are irrelevant because the Trendview runs as a Modbus master. 17

Acromag manual references Data representation: Modbus register maps: A) Input registers read with function 04 Data values in integer format reside in Input registers starting at 30018 decimal Data values in Floating point format reside in Holding registers starting at 30034 18

Holding registers are the identical to input register values remapped to 43xxx : Data values in integer format reside in Holding registers starting at 43018 decimal (read with function 03) Data values in Floating point format reside in Holding registers at 43034 (read with function 03) Application note courtesy of Dan Weise, Lesman Instrument Company About Acromag Acromag is a leading manufacturer of temperature transmitters and signal conditioners for use with thermocouple and RTD sensors. These instruments convert the sensor input to a proportional 4-20mA DC current, DC voltage, Modbus, Profibus, or Ethernet signal to interface with a PC, PLC, DCS, or other control equipment. Acromag has designed and manufactured measurement and control products for more than 50 years. They are an AS9100 and ISO 9001-certified international corporation with a world headquarters near Detroit, Michigan and a global network of sales representatives and distributors. Acromag offers a complete line of industrial I/O products including a variety of process instruments, signal conditioners, and distributed fieldbus I/O modules that are available with a 7-year warranty. Industries served include chemical processing, manufacturing, defense, energy, and water services. For more information about Acromag products, call the Inside Sales Department at (248) 295-0880, FAX (248) 624-9234. E-mail sales@acromag.com or write Acromag at 30765 South Wixom Road, P.O. Box 437, Wixom, MI 48393-7037 USA. The web site is www.acromag.com. 19