EMC Symmetrix DMX-3 and DMX-4 Electrical Power Estimation and Configuration Planning

Similar documents
Technical Note P/N REV A01 March 29, 2007

Power Vault in EMC Symmetrix DMX-3 and Symmetrix DMX-4 Systems

Assessing and Comparing HP Parallel SCSI and HP Small Form Factor Enterprise Hard Disk Drives in Server Environments

Virtualizing SQL Server 2008 Using EMC VNX Series and VMware vsphere 4.1. Reference Architecture

IBM Storwize V5000 disk system

EMC STORAGE FOR MILESTONE XPROTECT CORPORATE

EMC XTREMCACHE ACCELERATES ORACLE

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016

EMC SYMMETRIX VMAX 40K STORAGE SYSTEM

White Paper Features and Benefits of Fujitsu All-Flash Arrays for Virtualization and Consolidation ETERNUS AF S2 series

IBM Storwize V7000 TCO White Paper:

Reducing Costs in the Data Center Comparing Costs and Benefits of Leading Data Protection Technologies

A Look at CLARiiON with ATA CX Series Disk Drives and Enclosures

Virtualization and consolidation

EMC SYMMETRIX VMAX 40K SYSTEM

EMC CLARiiON Backup Storage Solutions

SQL Server 2008 Consolidation

EMC XTREMCACHE ACCELERATES VIRTUALIZED ORACLE

EMC Backup and Recovery for Microsoft Exchange 2007

Power Conservation Inside and Outside the Box EMC s Cross-Platform Approach to Energy Efficient Information Management

Optimizing Tiered Storage Workloads with Precise for Storage Tiering

VMware vstorage APIs FOR ARRAY INTEGRATION WITH EMC VNX SERIES FOR SAN

EMC SYMMETRIX VMAX 10K

Exam : Title : High-End Disk for Open Systems V2. Version : DEMO

Storage s Pivotal Role in Microsoft Exchange Environments: The Important Benefits of SANs

EMC Backup and Recovery for Microsoft Exchange 2007 SP1. Enabled by EMC CLARiiON CX4-120, Replication Manager, and VMware ESX Server 3.

Using EMC FAST with SAP on EMC Unified Storage

Optimizing the Data Center with an End to End Solutions Approach

Considering the 2.5-inch SSD-based RAID Solution:

DELL Reference Configuration Microsoft SQL Server 2008 Fast Track Data Warehouse

POWERMAX FAMILY. Appliance-based packaging. PowerMax 2000 and Specifications. Specification Sheet. PowerMax Arrays

EMC Celerra Manager Makes Customizing Storage Pool Layouts Easy. Applied Technology

Acer Hitachi AMS2300 specifications

EMC Virtual Infrastructure for Microsoft Exchange 2010 Enabled by EMC Symmetrix VMAX, VMware vsphere 4, and Replication Manager

Drive Sparing in EMC Symmetrix DMX-3 and DMX-4 Systems

USING EMC FAST SUITE WITH SYBASE ASE ON EMC VNX STORAGE SYSTEMS

Dell PowerEdge R720xd with PERC H710P: A Balanced Configuration for Microsoft Exchange 2010 Solutions

VEXATA FOR ORACLE. Digital Business Demands Performance and Scale. Solution Brief

PowerVault MD3 SSD Cache Overview

Overcoming the Challenges of Server Virtualisation

All-Flash Storage Solution for SAP HANA:

EMC Solutions for Enterprises. EMC Tiered Storage for Oracle. ILM Enabled by EMC Symmetrix V-Max. Reference Architecture. EMC Global Solutions

A Comparative Study of Microsoft Exchange 2010 on Dell PowerEdge R720xd with Exchange 2007 on Dell PowerEdge R510

Is Tape Really Cheaper Than Disk?

Vblock Architecture. Andrew Smallridge DC Technology Solutions Architect

Data center requirements

EMC Business Continuity for Microsoft Applications

Surveillance Dell EMC Storage with Cisco Video Surveillance Manager

Discover the all-flash storage company for the on-demand world

IBM System Storage EXP3500 Express

Dell EMC PowerVault ME4 Series Storage

Surveillance Dell EMC Storage with Digifort Enterprise

Dell Reference Configuration for Large Oracle Database Deployments on Dell EqualLogic Storage

Virtualized SQL Server Performance and Scaling on Dell EMC XC Series Web-Scale Hyper-converged Appliances Powered by Nutanix Software

EMC CLARiiON LUN Shrinking with Microsoft Exchange 2007

Dell Fluid Data solutions. Powerful self-optimized enterprise storage. Dell Compellent Storage Center: Designed for business results

The IBM Storwize V3700: Meeting the Big Data Storage Needs of SMBs

Increasing Energy Efficiency through Modular Infrastructure

Deploy a High-Performance Database Solution: Cisco UCS B420 M4 Blade Server with Fusion iomemory PX600 Using Oracle Database 12c

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy

Reducing Data Center Cooling Costs through Airflow Containment

EMC VSPEX FOR VIRTUALIZED MICROSOFT EXCHANGE 2013 WITH MICROSOFT HYPER-V

Evaluation Report: Improving SQL Server Database Performance with Dot Hill AssuredSAN 4824 Flash Upgrades

LEVERAGING EMC FAST CACHE WITH SYBASE OLTP APPLICATIONS

Assessing performance in HP LeftHand SANs

EonStor DS - iscsi Series High-Availability Solutions Delivering Excellent Storage Performance

DAHA AKILLI BĐR DÜNYA ĐÇĐN BĐLGĐ ALTYAPILARIMIZI DEĞĐŞTĐRECEĞĐZ

EMC Virtual Infrastructure for Microsoft SharePoint Server 2010 Enabled by EMC CLARiiON and VMware vsphere 4

Lenovo SAN Manager. Rapid Tier and Read Cache. David Vestal, WW Product Marketing. June Lenovo.com/systems

EMC Celerra NS20. EMC Solutions for Microsoft Exchange Reference Architecture

DELL EMC VMAX3 FAMILY

The PowerEdge M830 blade server

Hybrid Storage for Data Warehousing. Colin White, BI Research September 2011 Sponsored by Teradata and NetApp

Understanding the ESVA Architecture

Copyright 2012 EMC Corporation. All rights reserved.

EonStor DS - SAS Series High-Availability Solutions Delivering Excellent Storage Performance

Dell EMC SAN Storage with Video Management Systems

Executive Brief June 2014

Lenovo RAID Introduction Reference Information

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Entry-level Intel RAID RS3 Controller Family

Achieving Energy Efficiency with EMC CLARiiON CX3 Storage Systems Best Practices Planning

Frequently Asked Questions. s620 SATA SSD Enterprise-Class Solid-State Device

Business Benefits of Policy Based Data De-Duplication Data Footprint Reduction with Quality of Service (QoS) for Data Protection

The Data-Protection Playbook for All-flash Storage KEY CONSIDERATIONS FOR FLASH-OPTIMIZED DATA PROTECTION

Surveillance Dell EMC Storage with FLIR Latitude

DS8880 High Performance Flash Enclosure Gen2

Planning for Easy Tier with IBM System Storage Storwize V7000 and SAN Volume Controller

PESIT Bangalore South Campus

IBM System Storage DCS3700

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

DELL EMC UNITY: BEST PRACTICES GUIDE

VMAX3 AND VMAX ALL FLASH WITH CLOUDARRAY

Storageflex HA3969 High-Density Storage: Key Design Features and Hybrid Connectivity Benefits. White Paper

EMC XTREMCACHE ACCELERATES MICROSOFT SQL SERVER

VMware vsphere 5.0 STORAGE-CENTRIC FEATURES AND INTEGRATION WITH EMC VNX PLATFORMS

Hitachi Adaptable Modular Storage and Workgroup Modular Storage

EonStor DS 3000 Series

EMC Integrated Infrastructure for VMware. Business Continuity

Using EMC CLARiiON CX4 Disk-Drive Spin Down with EMC Celerra FAST

Transcription:

EMC Symmetrix DMX-3 and DMX-4 Electrical Power Estimation and Configuration Planning A Detailed Review Abstract This white paper provides a detailed description of the EMC Symmetrix DMX-3 and DMX-4 power systems design. It explains the various factors that contribute to power consumption and efficiency, with information on how to configure the storage array for the best efficiency. June 2008

Copyright 2006, 2007, 2008 EMC Corporation. All rights reserved. EMC believes the information in this publication is accurate as of its publication date. The information is subject to change without notice. THE INFORMATION IN THIS PUBLICATION IS PROVIDED AS IS. EMC CORPORATION MAKES NO REPRESENTATIONS OR WARRANTIES OF ANY KIND WITH RESPECT TO THE INFORMATION IN THIS PUBLICATION, AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Use, copying, and distribution of any EMC software described in this publication requires an applicable software license. For the most up-to-date listing of EMC product names, see EMC Corporation Trademarks on EMC.com All other trademarks used herein are the property of their respective owners. Part Number H2399.2 A Detailed Review 2

Table of Contents Executive summary...4 Introduction...4 Audience...4 Configuration planning...5 Configuring for power efficiency...5 Critical components in design...5 Disk drives...5 Drive density and configuration...6 Ultra-performing Flash drives...7 Tiered storage in large arrays...9 Virtual Provisioning...11 Configuration summary...12 Power density and cooling...13 Power Calculator tool: Getting the exact information...14 Conclusion...14 References...14 A Detailed Review 3

Executive summary As the need to conserve energy becomes more important in the data center, having the information needed to acquire and configure efficient storage systems becomes important as well. The typical spec sheets provided for facilities planning assumes a maximum load with a fully configured system, and with a high margin for safety under all possible conditions. While this is appropriate for wiring and safety, it is not always helpful in predicting the cost of actual energy usage, nor in providing the proper capacity for cooling, data center layout, and other environmental factors. EMC has taken great care to provide efficient storage systems, holding down the costs of operation. This white paper complements the facilities planning data by providing the information necessary to understand the various components in the array, how they contribute to power consumption, and how to configure Symmetrix DMX-3 and DMX-4 systems for the highest efficiency. It also introduces tools available to get detailed information about actual usage. Introduction Energy consumption is rapidly growing in importance in IT, energy prices have risen over the past few years, and at the same time the amount of information to be stored continues to expand. Customers are demanding that the products that they buy tomorrow are designed with power efficiency in mind, and that they have access to the information that they need to make informed choices. Energy management can be complex. Consumption varies with workload, availability requirements, time of year and other variables that make understanding the issues difficult. Power produces heat, which requires energy to cool, and all this must usually be managed for power failure as well. Power usage and cost continue to grow. A recent IDC survey 1 indicated that users expect power consumption to increase by 25 percent over the next two years. Since the amount of data to be stored is increasing by 56 percent per year, the challenge is to do more and store more while keeping power increases to much less than that. There are a number of concerns related to power efficiency. The most obvious is cost. The cost of electricity is increasing steadily, and there is more at stake than just the energy used by the storage. For each dollar spent on electricity to power the storage, it typically takes another dollar or more to get rid of the heat produced, which means that the cost can double in some situations. In some cases, data center redesign is required to manage the excess heat. Another problem can be even more severe. In some locations, additional power is unavailable at any price; the local utility is simply unable to provide additional capacity. Of course, storage is not generally the main culprit. As servers become more dense, the proportion of energy that they use can overshadow that used by storage, and there are certainly ways to consolidate servers with VMware and other conservation methods, but clearly, anything that can be done to reduce power consumption is quite important. This white paper will provide valuable information on how to do that. Audience This document is intended for technical customers and EMC personnel who are configuring DMX-3 and DMX-4 storage arrays. It provides an understanding of the various factors that contribute to energy consumption, and how those apply to EMC DMX-3 and DMX-4 products. It assumes some familiarity with DMX-3 and DMX-4 storage and electrical concepts. A useful prelude to this document can be found in the EMC white paper Power Efficiency and Arrays, which can be found at EMC.com. 1 IDC, End User Perspectives on Server Blade Adoption, Doc # TB20060525, May 2006 A Detailed Review 4

Configuration planning Many customers are constrained by the amount of power and cooling available in a building. In addition, their operating budgets aren t growing as fast as storage requirements, so the rising cost of electricity can be problematic. If there is not enough power or cooling available for a storage array, some older equipment may need to be removed and consolidated with the newer equipment. EMC offers some configuration options and methodologies that can free up power and cooling levels and improve the customer s power efficiency in the data center. The logical place to start is in the data center with the server population. Servers are faster, and consume more power, while blade server design packs more of them in smaller spaces, putting pressure on everything else in the data center, especially storage. Consolidating servers to reduce their numbers, perhaps using a product like VMware, can be quite beneficial. The next step is to use the EMC ControlCenter tools to measure utilization, particularly for multiple arrays, and Scope to highlight opportunities for consolidation. With larger, scalable DMX-3 and DMX-4 arrays available, a significant power savings can be realized by consolidating many older arrays into one. Using the DMX- 3 and DMX-4 and taking older equipment offline, can significantly improve power efficiency by reducing watts per terabyte. The removed equipment and its associated power consumption can be applied as a savings to the newer equipment. The application of the two software packages, VMware and ControlCenter, allows the customer to realize immediate power savings and free up a portion of the power and cooling budget for the new storage array. In cases where the availability of power is restricted, you will now know how much power and cooling are available for storage. As you will see, there are a number of tradeoffs available between capacity, performance, and efficiency, and it is important to configure the array to meet the intended applications. Since the DMX-3 and DMX- 4 can start with a small configuration and be increased nondisruptively over time to very large configurations, systems need not be overconfigured today to support future growth, which provides for the best efficiency today and in the future. Configuring for power efficiency The best case for optimum power efficiency is an in-the-box tiered storage solution, which the DMX-3 and DMX-4 are specifically designed to do. It is important to be familiar with the EMC Symmetrix DMX-3 Best Practices Technical Note to fully understand the options and recommended configurations available. It is also necessary to understand the applications and environment prior to configuring the system. The EMC Sales teams have access to the EMC Power Calculator, a tool that calculate the front-end and back-end workload, performance requirements, power consumption, and more. Critical components in design It is necessary to understand the functioning of three critical components in the DMX-3 and DMX-4 to produce the most efficient design. These are: The drives themselves, speed and capacity The arrangement of the drives in DAEs and storage s The advantages of using a minimum number of large arrays rather than more smaller arrays We ll explore each of these topics in detail before returning for some final recommendations Disk drives Disk drives are the largest users of power in storage arrays, and a good place to start. As you will see, there are many choices to be made, resulting in tradeoffs between performance and efficiency. Finding the right balance is important and can be quite difficult, but EMC provides the expertise, information, and tools that are needed to make these critical choices. The unparalleled flexibility and scalability of the DMX-3 and DMX-4 mean that you can provide for multiple environments in a single array, and easily change or grow as the need arises. A Detailed Review 5

EMC works closely with disk drive suppliers to ensure that Symmetrix arrays use drives that are designed for power efficiency. This ensures that the drives can be cooled properly, and that future upgrades can be done with the same power and cooling budget. Since the drives contribute the highest percentage to the overall power consumption, this translates into ongoing power savings. The most important factor in drive power consumption is the actual speed of the drive. The faster that it spins, the more energy is required to keep it spinning. Thus, there is an immediate tradeoff available between power and performance, making it important to select the proper speed drive for the application. Surprisingly, the capacity of the drive has very little effect on power consumption. For high speed drives, 73 GB and 146 GB drives use about the same power, and the same is true for 146 GB and 300 GB drives spinning at 10k rpm. This means that it is possible to immediately lower power consumption by specifying larger drives. But doubling the capacity reduces the number of spindles and may reduce the overall performance. Again, careful analysis is required to strike the right balance The I/O rate acting on the drives also has some significance on power as shown in Figure 1. This is not surprising; the more activity that a drive is subjected to, the more power it draws. The effect can be quite noticeable at high I/O rates and should be allowed for in planning and budgeting. DMX-4 Bay percent increase in Power as a function of I/O rate - 15k 73 GB drives Percent Increase in Power 14.0% 12.0% 10.0% 8.0% 6.0% 4.0% 2.0% 0.0% 0 20,000 40,000 60,000 80,000 I/O Rate, Mb/s Figure 1. Power consumption increases as a function of I/O rate Drive density and configuration A second factor in efficiency is the arrangement of the drives within a storage. A storage can contain as many as 240 drives, which are configured in 16 disk-array enclosures, or DAEs. Each DAE can contain up to 15 drives, so 15 x 16 will get you 240 total drives. The DAE provides power and connectivity to the individual drives, and the DAE chassis requires a certain amount of power itself, which does not increase with the number of drives, and is still required even when it contains no drives at all. A Detailed Review 6

360 W 120 W Total DAE Input Power (Watts) 300 W 240 W 180 W 120 W 60 W Total DAE Power Watts / Drive 100 W 80 W 60 W 40 W 20 W Watts/Drive 0 W 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Installed Drives Input Power Watts/Drive 0 W Figure 2. input power versus number of installed drives using recommended drive distribution to optimize availability Figure 2 illustrates this. The empty DAE with no drives is shown on the left axis, and you can see that it draws nearly 100W when empty. Since each individual drive adds about 17W, the average watts/drive is reduced significantly as the DAE fills up, dropping from 117W/drive to about 23W/drive with 15 drives included. Ultra-performing Flash drives Flash drives use less energy than rotating media, and weigh less as well. When compared to a 73 GB rotating drive, as can be seen in Table 1, the Flash drive uses 30 percent to 40 percent less energy. As the cost of these drives is reduced over time, this savings will become increasingly important. The real energy savings, though, becomes evident when comparing the two drives based on comparable IOPS. Performance testing indicates that a single Flash drive can deliver the same IOPS as 30 of the 15k rpm drives. When this comparison is made, using Flash drives for performance can cut energy use by as much as 97.7 percent. If 120 rotating drives can be replaced by four of the Flash drives, the savings can be significant, as shown in Figure 3. Existing DMX-4 and DMX-4 950 systems can be upgraded with Flash drives after upgrading to Enginuity 5773. A Detailed Review 7

Power / IOPS Power/IOPS 2,767 kwh/yr per 100k 99.2% less 30x IOPS jump 98.6% less 97.9% less 133,493 kwh/yr per 100k IOPS 193,608 kwh/yr per 100k IOPS 354,055 kwh/yr per 100k IOPS Performance 73 GB Flash 73 GB 15K 146 GB 15K FC 300 GB 10K FC Figure 3. On a per-iops comparison, Flash drives require 98% less energy 500 GB 7.2K And, of course, the savings in weight and floor space and even noise levels can be important as well. Table 1 compares individual power consumption and weight of Flash drives and HDDs. 1 Table 1. Power and weight comparison of 73 GB Flash drive and 73 GB 15k rpm HDD Drive type 73 GB Flash drive 73 GB 15k rpm HDD AC drive power in a system 15.80W 25.40W Weight 0.781 lb 1.85 lb 1 TB 7.2K Capacity 1 Power numbers in the table may vary depending on exact configuration. Consult your EMC representative for specific power usage derived from the EMC Power Calculator. A Detailed Review 8

Tiered storage in large arrays The third key to storage efficiency is consolidation. Instead of a larger number of smaller arrays, a smaller number of large, fully utilized arrays can mean a significant improvement in efficiency. Of course, this places a couple of critical requirements on storage. Both the DMX-3 and DMX-4 allow you to grow capacity without suffering performance degradation. As storage increases, performance for critical applications must increase in a completely linear manner. One of the principal advantages of the DMX-3 and DMX-4 systems is the ability to configure multiple storage tiers in the same array. This can be done in a way that prevents the various tiers from affecting one another so that applications receive the performance that they need. The in-the-box tiered storage solution essentially tailors the drive capacity to performance requirements for the intended applications. In this case, the drives are distributed so that certain DA pair processors have slower (high capacity) drives and others have faster (high performance) drives. There are four tiers frequently used to describe the performance requirements and criticality of the data, with Tier 0 being highest. Flash drives create a new ultra performance tier within a Symmetrix for applications such as algorithmic trading, Internet transactions, or foreign exchange. This ultra tier benefits from the full array of advanced capabilities that Symmetrix provides, including local and remote replication, cache partitioning, and priority controls. The DMX design provides up to four pairs of disk adapters, or DAs, and each of these can support up to eight storage ports. A single (pair of) port(s) can manage drives in multiple s cabled together, which are referred to as loops, Adding a large number of drives to a loop may affect performance. Now, using Flash drives, Tier 0 applications can be closely coupled with other storage tiers within Symmetrix for consistency and efficiency, eliminating the need for time invested in manual data layout or end-of-day data transfers from separate RAM disk or specialized memory storage systems. Tier 1 would include high performance applications, such as Exchange or Oracle, which are best suited for the 15- drive loops with the smaller, faster 73 or 146 GB 15k drives. Tier 2 applications include data warehousing and various noncritical database applications. These can be serviced with high capacity, medium speed, enterprise drives such as 300 GB 10k drives. Tier 3 is typically for data archiving and lower performance applications and uses the high capacity, low speed 500 or 1000 GB 7.2k drives with longer drive loops. Longer loops are accomplished via daisy chaining to subsequent storage s. Configuring in this manner provides the highest performance with the best predictability for critical applications and a more cost-effective, lower-performance tier for less critical applications. Some considerations are: Small loops of high performance drives use the most power but offer the highest possible performance. Larger capacity drives conserve power, but fewer spindles may have performance implications in some situations. Extending loops permits more drives to share the DA pair, and thus spread its power over a larger number of drives, but may have performance implications. Figure 4 illustrates the efficiency advantages of tiering quite clearly. It provides a direct comparison of power consumption per terabyte among drives of various sizes, and the power required at various I/O rates. Since the DMX-3 and the DMX-4 have the ability to mix multiple drive types in a single array, users have the ability to tailor the array to provide all the capacity and performance required with minimum power consumption. A Detailed Review 9

DMX-3 Bay Power Consumption per GB as a Function of I/O - 480 drives 0.3 0.25 0.2 Input VA/GB 0.15 7.2k, 500GB 10k, 300GB 15k, 146GB 0.1 0.05 0 0 2,000 10,000 25,000 50,000 I/O Rate, Mb/s Figure 4. Power consumption per GB of hard disk drives as a function of I/O rate As pointed out previously, for power efficiency it is also important that all slots in the DAEs be populated to fully utilize power overhead for cooling, logic, and power supply efficiency. Figure 5 shows the scaling concept and use of in-the-box tiered storage. The color coding shows the different disk adapter (DA) pairs that direct connect to DAEs in adjacent storage s and then they in turn daisy chain to DAEs in outer storage s. Each DA pair supports 120 to 480 physical drives via eight Fibre Channel loops. Each loop contains from 15 to 60+ drives. Starting with the yellow DA pair shown in Figure 5, the adjacent cabinet can be direct connected with fibre cable. Subsequent storage s can be daisy chain connected as shown in the lighter color. Depending on the applications and capacity and performance needed, the number of drives, type of drives, and number of DA pairs can be varied. Additional drives and performance can be realized by an additional DA pair, shown in green in Figure 5. It s best to scale the drives one way and then add DA pairs to scale on the other side. Figure 5. Scaling concept using different DA pairs For instance, the high performance Tier 1 15k drives could be the direct connect dark green color code. The light green could be the lower performance 10k drives. If the loops are to remain small for high performance and avoid A Detailed Review 10

contention, the light green drives might not be populated at all. For Tier 2 or 3 data, the 7.2k or 10k drives would be populated all the way to the outer s. For Tier 0, Flash drives are only supported in direct connect storage s. It is recommended to dedicate one quadrant to Flash drives with a maximum of 32 Flash drives per quadrant. All members of a RAID 5 group should be configured on homogeneous Flash drives. Virtual Provisioning EMC Virtual Provisioning builds on the base thin provisioning functionality, which is the ability to have a large thin device (that is, volume) configured and presented to the host while consuming physical storage from a shared pool only as needed. Symmetrix Virtual Provisioning can improve storage capacity utilization and simplify storage management by presenting the application with sufficient capacity for an extended period of time, reducing the need to provision new storage frequently and avoiding costly allocated but unused storage. Energy is conserved using Virtual Provisioning by allocating less storage and therefore reducing hardware requirements. Reported capacity Allocated Application perceived thin device Data devices Common storage pool Figure 6. Symmetrix Virtual Provisioning Symmetrix Virtual Provisioning will operate on any new or existing Symmetrix DMX-3 or DMX-4 system and will integrate easily into organizations existing knowledge and management processes for the Symmetrix platform. Configuring, replicating, managing, and monitoring thin devices and thin pools involves the same tools and the same or very similar functions as those used for years with standard provisioning. Symmetrix Virtual Provisioning will operate on typical Fibre Channel or new Flash drives, and thin pools can coexist with standard storage in the same system. Tiered storage Symmetrix Virtual Provisioning adds a new dimension to tiered storage in the array, most notably (when used appropriately) by improving the utilization of storage tiers that can tolerate performance variability. Thin devices and storage pools can be used in a tiered storage configuration in the same manner as standard devices. Thin devices will adhere to priorities assigned to them by Symmetrix Priority Controls. Data devices within a thin pool, meanwhile, can be assigned to cache partitions created by Dynamic Cache Partitioning. In addition, different RAID groups can be assigned to different thin pools, in accordance with their designated tier. Performance One of the direct consequences of Virtual Provisioning is the wide striping that occurs. Data volumes can be striped across a large number of drives, which can balance the workload and improve performance. In some cases, this A Detailed Review 11

improvement can allow you to use larger, more efficient drives, thus saving energy for the same reasons shown in the tiering discussion. Configuration summary The DMX-3 and the DMX-4 are the most scalable, and most flexible, storage arrays available today, and are the logical choice for situations where managing and minimizing power is important. In addition, EMC has tools that will provide detailed information about specific configurations, making it simple to plan and budget. Following the guidelines below will result in the best combination of performance and efficiency: Minimize DA pairs required. Use more daisy chain storage s to obtain needed capacity with less DA pairs. Fully load drive enclosures with drives (15) to reduce excess power overhead from cooling, logic, and power supply load efficiency. Fully populate your DA pairs before adding additional pairs. Order storage s in increments of half to fully utilize enclosures. Use larger capacity drives to reduce spindles. Use tiered storage to reduce the number of higher speed drives when requirements allow. Use Flash drives for maximum performance with latency sensitive applications. Use RAID 5 or other as opposed to RAID 1 full mirroring. Add incremental storage s and DA pairs as demand changes. Use shorter loops for high performance drives, longer loops for lower performance drives. Use Virtual Provisioning to allocate less storage and therefore reduce hardware requirements. A Detailed Review 12

Power density and cooling The power consumption, kva (kilovolts x amperes), of fully configured DMX-3 and DMX-4 machines with 10k rpm drives is used to determine the heat dissipation, BTU/hr (British thermal units per hour). It is assumed that all the input power of the system is converted into heat energy and no mechanical work is being done. This provides a worse-case number for facilities designers in sizing the HVAC system. The results are tabulated in Table 2. The typical power of the fully configured system is 5.8 kva and is factored into the total of each storage value. Table 2. Symmetrix DMX power consumption and heat dissipation DMX-3 and DMX-4 1 2 3 4 5 6 7 8 Drive count, max 240 480 720 960 1200 1440 1680 1920 Power consumption (kva) 12.5 18.6 27.7 30.8 36.9 43.0 49.1 55.2 Heat dissipation (BTU/hr) 41,380 61,180 80,980 100,780 120,580 140,380 160,180 179,980 The power consumed to remove the waste heat from the building can typically range from 40 percent to 60 percent of the input power to the cabinet. This also includes the 40 percent to 50 percent of the waste heat in the data center from the voltage transformers, UPS, and electrical distribution. The DMX-3 and DMX-4 have a patent pending cooling design that allows better flow of hot exhaust air to help improve efficiency of the HVAC cooling system. A simplified picture is shown in Figure 7. The hot exhaust air is forced to the ceiling, away from the front intake of the machine and toward the air return duct. This helps keep a higher air temperature entering the chiller and refrigeration unit, which improves its cooling efficiency. Less air needs to be moved around the room and refrigerated, humidified, and returned. It also reduces hot spots around the equipment that can permit for an overall increase in data center room temperatures, which can further reduce power consumption. The DMX-3 and DMX-4 cabinets also have the flexibility to be placed in a hot-aisle/cold-aisle or traditional bottom-to-top cooling environment. Figure 7. DMX-4 air flow diagram in data center A Detailed Review 13

Power Calculator tool: Getting the exact information The figures in this white paper are for typical systems, and may be useful for general planning, but your configuration probably isn t exactly like the examples. EMC has developed an effective tool that can be used to project the power consumption of various subsystems in a DMX-3 or DMX-4 storage system. The EMC Power Calculator is a flexible tool that estimates power consumption of a specific configuration. This tool enables users to derive an estimate of AC and DC power of various EMC storage system configurations. The power estimate ranges from typical to maximum and includes a recharge power value that represents the time after the battery discharges and then recharges. The purpose of the tool is to provide a means for customers to estimate power and cooling requirements, and then be able to interactively vary the configurations to meet specific power requirements. This can be combined with the configuration guidelines listed above to allow customers to meet their power and cooling targets. Contact your local EMC Sales Representative to obtain additional information on the EMC Power Calculator. Conclusion Controlling energy consumption in a data center environment is becoming more important with every passing day. As the need for processing power grows, along with the need for more storage, so does power consumption and the concentration of that consumption into smaller and smaller areas. The DMX-3 and DMX-4 products were designed with efficiency as a high priority and offer many configuration options to balance energy usage with performance requirements and capacity. These options make it possible to deliver the capacity, performance, and features required with the lowest possible energy usage. EMC provides the information and tools needed to take advantage of this flexibility and configure the most efficient storage arrays available. References The following documents provide additional sources of Symmetrix information. They are available on EMC.com and Powerlink, EMC s customer- and partner-only extranet, except where noted. Power Efficiency and Arrays white paper EMC Symmetrix DMX-3 Best Practices Technical Note (Powerlink only) EMC Symmetrix Virtual Provisioning white paper EMC Symmetrix DMX-4 Ultra-Performance Tier 0 Using Flash Drives white paper A Detailed Review 14