IFC 100 Supplementary instructions

Similar documents
ETHERNET/MFC 010 Technical Datasheet

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2

INTELLIS. Modbus Direct Network Monitor

RS 485 Mini Modbus 1AO

UFD 5. Display for ALTOSONIC 5. Technical Datasheet. Configurable display for ALTOSONIC 5 Easy installation Durable design

RS485 MODBUS Module 8AO

1.Eastron SDM530-Modbus Smart Meter Modbus Protocol Implementation V1.1

GE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C

VPGate Manual PROFIBUS to serial

AL2-MBU Advanced Manual

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM102(1739) For 4511 devices from ser. no:

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

RS485 MODBUS Module 16I-M

F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide

T2314, T2414. Instruction Manual

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

AXL E IOL AO1 U M12 R

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

List of Contents 1. INTRODUCTION DEFINITIONS AND ABBREVIATIONS REFERENCES TECHNICAL DATA GENERAL MODBUS RTU...

ZBRN2 Modbus Serial Line Communication

RS485 MODBUS Module 8I8O

Modbus. Instructions 42/ EN

Remote Operation Instructions HART Communicator 275 Asset Management Solutions (AMS) IFC090 KROHNE 11/2000

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM100(1402)

8 data bits, least significant bit sent first 1 bit for even/odd parity (or no parity) 1 stop bit if parity is used; 1 or 2 bits if no parity

INTEGRA DL1 DUAL LOAD DIGITAL METER COMMUNICATIONS GUIDE DIGITAL ENERGY METER FOR MULTIPLE LOADS IN AN ELECTRICAL SYSTEM

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

RS485 MODBUS Module 6RO

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

I/O Module. Modbus Manual DMB Series.

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM101(1445) For 4511 devices from ser. no:

DRS-100-3P MID Energy Meter Direct Connect, 100A, Three phase Communications Guide

SMARTRAIL X100 Protocol

Copyright: December 2017 Nidec Issue: E

ALTOSONIC V12 Modbus manual. Protocol description & set-up

TRANSDUCER T4311, T4411

T2314, T2414. Instruction Manual

SKD-005-M Protocol. 2 RS485 General Information 2.1 Half Duplex 2.2 Connecting the Instruments 2.3 A and B terminals 2.

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for

MODBUS MANUAL For the AccUView UV Transmission Monitor

Golander Peristaltic Pump MODBUS Communication Instruction

VISY-Command. Technical Documentation. with Modbus Protocol. Edition: Version: 1 Art. no.:

Modbus RTU Serial Communication User Manual

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

Modbus on CO 2 Engine and esense

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM100(1402)

General Specifications

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4116MCM101(1445) For 4511 devices from ser. no:

RS485 MODBUS Module 8I8RO

SPM90 MODBUS PROTOCOL AND REGISTER LIST V1.0

OPTRIS CT/CTL communication interface

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

Interface design document MODBUS Protocol. Ab s t r a c t Description of the MODBUS implementation for the Modbus I/O board

VERIS H8035 and H8036

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM101(1445) For 4511 devices from ser. no:

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

MODBUS Message Protocol MODEL FT3

Optris CT/ CTlaser/ CTvideo communication interface

Modbus for FICO, slave mode General Engineering Guide

Interface Module XC Modbus Protocol Converter / User Manual

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100

DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS

OPTRIS CT communication interface

4511 MODBUS RTU. Configuration Manual. Pulse isolator. No. 9202MCM101(1707) For 4511 devices from ser. no:

EGW1-IA3-MB User s Manual

1. Introduction. 2. Installation MODBUS INTERFACE

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

ELECTRONIC METER SX1-A31E MODBUS RTU Protocol Specifications MDD-T0025A

General Specifications

ENG-7680: SCADA Laboratory Experiments

MODBUS MESSAGE PROTOCOL FOR MODEL FT2 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

RS-FX-N01 wind transmitter user's Guide (485type)

Modbus Remote Communication Protocol for REM 54_. Technical Description

ABB Drives. User s Manual RS-485 Adapter Board FRSA-00

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

AP25-3DO PROTOCOL. Modbus Guide - Issue 1.0 SUBJECT TO CHANGE WITHOUT NOTICE

mbc082 Bus Converter

General Specifications

4511 MODBUS RTU. Configuration Manual. Solenoid / alarm driver. No. 9203MCM100(1328)

Modbus Protocol For FTS/FTM 3x&8x

Revision 1.2. July 24, COM Protocol Manual. for MDC and ADC N 11th St - San Jose CA

DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL

THT-500-A/R (C5) 1. System Configuration COMMUNICATION INSTRUCTION MANUAL. No. THT5CE

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

Programmable transmitter of temperature, relative humidity and other derived humidity values with RS485 serial output Instruction Manual

RS-FS-N01 Wind speed transmitter user's Guide (485type)

Technical Documentation

MODBUS Protocol for MiCOM P30 Series

MODBUS Protocol. The ecode Encoders contain both single register (16 bit) and double register (32 bit) values.

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

GW-7228 J1939/Modbus RTU Slave Gateway

Transcription:

IFC 100 Supplementary instructions Signal converter for electromagnetic flowmeters Description of Modbus interface Electronic Revision: ER 3.0.xx Modbus version: 1.0.xx KROHNE

CONTENTS IFC 100 1 Important information 3 2 Technical data 4 2.1 General technical data...4 2.2 Technical data of the Modbus interface (acc. to EIA standards)... 4 3 Connection in bus systems 5 4 Local configuration 6 5 Electrical connection 7 6 Modbus protocol 8 6.1 General information concerning the protocol... 8 6.2 RTU frame format... 8 6.3 Addressing... 9 6.4 Overview of supported functions... 9 6.5 Device identification on the Modbus interface... 10 6.6 Coil registers... 10 6.6.1 Converter controls... 10 6.6.2 Counter controls... 11 6.6.3 Start calibration functions... 11 6.7 Input registers... 12 6.8 Holding registers... 13 6.8.1 Counter parameters... 13 6.8.2 Process input filter and self test parameters... 14 6.8.3 Modbus parameters... 16 6.9 Diagnostics... 16 6.10 Calibration procedures... 17 6.10.1 Zero Flow Calibration... 17 6.10.2 Coil Temperature Calibration... 18 6.10.3 Conductivity Calibration... 19 2

IFC 100 IMPORTANT INFORMATION 1 The flow converter with the RS485 interface card fitted, is able to communicate with an external device (PC or other suitable computer system) using the Modbus protocol. This option allows data exchange between PC or computer and single or multiple devices. The bus configuration consists of one external device as a master and one or more converters as slaves. For bus operation the device address (menu C5.8.1), baudrate (menu C5.8.2) and settings (menu C5.8.3, C5.8.4, C5.8.5 & C5.8.6) must be set in the converter. All devices connected to the bus, must have different unique addresses but the same baud rate and settings. 3

2 TECHNICAL DATA IFC 100 2.1 General technical data Interface RS485, galvanically isolated Baud rate 1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600 or 115200 Protocol Maximum participants on bus Coding Modbus RTU (available as a separate document on request) 32 per line, master included (may be extended by repeaters) NRZ bit coding Address range Modbus: 1...247 Transmission procedure Bus access Cable Distances Half duplex, asynchronous Master / slave Shielded twisted pair for RS 485 applications Maximum 1.2 km / 3937 ft without repeater (dependant on baud rate and cable specifications) 2.2 Technical data of the Modbus interface (acc. to EIA standards) Kind of signal transmission Maximum number of transmitter/receivers Voltage range on converter input Maximum voltage on converter output Minimum voltage on driver output, max. load Maximum input current (off state) Receiver input voltage Sensitivity of the receiver Receiver input resistance Short circuit current Termination / polarization resistors (refer to chapter "Electrical connection") Differential, 2-wire topology 32-7...+12 V 5V U diff >1.5V -20...+20 μa -7...+12 V -200...+200 mv >12kΩ < 250 ma 120 Ω / 560 Ω 4

IFC 100 CONNECTION IN BUS SYSTEMS 3 For proper operation of Modbus in half duplex mode in single or multi-drop communication, it is recommended that a termination resistor is applied to both ends of the data line. The simplest form of termination is line-to-line resistor across the differential input. In RTU mode the Modus protocol requires quiet periods on the communications bus for synchronisation. It is therefore important that the Modbus is not allowed to "float", i.e. unreferenced to 0 V, as this could lead to spurious signals due to noise pick-up. It is therefore necessary to employ biasing resistors at one point on the bus network, normally the "end". 5

4 LOCAL CONFIGURATION IFC 100 Converter Fct. No. Display Description and settings C5.8.1 Slave Address Selects the Modbus address of the device. Range: 1..247 (default = 1) C5.8.2 Baud Rate Selects the baud rate of the device. Options: 1200 / 2400 / 3600 / 4800 / 9600 / 19200 (default) / 38400 / 57600 / 115200 C5.8.3 Parity Selects the parity. Options: Even (default) / Odd / No C5.8.4 Data Format Selects the data format. Options: Big Endian (default) / Little Endian C5.8.5 Transmission Delay Selects the delay between receiving the last byte of a request and sending the first byte of the response. Range: 0..40ms (default = 0ms) C5.8.6 Stop Bits Selects the number of stop bits. Options: 1 (default) / 2 C5.8.7 Information Displays information about the device. 6

IFC 100 ELECTRICAL CONNECTION 5 Refer to the standard handbook of the converter for connection details. Modbus connections Terminals Description B- Signal B (D 1) B Signal A (D 0) C- Common 0 V C 3.3 V; 560 Ω D- Pulse output - D Pulse output + Example for bus termination R1: 120 Ω R2: 560 Ω 7

6 MODBUS PROTOCOL IFC 100 6.1 General information concerning the protocol Using RTU (Remote Terminal Unit) format, data is transmitted as 8 bit binary characters. There are no special characters to determine the start and end of a message frame. Synchronisation is achieved by a minimum silent period of at least 3.5 character times before the start of each frame transmission and a maximum silent period of 1.5 character times between characters in the same frame. 6.2 RTU frame format The format of the query and response frames vary slightly depending upon the command function. The basic form is outlined below. Command function Frame format Description Silent period 3.5 x T All transmissions must be preceded by a minimum silent period of 3.5 x T, where T is the transmission time of a single character. This can be calculated from the baud rate, e.g. at 19.2 kb no parity with 1 stop bit (10 bits), T=520µs. Slave address 8bits This is a single byte slave address which is transmitted first and must be in the range of 1...247. Address 0 is reserved for a broadcast address which all slaves should recognise, and therefore requires no response. Function code 8bits This is an eight bit code in the range of 1...255 although only 126 functions exist as the codes 129...255 represent an error condition. An error condition occurs when the addressed slave does not accept the command, in which case it responds with the function code + 128, i.e. with its MSB set to 1. Register start address or byte count when required 8 bit byte count 16 bit address Register start address: for a query command that requires data to be returned, this field will contain the 16 bit start address of the register (or data) to be returned. Note that the signal converter uses protocol addresses. Therefore the register address listed is the actual number required in the Modbus command. E.g: to access input register 30006, the register start address is 30006dec = 7536hex. Number of points or data bytes when required n 8bits Byte count: In general this is only present in frames that are transferring data, and has a value equal to the number of bytes contained in the data field. The data field is limited to a maximum of 250 bytes. Number of points: for a query command that requires data to be returned, this field will contain the number of registers to be returned regardless of their bit size. Data bytes: contains the data requested. The signal converter can use Big Endian format (MSB first) or Little Endian format (LSB first). CRC 16 bits This field contains a 16 bit CRC which is calculated on all the data bits of the message bytes. 8

IFC 100 MODBUS PROTOCOL 6 6.3 Addressing In the following tables the Modbus protocol addresses / data addresses are listed. Some systems cannot use addresses above 9999. For these systems there is the possibility to use the listed addresses but for Input Registers omit the leading 3 of 3xxxx; for Holding Registers omit the leading 4 of 4xxxx; for Input Registers replace the leading 20 of 20xxx by 9xxx. Sometimes register numbers are asked for. The register numbers can be calculated by adding a 1 to the protocol address and using a prefix according to the block: prefix 1 for coils prefix 3 for Input Registers prefix 4 for Holding Registers 6.4 Overview of supported functions The following table shows Modbus functions supported by RS485 interface. Function code Name Access to hex dec 01 01 Read Single Coil Status of calibration functions, counter status (start/stop) 03 03 Read Holding Register Acyclic Registers Signal converter configuration parameter 04 04 Read Input Register Cyclic Register Measurement values, status values and calibration results 05 05 Write Single Coil Cold start, warm start, error reset, start calibration function, start/stop counter 08 08 Diagnostics - 10 16 Write Multiple Register Acyclic Registers Signal converter configuration parameter 2B 43 Encapsulated Interface Transport Transparent Channel, Read Device Identification 9

6 MODBUS PROTOCOL IFC 100 6.5 Device identification on the Modbus interface The device identification is according to the category "Regular" according to the Modbus Application Protocol Specification V1.1a. Function code 43 / 14 (0x2B / 0x0E). Modbus object Id Object name / Description Type Content 0x00 VendorName 16 byte ASCII String KROHNE 0x01 ProductCode 10 byte ASCII String CG number; order code for the converter assembly 0x02 MajorMinorRevision 7 byte ASCII String V1.0.xx 0x03 Vendor URL 32 byte ASCII String 0x04 ProductName 16 byte ASCII String IFC100 0x05 ModelName 16 byte ASCII String Modbus 0x06 UserApplicationName 16 byte ASCII String User tag, displayed on the header of the local screen 6.6 Coil registers These function codes are used for access: 0x01 = read input coil 0x05 = write single coil 6.6.1 Converter controls Coil address Function 1000 Write 1 generates a cold start, write 0 is ignored 1001 Write 1 generates a warm start, write 0 is ignored 1002 Write 1 generates an error reset, write 0 is ignored 10

IFC 100 MODBUS PROTOCOL 6 6.6.2 Counter controls Modbus protocol address Description Settings Converter Fct. No. 3000 Start / Stop Write 1 start counter C3.1.8 / C3.1.9 Counter 1 Write 0 stop counter Read 1 counter is running Read 0 counter is stopped 3001 Start / Stop Write 1 start counter C3.2.8 / C3.2.9 Counter 2 Write 0 stop counter Read 1 counter is running Read 0 counter is stopped 3002 no function 3003 Reset Counter 1 Write 1 reset counter C3.1.6 Write 0 - Read 0-3004 Reset Counter 2 Write 1 reset counter C3.2.6 Write 0 - Read 0-3005 no function 6.6.3 Start calibration functions Modbus protocol address Description Settings Converter Fct. No. 2000 Zero Calibration Write 1 start function C1.1.1 Write 0 - Read 0-2001 Coil Temperature Write 1 start function C1.1.8 Calibration Write 0 - Read 0-2002 Electrode Factor Write 1 start function C1.1.11 Calibration Write 0 - Read 0-11

6 MODBUS PROTOCOL IFC 100 6.7 Input registers All input registers in the Modbus protocol address range from 30000 to 38998 are mapped into the range 0 to 8998. All input registers in the Modbus protocol address range from 20000 to 20998 are mapped into the range 9000 to 9998. This is done to give systems with restriction on the address range access to the device. Measurement and status values are read only and can be accessed as Modbus "Input Registers". Cyclic GDC objects are mapped to Modbus Registers. Function code is 04 (0x04). Modbus protocol address Description and settings Type Number of registers 1st 2nd 30000 0 flow speed [m/s] float 2 30002 2 volume flow [m 3 /s] float 2 30004 4 mass flow [kg/s] float 2 30006 6 coil temperature [K] float 2 30008 8 conductivity [S/m] This value may not be measured. float 2 Depending on register (4)2003. 0 = off (not measured) 1 = conductivity [S/m] 2 = cond. + empty pipe (S) [S/m] 3 = cond. + empty pipe (F) [S/m] 4 = cond. + empty pipe (I) [S/m] 30010 10 diagnosis value This value may not be measured. float 2 Depending on register (4)2011. 25 = off (not measured) 31 = electrode noise [m/s] 8 = terminal 2 DC [Volt] 9 = terminal 3 DC [Volt] 30012 12 Display Channel 1 Represents the value on the first line of float 2 the first measurement screen in SI units 30014 14 Display Channel 2 Represents the value on the first line of float 2 the second measurement screen in SI units 30016 16 Operating time [s] float 2 30018 18 Not used, returns zero float 2 30020 20 Counter 1 [m 3 ] or [kg] double float 4 30024 24 Counter 2 [m 3 ] or [kg] double float 4 30028 28 Not used, returns zero double float 4 30032 32 long status sensor byte [4] 2 30034 34 long status device byte [4] 2 Input register 30018 is not used up to now. This is included to fill the gap between the float and double float values and allows to read the full range of registers. 12

IFC 100 MODBUS PROTOCOL 6 Also the result of a calibration procedure is accessed by an input register at Modbus Protocol Address 20000 or 9000. The type are one or more float values. This is depending on the used function (refer to "Calibration procedures"). Modbus protocol address Description and settings Type Number of registers 1st 2nd 20000 9000 Result of a calibration function one or more float values 2 times number of values 6.8 Holding registers All holding registers in the Modbus protocol address range from 40000 to 49998 are mapped into the range 0 to 9998. This is done to give systems with restriction on the address range access to the device. Some parameters of the device can be accessed as Modbus "holding registers". Function code 03 (0x03) for "Read" operations and function code 16 (0x10) for "Write" operations. The holding registers are grouped into the following different sections. 6.8.1 Counter parameters Modbus protocol address Description and settings Converter Fct. No. Type Number of registers 1st 2nd 40000 0 counter 1 function 1=sum counter C3.1.1 byte 1 2=+counter 3 = - counter 0=off 40001 1 measurement Cnt1 21 = volume flow C3.1.2 word 1 22 = mass flow 40002 2 counter 2 function 1=sum counter C3.2.1 byte 1 2=+counter 3 = - counter 0=off 40003 3 measurement Cnt2 21 = volume flow C3.2.2 word 1 22 = mass flow 40004 4 no function byte 1 40005 5 no function word 1 41000 1000 low flow cutoff value Cnt1 [m 3 /s] or [kg/s] C3.1.3 float 2 41002 1002 time constant Cnt1 [s] C3.1.4 float 2 41004 1004 set counter Cnt1 or read Cnt1 [m 3 ] or [kg] C3.1.7 float 2 41006 1006 low flow cutoff value Cnt2 [m 3 /s] or [kg/s] C3.2.3 float 2 41008 1008 time constant Cnt2 [s] C3.2.4 float 2 13

6 MODBUS PROTOCOL IFC 100 Modbus protocol address Description and settings Converter Fct. No. Type Number of registers 1st 2nd 41010 1010 set counter Cnt2 or read Cnt2 [m 3 ] or [kg] C3.2.7 float 2 41012 1012 no function float 2 41014 1014 no function float 2 41016 1016 no function float 2 41018 1018 preset counter 1 [m 3 ] or [kg] C3.1.5 float 2 41020 1020 preset counter 2 [m 3 ] or [kg] C3.2.5 float 2 41022 1022 no function float 2 6.8.2 Process input filter and self test parameters Modbus protocol address Description and settings Converter Fct. No. Type Number of registers 1st 2nd 42000 2000 flow direction 0=normal direction C1.2.2 byte 1 1 = reverse direction 42001 2001 pulse filter 0=off C1.2.4 byte 1 1=on 2 = automatic 42002 noise filter 0=off C1.2.7 byte 1 1=on 42003 2003 empty pipe 0=off C1.3.1 byte 1 1 = conductivity 2 = cond. + empty pipe (S) 3 = cond. + empty pipe (F) 4 = cond. + empty pipe (I) 42004 2004 no function byte 1 42005 2005 no function byte 1 42006 2006 no function byte 1 42007 2007 no function byte 1 42008 2008 no function byte 1 42009 2009 electrode noise 0=off C1.3.13 byte 1 1=on 42010 2010 settling of field 0=off C1.3.16 byte 1 1=on 42011 2011 diagnosis value 25 = off C1.3.17 byte 1 31 = electrode noise 8=terminal2DC 9=terminal3DC 43000 3000 limitation low [m/s] C1.2.1 float 2 14

IFC 100 MODBUS PROTOCOL 6 Modbus protocol address Description and settings Converter Fct. No. Type Number of registers 1st 2nd 43002 3002 limitation high [m/s] C1.2.1 float 2 43004 3004 time constant [s] C1.2.3 float 2 43006 3006 pulse width [s] only if pulse filter is set to 1: on C1.2.5 float 2 43008 3008 pulse limitation [m/s] C1.2.6 float 2 43010 3010 noise level [m/s] C1.2.8 float 2 43012 3012 noise suppression C1.2.9 float 2 43014 3014 low flow cutoff value [m/s] C1.2.10 float 2 43016 3016 limit empty pipe [S/m] C1.3.3 float 2 43018 3018 no function float 2 43020 3020 no function float 2 43022 3022 limit electrode noise [m/s] C1.3.14 float 2 43024 3024 Zero point [m/s] C1.1.1 float 2 43026 3026 Coil Resistance Rsp, 20 [Ω] C1.1.7 float 2 43028 3028 Coil Temperature Calpoint [K] C1.1.8 float 2 43030 3030 Coil Resistance Calpoint [Ω] C1.1.8 float 2 43032 3032 Electrode Factor EF [m] C1.1.11 float 2 43034 3034 Conductivity Calpoint [S/m] C1.1.11 float 2 43036 3036 Conductivity Calpoint [S/m] C1.1.11 float 2 43038 3038 pulse width [s] only if pulse filter is set to 2: automatic C1.2.5 float 2 15

6 MODBUS PROTOCOL IFC 100 6.8.3 Modbus parameters Modbus protocol address 6.9 Diagnostics Description and settings The Modbus interface supports the diagnostic function defined by the "Modbus Application Protocol Specification". Function code is 08 (0x08). Converter Fct. No. Type 50000 baud rate 1200 / 2400 / 3600 / 4800 / 9600 / 19200 C5.8.2 ulong 2 (default) / 38400 / 57600 / 115200 50002 slave address C5.8.1 byte 1 50003 parity 0 = even parity (default) C5.8.3 byte 1 1 = odd parity 3=no parity 50004 data format 1=Big Endian 2 = Little Endian C5.8.4 byte 1 Number of registers Sub function code Name hex dec 00 00 Return Query Data 01 01 Restart Communication Option 04 04 Force Listen Only Mode 0A 10 Clear Counters 0B 11 Return Bus Message Count 0C 12 Return Bus Communication Error Count 0D 13 Return Bus Exception Count 0E 14 Return Slave Message Count 0F 15 Return Slave No Response Count 10 16 Return Slave NAK Count (counter not used) 11 17 Return Slave Busy Count (counter not used) 12 18 Return Bus Character Overrun Count 16

IFC 100 MODBUS PROTOCOL 6 6.10 Calibration procedures 6.10.1 Zero Flow Calibration 1 User reduces the actual flow through the meter to zero 2 Start zero calibration: Set single coil 2000 to 1 (Modbus Fct. 0x05) 3 Check status of calibration Read single coil 2000 (Modbus Fct. 0x01) 3a [2000 == 1: calibration running] 3b [2000 == 0: calibration complete] 4 Read Calibration Value Read Input Register 20000 type float (Modbus Fct. 0x04) 5 User checks the calibration value: -0.01...+0.01: good results -0.1...+0.1: acceptable result for difficult application 5a Not ok 5b ok 6 User tries to improve the calibration situation 6a Improvement done 6b Improvement not possible -Break- 7 Write the calibration value Write Holding Register 43024 type float (Modbus Fct. 0x10) 8 Activate new values Set single coil 1001 to 1 (Modbus Fct. 0x05) 8a This results in a warm start of the device. Will take maximum 5s. 17

6 MODBUS PROTOCOL IFC 100 6.10.2 Coil Temperature Calibration 1 Read actual Rsp,20 Read Holding Register 43026 type float (Modbus Fct. 0x03) 2 User checks the value with the calibration value on the type plate of the device 2a Rsp,20 not correct 2b Write correct Rsp,20 Write Holding Register 43026 type float (Modbus Fct. 0x10) 2c Rsp,20 correct or corrected 3 User enters the actual coil temperature in K This is the target for the calibration 4 Write actual coil temperature Write Holding Register 43028 type float (Modbus Fct. 0x10) 5 Start coil temperature calibration: Set single coil 2001 to 1 (Modbus Fct. 0x05) 6 Check status of calibration: Read single coil 2001 (Modbus Fct. 0x01) 6a [2001 == 1: calibration running] 6b [2001 == 0: calibration complete] 7 Read Calibration Value Read Input Register 20000 type foat (Modbus Fct. 0x04) 8 Write the calibration value Write Holding Register 43030 type foat (Modbus Fct. 0x10) 9 Activate new values Set single coil 1001 to 1 (Modbus Fct. 0x05) 9a This results in a warm start of the device. Will take maximum 5s. 18

IFC 100 MODBUS PROTOCOL 6 6.10.3 Conductivity Calibration 1 User enters the actual conductivity in S/m This is the target for the calibration 2 Write actual conductivity Write Holding Register 43034 type float (Modbus Fct. 0x10) 3 Write actual conductivity Write Holding Register 43036 type float (Modbus Fct. 0x10) 3a The target value has to be written to both registers! 4 Start conductivity calibration: Set single coil 2002 to 1 (Modbus Fct. 0x05) 5 Check status of calibration: Read single coil 2002 (Modbus Fct. 0x01) 5a [2002 == 1: calibration running] 5b [2002 == 0: calibration complete] 6 Read Calibration Value Read Input Register 20000 type float (Modbus Fct. 0x04) 7 Write the calibration value Write Holding Register 43032 type float (Modbus Fct. 0x10) 8 Activate new values Set single coil 1001 to 1 (Modbus Fct. 0x05) 8a This results in a warm start of the device. Will take maximum 5s. 19

KROHNE product overview KROHNE - Subject to change without notice. Electromagnetic flowmeters Variable area flowmeters Ultrasonic flowmeters Mass flowmeters Vortex flowmeters Flow controllers Level meters Temperature assemblies Pressure transmitters Analysis products Products and systems for the oil & gas industry Measuring systems for the marine industry Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.:+49 203 301 0 Fax:+49 203 301 103 89 info@krohne.com The current list of all KROHNE contacts and addresses can be found at: