XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Similar documents
XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

MRT1 Test Unit. Manual MRT1 (Revision A)

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

02/11/2015

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Contact protection relay

Electronic timer CT-ERS.21

08/07/2015

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

02/11/2015

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Electronic timer CT-ERD.12

Electronic timer CT-ARS.11

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Arc protection relay. Features Three-phase overcurrent function. Application

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-BUFFER/24DC/24DC/40

Electronic timer CT-AHD.22

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

TRIO-DIODE/12-24DC/2X10/1X20

MINI MCR-SL-UI-REL(-SP)

02/11/2015

STEP-PS/1AC/24DC/1.75

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relay

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Power Supply HARTING pcon

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Arc protection relay. Features Three-phase overcurrent function. Application

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

MINI MCR-SL-PT100-UI(-SP)(-NC)

MRP2-S3 Apparent Power Relay. Manual MRP2-S3 (Revision A)

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

Earth-fault Relay SPAJ 110 C. Product Guide

Residual overvoltage relay

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

MINI-PS AC/10-15DC/8

Binary output and supervision 520CSD01 Data sheet

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

RM4JA01F current measurement relay RM4-J - range ma V AC

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

PHOENIX CONTACT - 01/2007

RM4TR31 three-phase network control relay RM4-T - range V

Zelio Control-modular measurement and control relays 1

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

FL MC 2000E (SM40) LC

Installation / Control Technique

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RM4TA32 three-phase network control relay RM4-T - range V

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

Power Supply HARTING pcon

NI REM Remote I/O Overview DATASHEET. Digital Output Module for Remote I/O

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

QUINT-PS-3x AC/24DC/10

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

EM2020 Selectable AC transducer A (UK)

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

MINI MCR-SL-UI-2I(-SP)(-NC)

Feeder protection relay SPAA 121 C. Product Guide

Power supply CP-C 24/5.0

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

Transcription:

XU1-E Earth fault voltage relay (August 1996) Manual XU1-E (Revision New)

Woodward Manual XU1-E GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken. Woodward 1994-2008 2 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward Contents 1. Applications and features... 4 2. Design... 5 3. Function... 6 4. Operation and settings... 7 4.1 Setting of DIP-switches... 8 4.2 Setting of the tripping values... 9 4.3 Communication via serial interface adapter XRS1... 10 5. Relay case and technical data... 11 5.1 Relay case... 11 5.2 Technical data... 12 TD_XU1-E_08.96_GB_Rev.New 3

Woodward Manual XU1-E GB 1. Applications and features The XU1-E of the PROFESSIONAL LINE is a digital relay for earth fault detection in isolated and resistively earthed medium voltage systems. Digital filters ensure a suppression of harmonics. The relay can be connected to the open e-n winding of the voltage transformer. When compared to conventional protection equipment all relays of the PROFESSIONAL LINE reflect the superiority of digital protection techniques with the following features: High measuring accuracy by digital data processing Fault indication via LEDs Extremely wide operating ranges of the supply voltage by universal wide range power supply Very fine graded wide setting ranges Data exchange with process management system by serial interface adapter XRS1 which can be retrofitted RMS - measurement Extremely short response time Adjustment of rated data Compact design by SMD-technology In addition to this relay XU1-E has the following special features: Different switching hysteresis adjustable Adjustable trip delay 4 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward 2. Design Figure 2.1: Connection diagram Analog inputs The analog input signals of earth fault voltage are connected to the protection device via terminals Ue and Un. Auxiliary voltage supply Unit XU1-E can be supplied directly from the measuring voltage itself or by a secured auxiliary supply. Unit XU1-E has an integrated wide range power supply. Voltages in the range from 19-55 V DC can be applied at connection terminals A1(L-) and A2(L+). Terminals A1/A3 are to be used for voltages from 50-750 V DC or from 36-520 V AC. Contact positions Figure 2.2: Contact positions of the output relays TD_XU1-E_08.96_GB_Rev.New 5

Woodward Manual XU1-E GB 3. Function Unit XU1-E has a single step earth fault voltage supervision. The noise signals caused by inductive and capacitive coupling are suppressed by an analog RC-filter circuit. The analog voltage signals are fed to the A/D-converter of the microprocessor and transformed to digital signals. The analog signals are sampled with a sampling frequency of 16 x fn, namely, a sampling rate of 1.25 ms (1,04 ms) for every measuring quantity at 50 Hz (60 Hz). The earth fault voltage is compared with the set reference value. Pickup of the supervision circuit is indicated by flashing of the LED UE>, after tripping it is steady lit. 6 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward 4. Operation and settings All operating elements needed for setting parameters are located on the front plate of the XU1-E as well as all display elements. Because of this all adjustments of the unit can be made or changed without disconnecting the unit off the DIN-rail. Figure 4.1: Front plate For adjustment of the unit the transparent cover has to be opened as illustrated. Do not use force! The transparent cover has two inserts for labels. Figure 4.2: How to open the transparent cover LEDs LED "ON" is used for display of the readiness for service (at applied auxiliary voltage Uv). LED UE> signals pickup (flashing) or tripping (steady light). Test push button This push button is used for test tripping of the unit and when pressed for 5 s a check-up of the hardware takes place. Both output relays are tripped and all tripping LEDs light up. TD_XU1-E_08.96_GB_Rev.New 7

Woodward Manual XU1-E GB 4.1 Setting of DIP-switches The DIP-switch block on the front plate of the XU1-E is used for adjustment of the rated values and setting of function parameters: DIP-switch OFF ON Function 1 2 3 4 5 x 1 x 10 Time multiplier for tue> 6 50 Hz 60 Hz Rated frequency 7* 1 % 2 % Switching hysteresis 8* 1 % 5 % Table 4.1: Function of DIP-switches * Only one of the DIP-switches 7-8 shall be in "ON" position at the same time. Rated frequency With the aid of DIP-switch 6 the rated frequency can be set to 50 or 60 Hz, depending upon the given mains characteristics. Switching hysteresis The switching hysteresis can be adjusted with the aid of DIP switches 7-8 to 1, 2 or 5% of the tripping value. It has to be ensured that only one of the two DIP-switches is switched on. The smallest switching hysteresis is limited to 0.5 V Multiplier for tue> If DIP-switch 5 is in position ON, the scale reading of time delay tue> is multiplied by 10. In position OFF the actual scale reading applies. 8 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward 4.2 Setting of the tripping values The PROFESSIONAL LINE units have the unique possibility of high accuracy fine adjustments. For this, two potentiometers are used. The coarse setting potentiometer can be set in discrete steps of 20 V. A second fine adjustment potentiometer is then used for continuously variable setting of the final 0-20 V. Adding of the two values results in the precise tripping value. Earth fault voltage element The earth fault voltage element can be set in the range from 1 to 120 V with the aid of the potentiometer illustrated on the following drawing. Example A tripping value UE> of 72 V is to be set. The set value of the right potentiometer is just added to the value of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be inside the marked bar, otherwise no defined setting value). Figure 4.3: Adjustment example The smallest adjustment UE> is 1 V. Time delay The time delay can be adjusted infinitely variably in the range from 0-10 s or 0-100 s. TD_XU1-E_08.96_GB_Rev.New 9

Woodward Manual XU1-E GB 4.3 Communication via serial interface adapter XRS1 Figure 4.4: Communication principle For communication of the units with a superior management system, the interface adapter XRS1 is available for data transmission, including operating software for our relays. This adapter can easily be retrofitted at the side of the relay. Screw terminals simplify its installation. Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the software, actual measured values can be processed, relay parameters set and protection functions programmed at the output relays. Information about unit XRS1 in detail can be taken from the description of this unit. 10 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward 5. Relay case and technical data 5.1 Relay case Unit XU1-E is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the PROFESSIONAL LINE. The front plate of the unit is protected with a sealable transparent cover (IP40). Figure 5.1: Dimensional drawings Connections terminals The connection of up to a maximum of 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see chapter 4). TD_XU1-E_08.96_GB_Rev.New 11

Woodward Manual XU1-E GB 5.2 Technical data Measuring input circuits Rated data Rated frequency: Power consumption in voltage circuit: Thermal capacity of the voltage circuit: 50 / 60 Hz 1 VA per phase at Un continuously 520 V AC Auxiliary voltage Rated auxiliary voltage Uv/ 36-520 V AC (f = 35-78 Hz) or 50-750 V DC / 4 W (terminals A1-A3) Power consumption: 19-55 V DC / 3 W (terminals A1 (L-) and A2 (L+)) Common data Dropout to pickup ratio: Resetting time from pickup: Returning time from trip: Minimum initialization time after supply voltage has applied: Minimum response time when the supply voltage is available: depending on the adjusted hysteresis <50 ms 200 ms 120 ms 70 ms Output relay Number of relays: 2 Contacts: 1 changeover contact for each trip relay Maximum breaking capacity: ohmic 1250 VA/AC resp. 120 W/DC inductive 500 VA/AC resp. 75 W/DC Max. rated voltage: 250 V AC 220 V DC ohmic load Imax. = 0,2 A inductive load Imax. = 0,1 A at L/R 50 ms 24 V DC inductive load Imax. = 5 A Minimum load: 1 W / 1 VA at Umin 10 V Maximum rated current: 5 A Making current (16 ms): 20 A Contact life span: 10 5 operations at max. breaking capacity System data Design standard: VDE 0435 T303; IEC 0801 part 1-4, VDE 0160; IEC 255-4; BS 142; VDE 0871 Temperature range at storage and operation: -25 C to +70 C Constant climate class F acc. to DIN 40040 and DIN IEC 68, T.2-3: more than 56 days at 40 C and 95 % relative humidity High voltage test acc. to VDE 0435, part 303 Voltage test: 2,5 kv (eff) /50 Hz; 1 min Surge voltage test: 5 kv; 1.2/50 µs, 0.5 J High frequency test: 2,5 kv / 1 MHz Electrostatic discharge (ESD) acc. to IEC0801 part 2: 8 kv 12 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward Radiated electromagnetic field test acc. to IEC 0801 part 3: Electrical fast transient (burst) acc. to IEC 0801 part 4: Radio interference suppression test as per DIN 57871 and VDE 0871: 10 V/m 4 kv/2.5 khz, 15 ms limit value class A Min. limit value UE>: 1 V Min. Hysteresis: 0,5 V Repeat accuracy: 1 % Basic time delay accuracy: 0.5 % or ±25 ms Accuracy of the specific rated values: 1 % at nominal frequency Temperature effect: 0.02% per K Frequency effect: 1 % per 1 Hz deviation of nominal frequency Mechanical test Shock: class 1 acc. to DIN IEC 255-21-2 Vibration: class 1 acc. to DIN IEC 255-21-1 Degree of protection Front panel: Weight: Mounting position: Relay case material: Relay case material: IP40 at closed front cover approx. 0.7 kg any self-extinguishing self-extinguishing Parameter Setting ranges Graduation UE> 1-120 V continuously variable tue> 0-10 s / 0-100 s continuously variable Hysteresis U</U> 1, 2, 5 % Table 5.1: Setting ranges and graduation Technical data subject to change without notice! TD_XU1-E_08.96_GB_Rev.New 13

Woodward Manual XU1-E GB Setting-list XU1-E Project: SEG job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters Function Unit Default settings UE> Earth fault voltage tripping V 1 tue> Trip delay for UE> s 0 DIP-switch Function Default settings 1 2 3 4 5 Multiplier for tue> x 1 6 Adjustment of the rated frequency 50 Hz 7* Hysteresis 1 % 8* 1 % Actual settings Actual settings *Only one of the DIP-switches 7-8 shall be in ON -position at the same time. 14 TD_XU1-E_08.96_GB_Rev.New

Manual XU1-E GB Woodward TD_XU1-E_08.96_GB_Rev.New 15

Woodward Woodward Kempen GmbH Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet www.woodward.com Sales Phone: +49 (0) 21 52 145 216 or 342 Telefax: +49 (0) 21 52 145 354 e-mail: salesemea_pgd@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: SupportEMEA_PGD@woodward.com