FAQ Communication over PROFIBUS

Similar documents
FAQ Communication over IE

FAQ Communication over PROFIBUS

FAQ Communication via IE

FAQ about communication via IE

FAQ about S7 communication via IE

FAQ Kommunikation over PROFIBUS

FAQ about communication via IE

FAQ about Drive Technology

Cover. Configuration of an IM 308-C as DP Slave to a CP as DP Master PROFIBUS DP. FAQ July Service & Support. Answers for industry.

FAQ about Drive Technology

Connecting a PC Station to an S using OPC

Usability Improvement SIMATIC NET PC CD 11/2003

TS8000. Profibus DP Slave Configuration Application Note TS8922U001

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D3

FAQ Communication over IE

Iris Demo V3. for use with a Siemens PLC

Why can you not transfer the HMI configuration to the panel? - PROFIBUS Connection - FAQ 03/2014

ProfinetCommander User Manual 3.1 March 2010

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D5

How Do You Replace a CPU 41x with the CPU 410-5H Process Automation? SIMATIC PCS 7 FAQ 01/2016

While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied.

SIMATIC. S7 and Profibus- DP Configuration Guide G1026

Commissioning PC Stations - Manual. and Quick Start SIMATIC NET. PC software Commissioning PC Stations - Manual and Quick Start.

Description of the Simotion D4xx Firmware update

How-To-Do. EtherCAT Communication with CPU 300S

Profibus PLC Setup Hardware setup, jumper settings and SYCON configuration. Design Studio driver configuration and I/O sheet setup.

TECHNICAL NOTE TNOI30

How-To-Do. Hardware Configuration SLIO CPU 015

Service & Support. Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server SIMATIC S7. Function description March 2013

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

LB/FB8X09* / LB/FB8X05*

How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ

OPERATOR INTERFACE PRODUCTS APPLICATION NOTE

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E09. PROFINET with 2x CPU 315F-2 PN/DP

Applications & Tools. Brief instructions on the communication connection of the MSS 3RK3 to the S via AS-Interface.

Danfoss FCD 300 AS-i and Siemens DP/AS-i Link 20E

Korea PROFIBUS/PROFINET Association 각사회사이름 각사 LOGO

Connecting UniOP to Simatic S7 Profibus

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

Document: S7 Driver Configuration. Setting up the S7 driver to communicate with Siemens Hardware (S7-300/400 Series) using CP

Configuration and Parameter Assignment Frame for the CPU 31x-2

SIMATIC. Component based Automation - WinLC PN Addendum to WinAC Basis V3.0. Foreword. Introduction to CBA and WinAC PN 2. Routing with WinLC PN 3

SIMATIC. Windows Automation Center WinAC Basis V4.1. User Manual. Version: 05/2004 A5E Siemens Automation

SCE Training Curriculum for Integrated Automation Solutions Totally Integrated Automation (TIA)

SIMATIC. Communications processor CP 340 first commissioning steps. Getting Started 04/2005 A5E

Catalog 1 Product Overview General Important User Information About the Gateway Function Features Tec

SIMATIC. Windows Logic Controller (WinLC) Preface, Contents. Product Overview 1. Setting Up WinLC Software 2

I-Device Function in Standard PN Communication SIMATIC S7-CPU, CP, SIMOTION, SINUMERIK. Configuration Example 08/2015

Programmable Controllers

Information About the Getting Started PCS 7 - First Steps Documentation

SIMATIC. Windows Automation Center. WinAC Basis. Overview. Preface. Product Overview 1. Installing the Components of. WinAC Basis

SIMATIC NET. S7-CPs for PROFIBUS. CP Extended for PROFIBUS. Manual Part B4

IE/PB LINK PN IO. PROFINET applications

SIMOTION V4.1 SP2 HF3/HF4

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

Process Control System PCS 7 V7.0. Getting Started First Steps Documentation November 2006

Accessing SINAMICS parameters via OPC server

Totally Integrated Automation Application Notes

CDN Series Displays with Profibus-DP ELEN UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE

efesotomasyon.com - Lenze EDBDRS3!P</ Ä!P</ä Handbuch/Manual Global Drive Busserver S7 Ers te S c h ri tte/getti ng Started

Service & Support. How can the Safety Functions of SINAMICS S120 be activated in an existing STEP 7 Project? Technology CPU.

SIMATIC. PDM V5.2 The Process Device Manager. Preface, Contents. Product Introduction 1. Starting SIMATIC PDM 2 Configuring Networks and Devices 3

PROFIBUS DP/CAN Gateway PCA-100. User Manual

SINAUT ST7. SINAUT ST7cc Control Center A I. Manual. Introduction to ST7cc. Installation. Preparation. Working with ST7cc Config

Start-up of IRI-KHD2-4HB6, IRI-KHA6-4HB6 at S7-300 V1.2. Table of Contents TABLE OF CONTENTS... 1

Murdoch University Engineering Thesis. Appendix XII. Profibus PA System Configuration Instructions

SCE Training Curriculum For Integrated Automation Solutions Totally Integrated Automation (TIA)

FAQ about Drive Technology

Applications & Tools. Failsafe and standard cross communication of the MSS 3RK3 via AS-Interface. SIRIUS Safety. FAQ February 2012

Application for Process Automation

SIMATIC NET. Telecontrol SINAUT ST7sc SCADA Connect Software. Preface, Contents. Introduction and installation 1

SIMATIC. Working with STEP 7. Introduction to STEP 1. The SIMATIC Manager 2. Programming with Symbols. Creating a Program in 4

SIMATIC. Modifying the System during Operation via CiR. Requirements and Overview 1. CiR Objects and CiR Modules. User Interface 3

SIMATIC. Windows Automation Center RTX WinAC RTX V4.0. User Manual A5E

SIMATIC. Configuring Hardware and Communication Connections STEP 7. Basics of Configuring Hardware with STEP 7. Configuring Central Racks 2

WinAC RTX 2010 Getting Started. Getting-started. Edition ( )

Modicon Quantum and Siemens S7-300 PLC as DP slave System User Guide [source code]

Tech Note 220 Configuring the S7 Server for MPI or Profibus Communications for Windows NT 4.0 to Access S7-400 PLCs via the Siemens CP5613 Card

PROFIsafe SITRANS. Pressure transmitter SITRANS P, DS III PROFIsafe series. Product Information 7MF4*34 04/2008 A5E

Siemens SIMATIC. Windows Automation Center WinAC Pro. Preface, Contents Product Overview and Installation. Getting Started 2.

S7-400, M7-400 Programmable Controllers

FAQ about Communication

Siemens Distributor SIMATIC. Component based Automation Creating PROFInet Components

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting.

SIMATIC. Configuring Hardware and Communication Connections STEP 7. Preface Basics of Configuring Hardware with STEP 7 1

Training Manual for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE E13

TIA Portal Workshop. Unrestricted. Siemens AG All rights reserved.

SIMATIC NET. S7-CPs for PROFIBUS Configuring and Commissioning

Think & Do Profibus Network Setup with the H0 PSCM


Table of Contents. Table of Contents

Fisher FIELDVUE DVC6200p Digital Valve Controller Device Setup and Accessing Communication and Calibration using Siemens SIMATIC Manager/PDM

DVPPF02-SL PROFIBUS DP Slave Communication Module

Configuration limits for products of the SIMATIC NET PC Software V8.1 SIMATIC NET

Supply voltage. Input current. Power loss. Memory. Battery. CPU processing times

SIMATIC. Process Control System PCS 7 First Steps (V7.1) Preface 1. Creating the PCS 7 Project 2. Configuring the hardware and networks

STEP 7. Function. Page 1791 Mar 2008 Siemens ITS

Trebing & Himstedt OPC Server DP. Installation Guide

SIMATIC. Windows Logic Controller WinLC RTX 3.1. Preface, Contents. Product Overview 1. Setting Up the WinLC RTX Software

Profibus DP Driver for JMobile

Transcription:

FAQ Communication over PROFIBUS Communication over PROFIBUS FAQ

Table of Contents Table of Contents... 2 Question...2 How do I configure a PC station as DP Slave interfacing to a S7 station (as DP Master) for the SIMATIC NET OPC server with the SIMATIC NET PC Software?... 2 Answer... 2 The instructions and notes listed in this document provide a detailed answer to this question.... 2 1 Assignment of tasks... 3 1.1 Condition... 3 2 Configuration of the PC station... 4 3 Interfacing the PC station (DP slave) to the S7 station (DP master)... 11 Rules... 14 4 Start of the OPC Scout... 16 5 History... 20 This entry is from the Internet offer of Siemens AG, Automation and Drives, Service & Support. Clicking the link below directly displays the download page of this document. http://support.automation.siemens.com/ww/view/en/16650883 Question Answer How do I configure a PC station as DP Slave interfacing to a S7 station (as DP Master) for the SIMATIC NET OPC server with the SIMATIC NET PC Software? The instructions and notes listed in this document provide a detailed answer to this question. V1.0 10.03.2008 2/20

1 Assignment of tasks In this example a CP5611 is used that implements the communication over the OPC server as DP slave with a S7 station as DP master on PROFIBUS. NOTE The method described in these instructions also applies to the communications processors CP 5511, CP 5512 and CP5621. 1.1 Condition There are the following configuration tools: NCM PC: NCM PC is supplied with the SIMATIC NET CD and allows you to create PC projects and open STEP 7 projects. It is, however, not possible to edit S7 blocks in the STEP 7 project with this software. STEP 7: STEP 7 is a separate software package with which you can create S7-400, S7-300 and PC projects. S7 blocks can be edited with this software. It `s assumed that STEP 7 is installed and that the project engineering for the DP master already exists (for example STEP 7 project with the configuration of the S7 station). If the DP master is a PC station instead of a S7 station, the project engineering can also be created with NCM PC. In chapter 2 Configuration of the PC station is described the configuration of the PC station so that you can use it as DP slave on a S7 station, which works as DP master. V1.0 10.03.2008 3/20

2 Configuration of the PC station After successful completion of the hardware and software installation of the SIMATIC NET CD and the configuration tool and after restarting your computer, you start NCM PC or STEP 7 with "Start (in Windows XP: All Programs ) SIMATIC SIMATIC Manager or SIMATIC NCM PC Manager or using the desktop icon of the same name. Open the STEP 7 project with the configuration of the S7 station as DP master. Figure 2-1 opening STEP 7 project Confirm the selection of the project (in the example: "S7300") with OK. The project is opened. V1.0 10.03.2008 4/20

Figure 2-2 inserting the PC station With the menu command "Insert Station SIMATIC PC-Station" you insert the PC station. Figure 2-3 changing the name of the PC station V1.0 10.03.2008 5/20

Give the PC station you have just inserted the same name as your computer (in the example: "PC_Station"). Now open the hardware configuration of the PC station by selecting the PC station, then pressing the right mouse button and selecting "Open Object". Figure 2-4 hardware configuration of the PC station You will see an empty rack. If you cannot see the hardware catalog, click on the button marked in red. V1.0 10.03.2008 6/20

Figure 2-5 selecting the modules from the hardware catalog Now place your PC modules in this rack (for example by dragging them from the hardware catalog). The following dialog appears automatically after you insert the module in the PC station. Figure 2-6 address assignment dialog V1.0 10.03.2008 7/20

You have to configure the DP master and DP slave on the same PROFIBUS network. For this reason select the PROFIBUS network to which the DP master is connected. Figure 2-7 property view of the CP5611 register General Now the CP5611 is connected to the same PROFIBUS network like the DP master. Change to the register Operating Mode in the property view of the CP5611. V1.0 10.03.2008 8/20

Figure 2-8 property view of the CP5611 register Operating Mode Activate the function DP slave, to use the CP5611 as DP slave. In the selection box Assigned application you have to select the entry OPC Server. Confirm the dialog with OK. Figure 2-9 hardware configuration projecting the CP5611 V1.0 10.03.2008 9/20

Select the OPC server in the hardware catalog and then drag it to any slot. Save and compile the configuration with the menu command Station Save and Compile. At that time the DP slave isn t interfaced to a DP master. For this reason the following message appears while saving and compiling the hardware configuration of the PC station. Figure 2-10 inconsistency of the system data The system data only becomes consistent after the PC station has been interfaced to the S7 station. V1.0 10.03.2008 10/20

3 Interfacing the PC station (DP slave) to the S7 station (DP master) Open the existing STEP 7 project with the SIMATIC Manager. Figure 3-1 opening the STEP 7 project The project includes the S7 station and the configured PC station. NOTE In this example is used a S7-300 station as DP master. If a S7-400 station is used as DP master the same procedure is implemental. Open the hardware configuration of the S7 station. In the hardware configuration of the S7-300 CPU you have to double-click on the interface DP. The property view of the DP interface opens. Change to the register Operating Mode and activate the function DP master. Confirm the property view of the DP interface with OK. V1.0 10.03.2008 11/20

Figure 3-2 hardware configuration of the S7 station In the hardware catalog got to PROFIBUS DP Configured Stations and select the PC station as DP Slave object. Following drag and drop the selected object to the configured PROFIBUS DP master system. The dialog for connecting the PC station to the DP master is displayed. Click on the button Connect and confirm the dialog with OK. V1.0 10.03.2008 12/20

Figure 3-3 connecting the PC station to the DP master Now select the PC station you just inserted. An empty slot table appears. In this example two universal modules are inserted in the empty rack table of the PC station. V1.0 10.03.2008 13/20

Figure 3-4 Specifying inputs and outputs for the DP slave Double-click on the inserted universal module in the slot table. Parameterize the universal module as output with 16 bytes length and the other universal module as input with 16 bytes length. Rules In the configuration data of the universal modules use only "Byte" as the unit. In the configuration data of the universal modules, use only "Unit" for the "Consistent over:" setting. Do not enter any empty modules. The maximum data length per module is 16 bytes. A maximum of 122 bytes inputs and maximum 122 bytes outputs are permitted in total. A maximum of 32 sub modules are permitted. V1.0 10.03.2008 14/20

Figure 3-5 configuring universal modules Save and compile the configuration with the menu command Station Save and Compile. Download the configuration into S7-300 station with the menu command PLC Download. After completing the download, close the hardware configuration of the S7-300 station. Following open the hardware configuration of the PC station. Save and compile the configuration of the PC station with the menu command Station Save and Compile. Download the configuration into PC station with the menu command PLC Download to Module. Exit the hardware configuration of the PC station. V1.0 10.03.2008 15/20

4 Start of the OPC Scout Start the OPC Scout with "Start SIMATIC SIMATIC NET OPC Scout". Double-click the OPC.SimaticNet for connection with the SIMATIC NET OPC server. In the dialog that appears, enter a suitable group name and confirm this with OK. Figure 4-1 connecting with the OPC server and enter a group name Double-click the OPC group which you have created. The "OPC-Navigator" opens. You will now see your protocols in the OPC Navigator. Double-click on "DP". The configured DP connection appears. V1.0 10.03.2008 16/20

Figure 4-2 OPC-Navigator Double-click on the configured DP-Slave, which means double-click on CP5611. You can see all objects which can be accessed. Figure 4-3 objects in the OPC-Navigator V1.0 10.03.2008 17/20

In the OPC-Navigator select the inputs Eingänge _I and move the existing item to the right-hand window with the button. Figure 4-4 defining itms for the inputs of the DP slave In the OPC-Navigator select the Outputs _Q and move the existing item to the right-hand window with the button. Figure 4-5 defining items fort he outputs of the DP slave Exit the OPC-Navigator with OK. The items are applied in den OPC Scout. If the quality of the created OPC items is good, your connection between PC station and S7 station is established. So it s possible to read and write respectively the OPC items. V1.0 10.03.2008 18/20

Figure 4-6 OPC Scout Double-click on the box value of the defined Input-Item to write values into S7 station. V1.0 10.03.2008 19/20

5 History Version Date Changes V 1.0 10.03.2008 First Issue V1.0 10.03.2008 20/20