Wireless Sensor Adapter (WSA10) Installation Instructions

Similar documents
Wireless Fixture Adapter (WFA100-SN) Installation Instructions

Wireless General Purpose Adapter (WGA100) Installation Instructions

Wireless Adapter (WA100-PM) i. Installation Instructions

Wireless Area Controller (WAC60)

Satellite INSTALLATION GUIDE

Wireless Area Controller (WAC50) i. Installation Instructions

PRO-HC IRRIGATION CONTROLLER

PACKAGE CONTENTS SPECIFICATIONS

SuperBus 2000 Phone Interface/Voice Module Installation Instructions

Hardware Installation 1. Install two AA batteries in the mouse. Pairing Process in Vista and Windows XP SP2

Mounting and Operating Instructions (Simple Programming) Art.No..: , published: 10/2003

USER GUIDE. Element Wireless Smart Plug Model: E1C-NB6

ZIPATILE. Quick Start Guide v.1.1

Welcome. Touch 1 (844) LIGHTCLOUD

1101 Universal Transmitter

Laser Stakes. FarmTek. Laser Positioning System For Barrels and Poles. User s Manual. Sport Timing Specialists

Contents Safety precautions Product components Optional accessories Names of each parts Product Dimension Cables and Connectors Power Connection

ATP1000 Touchpad/Display Installation Instructions

WavePRO Wireless Programmable T2500 Thermostat & R2500 Receiver OPERATING MANUAL. Model K

INSTALLATION INSTRUCTIONS

DELORME PowerPack for Earthmate GPS with Bluetooth GPS 9822

Installation Instructions Installation Guidelines. Product Summary. For the maximum number of bus devices and touchpads per panel see Table 1.

PACKAGE CONTENTS SPECIFICATIONS PRODUCT DIAGRAM

User Manual. Smart Dimmer Switch. Part 1: General Specification Main Features... 2

RAINWATCH WIRELESS RECEIVER WIRING

*520886* IntelliTouch Pool & Spa Control System MobileTouch Wireless Controller. User s and Installation Guide. P/N Rev A

WIRELESS BLUETOOTH BOOMBOX

Handset Charging Rack OpenStage WL 3 / OpenStage WL3 Plus. Installation Guide A31003-M2000-J

Chicony Standard Bluetooth Keyboard Users Manual. Model No.: KT-1063

Z-Wave Ceiling-mount Smoke Detector HZS-200E/HZS-200A

InnoMedia ipbx-400. Quick Install Guide.

ZIPATILE. Quick Start Guide v.1.3

The Solution. Multi-Input Module IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

NA502S Multiple RF Home Gateway

HomePro ZRF113. Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2

Bluetooth Mini Keyboard. User s Manual. Version /05 ID NO: PAKL-231B

USER GUIDE. Smart Wi-Fi LED Bulb (2700K and 5000K) Model: W11-N11

Control different load types with one device

User Manual. eufy Security SpaceView Baby Monitor

DECOFLEX WIREFREE RTS SWITCH

Home Security Camera icamera-1000

SleepMinder TM Non Contact Sleep Monitoring

AX3000 Platine Terminal Ethernet TCP/IP

TV WIRELESS HEADPHONES

PWRguard PLUS Spring City Drive Waukesha, WI

MobilePro Users Guide Page 1 of 35. MobilePro HPC. User's Guide. Notices Proprietary Notice and Liability Disclaimer Table of Contents

Monoprice Harmony Bluetooth Wireless Speaker. User Guide P/N 33827

MXHP-H500 (Hub) Owner s Manual v.1.0

Documentation on all Paxton products can be found on our web site -

SySTIUM TECHNOLOGIES. Assembly Guide. Model 133i

SPK User Manual. 900MHz Wireless Stereo Headphones INTRODUCTION FEATURES IMPORTANT SAFETY INFORMATION

W Remote Control 1

Tabel of Content. What s in the Box 01. Feature Introduction 02. Setting Up the Camera and Monitor 03. Replacing the Camera lens 11.

NA502 Multiple RF Home Gateway

Telephone Line Monitor USER GUIDE

PRODUCT DIAGRAM PACKAGE CONTENTS

Wireless Wall Switch Guide

Bi Directional Wireless IR Repeater System User Guide

Bluetooth Micro Dongle User s Guide. Rating: 5V DC 80mA Made in China

Wireless Lighting Control. On/Off. Outdoor Module.

COMMERCIAL. VAM24-90-(A) Series Installation Instructions

REMOTE CONTROL INSTALLATION & OPERATING INSTRUCTIONS

Wireless Outlet User Manual

AX3000 Platine Terminal Ethernet TCP/IP

SANnet II Family Safety, Regulatory, and Compliance Manual

RV CONTROL AND MONITORING SYSTEM Installation and Operation Manual. Patent # US 9,679,735

Wireless Bluetooth Music Receiver

9362 Enterprise Cell V2.2 WCDMA B2/B5. Getting Started Guide

Z-Wave 4-in-1 Multi Sensor HZS-300E/HZS-300A

Quick Start Guide.

FEMTOCELL MULTI-BAND SOHO B2/B4 (SS2FII)

EasyIO FW 08VUser Reference

DH GHz Digital Wireless Headphone. User s Manual. Please read before using the equipment. Please visit for details.

Active RFID Reader User Manual

DVI KVM Switch user manual Model

Prime bolt User Manual

HARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide

Wireless Temperature Module

Operation Manual for Cloud 3700F Version 0

USER MANUAL. Model NAME : Anker USB 2.4G Wireless Vertical Mouse MODEL NO. : A VERSION : 0.1 DATE : A User Manual VER: 0.

Monnit Wireless Sensors. and Ethernet Gateway Quick Start Guide

+Cam Quick Start Guide

elise 3 embedded linux server including safety instructions

Installation Guide AVA-2902E/I. PCI-to-Fast SCSI Host Adapters. PCI SCSI Host Adapter with Internal or External Connector

WHAT YOU LL NEED TO BEGIN:

A0326. ARIA Audio Streaming Source Receiver with a built in Bluetooth 4.2 Module. ARIA Audio

Cube Camera with Fixed Lens Hardware Manual D11, D12. Ver. 2013/05/17

INSTRUCTIONS. A0325 ARIA Audio Streaming Source Receiver with built-in Bluetooth 4.2 Module MADE IN THE USA 2017 CHANNEL VISION TECHNOLOGY

Deluxe In/Out Remote Thermometer with Trend Chart

ADVANCED REMOTE CONTROL

LPWWS Smart Wi-Fi Wall Station

Power Hub Cat. No. 83A00-1. Installation Manual WEB VERSION

Installation Instructions

Allworx Tx 92/24 Telephone Expander Installation Guide

4 Channel RFID reader LF 125KHz with CAN bus LT-LFS03 USER MANUAL

Wireless Lighting Control Duplex Receptacle

56-A11A Plantronics Calisto Headset with Bluetooth USB Adapter. User Guide

PUSH-TO-TALK USER GUIDE

Miccus Home RTX Long Range Wireless Audio Transmitter or Receiver

Datasheet DFBM-NQ62X-DT0R. A Bluetooth Low Energy System On Chip Module. Proprietary Information and Specifications are Subject to Change

Transcription:

(WSA10) Installation Instructions The Daintree Networks WSA10 is a control component within ControlScope. The WSA10 enables open, standards based ZigBee wireless control communications with a variety of sensor devices used in HVAC systems. The WSA10 provides up to four (4) thermistor temperature sensor inputs for temperature monitoring and logging, and up to two (2) 0-1 analog inputs suitable for connection to a broad range of transducers, enabling wireless control and management of wired end-devices within the ControlScope system. Installation Process 1. Disconnect power to the power supply before installation. Confirm that power is off before continuing. 2. IMPRTANT: Use the provided Plan label to identify the wireless-adapted sensor location on the building s floorplan. 3. Mount the WSA10 on a flat surface in the HVAC packaged unit, or in the facility s electrical/mechanical room. See Mounting. 4. Connect low voltage wiring between the WSA10 and the power supply and sensors as appropriate. Connect the sensor cable shield drain wire as appropriate. Improper connection of the shield drain may cause incorrect or unstable sensor readings. See Wiring. 5. Check wiring then restore power to the power supply. 6. Ensure the WSA10 green LED is n. 7. Press and hold the Reset button on the WSA10 for 3 seconds to reset the unit. Release the button when the green Joined LED and the red Error LEDs begin flashing. LED Indicators Fig. 1: LED indicators Error/Reset n when the Adapter is in an error state. Flashes to indicate unit Reset (red). Joined n when the Adapter has joined a ZigBee network. Flashes to indicate Reset (green). n when power is applied to the Adapter (green). IMPRTANT: Reset the WSA10 as described above after adding sensors or making any change to wiring connections. LED Joined LED Error LED 1 DT104 (Rev. 12.8.17)

(WSA10) Wiring Fig. 2: WSA10 terminal connections 0-1 sensors and thermistors, using a DC Drain 1 Shield DC Drain DC Shield 2 10K Type 2 (1) 10K Type 2 (1) 4 4 IN 1 (Analog ) 0-1 2 (Analog ) 0-14 IN 0-1(Reference IN 1 (Analog ) GND ) IEEE Address: Adapter 0-1 IN 2 (Analog ) AC/DC GNDAC/DC (Reference ) : AC/DC; Current: 10mA :gage: AC/DC; Current: 10mA Wire 24-16 AWG D NT PEN DEVICE 21 12 23 32 3 Fig. 3: WSA10 terminal connections for 0-1 sensors and thermistors, using a WFA100-SN for DC NTE: WFA100-SN is inside an approved electrical fiture, or enclosure to provide double insulation of the line voltage wiring. Drain 10K Type 2 (1) 10K Type 2 (1) Drain 0-1 1s 1 4 4 IN 1 (Analog ) 0-1 2 (Analog ) 0-14 IN 0-1(Reference IN 1 (Analog ) GND ) 2 0-1 IN 2 (Analog ) AC/DC GNDAC/DC (Reference ) Adapter RED ( ut) RED ( ut) GRAY (/) GRAY (/) 120/277VAC Line Voltage Neutral : WHITE output: 35mA maimum Drain Drain 1 10K Type 2 (1) 10K Type 2 (1) 4 1 (Analog ) 0-14 IN 2 (Analog ) 0-14 IN 0-1 IN 1 (Analog ) GND (Reference ) 0-1 IN 2 (Analog ) AC/DC GND (Reference AC/DC ) : AC/DC; Current: 10mA Wire 24-16 AWG :gage: AC/DC; Current: 10mA Internal Backup: AA 3.6V Li-SCl2 D NT Ba PENryDEVICE 23 23 3 3 21 21 23 23 3 ( power output) RED BLACK Hot BLACK - (/Common) ( power output) RED BLACKNeutral Hot WHITE WHITE Neutral Line Voltage Wires Line Voltage Wires 21 21 BLACK 2 DC DC WFA100-SN output: 35mA maimum WFA100-SN 120/277VAC : 120/277VAC Line Line Voltage Voltage Hot Neutral : BLACK WHITE 120/277VAC Line Voltage Hot : : AC/DC; Current: 10mA :gage: AC/DC; Current: 10mA Wire 24-16 AWG D NT PEN DEVICE Hot 120/230/277VAC BLACK 14AWG Hot 120/230/277VAC BLACK 14AWG - (/Common) BLACK WA100-family WGA100 DIP Switch Setting after connecting to the WSA10: Range Etender Range Etender If all devices are removed, or this is a new unit connected only to the WA100-family For an eisting WA/WGA unit with other All FF WGA100 DIP Switch Setting after connecting to the WSA10: WSA10, set switches for Range Etender mode and reset the unit. devices attached, leave switches as-is. Range Range 4 5 6 1 2 3Etender 4 5 6 N 1 2 3Etender N2 If all devices are removed, or this is a new unit connected only to the For an eisting WA/WGA unit with other All FF WSA10, set switches for Range Etender mode and reset the unit. devices attached, leave switches as-is. N1 2 3 4 5 6 N1 2 3 4 5 6 DC WGA100 or WA100 product family DC

Drain 10K Type 2 (1) 4 0-1 IN 1 (Analog ) 0-1 IN 2 (Analog ) GND (Reference ) : AC/DC; Current: 10mA 2 3 (WSA10) RED ( ut) DC GRAY (/) WFA100-SN 120/277VAC Line Voltage Neutral : WHITE 120/277VAC Line Voltage Hot : Wiring continued output: 35mA maimum BLACK Fig. 4: WSA10 terminal connections for 0-1 sensor and thermistors, using a WGA100 or WA100-family adaptor for DC Drain 10K Type 2 (1) 4 0-1 IN 1 (Analog ) 0-1 IN 2 (Analog ) GND (Reference ) : AC/DC; Current: 10mA 2 3 ( power output) RED BLACK Hot - (/Common) BLACK WHITE Neutral WA100-family DIP Switch Setting after connecting to the WSA10: Range Etender If all devices are removed, or this is a new unit connected only to the For an eisting WA/WGA unit with other WSA10, set switches for Range Etender mode and reset the unit. devices attached, leave switches as-is. N1 2 3 4 5 6 Line Voltage Wires Hot 120/230/277VAC BLACK 14AWG WGA100 Range Etender N1 2 3 4 5 6 All FF DC WGA100 or WA100 product family WHITE 18AWG Neutral J-Bo or Equivalent output: 75mA maimum Low Voltage Wires RED 14AWG Switched load Cap unused wires Fig. 5: WSA10 terminal connections for 0-1 sensors and thermistors, using an AC adaptor for DC To reduce AC noise on the sensor signal line, install the AC to DC power supply near the WSA10, rather than near the sensor(s). Shield AC to DC Drain AC 10K Type 2 (1) Locate near WSA10 4 0-1 IN 1 (Analog ) 0-1 IN 2 (Analog ) GND (Reference ) AC 4-20mA s Shield 4-20mA 4-20mA - : AC/DC 2 3 AC *or AC supply from HVAC packaged unit DC Drain 10K Type 2 (1) 4 3 0-1 IN 1 (Analog ) 0-1 IN 2 (Analog ) : AC/VDC (10mA) 2

AC to DC Shield 0-1 s Shield AC to DC AC Drain 10K Type 2 (1) Drain 10K Type 4 2 (1) (WSA10) Locate near WSA10 AC 0-1 IN 1 (Analog ) 0-1 IN 2 (Analog ) GND (Reference ) 4 0-1 IN 1 (Analog ) Adapter 0-1 IN 2 (Analog ) Locate near WSA10 AC AC Wiring continued 2 : AC/DC 3 2 : AC/DC GND (Reference ) *or AC supply from HVAC packaged unit 3 AC Fig. 6: WSA10AC terminal connections for 4-20mA sensors and thermistors, AC supply from HVAC packaged unit using a DC *or adaptor for DC 4-20mA s Shield DC 4-20mA DC 4-20mA s 4-20mA 1 Shield 10K Type 2 (1) 10K Type 2 (1) 4 : AC/VDC (10mA) 2 0-1 IN 1 (Analog ) 0-1 4 IN 2 (Analog ) GND (Reference ) 4 AC/DC 0-1 IN 1 (Analog ) Adapter AC/DC 0-1 IN 2 (Analog ) : AC/VDC (10mA) 1 3 32 F to 122 F (0 C to 50 C) Temperature: 2 CNTAINS FCC ID: Z6G-DT357 Wire gage: 24-16 AWG GND (Reference ) 3 AC to DC AC 4-20mA s 4-20mA Locate near WSA10 1 Shield AC 4-20mA 4-20mA 4-20mA AC AC 4-20mA 4-20mA - 4-20mA 2 Locate near WSA10 AC 10K Type 4 2 (1) 0-1 IN 1 (Analog ) 0-1 4 IN 2 (Analog ) GND 4 (Reference ) ) 0-1 IN AC/DC 1 (Analog ) 0-1 IN AC/DC 2 (Analog GND (Reference ) 2 : AC/VDC (10mA) 1 3 2 CNTAINS FCC ID: Z6G-DT357 Adapter : AC/VDC (10mA) Fig. 7: WSA10 terminal connections for 4-20mA sensors and thermistors, using an AC for DC To reduce AC noise on the sensor signal line, install the AC to DC power supply near the WSA10, AC to DC 4-20mA s the than near sensor(s). 10K Type 2 (1) rather 1 Shield 4-20mA 4-20mA 4-20mA - 4-20mA 4-20mA 4-20mA 2 Drain 4-20mA Drain 3 *or AC supply from HVAC packaged unit AC *or AC supply from HVAC packaged unit CAUTIN: Risk of electrical shock Disconnect all power before installation. Wiring connectors are not supplied. UL recognized wiring connectors must be used in the installation. Each terminal can accept one conductor only. Connect only one 24AWG to 16AWG wire to any terminal. All installation and maintenance of line voltage equipment must be performed by a qualified electrician. The WSA10 must be installed in accordance with all local, state, and national electrical codes and requirements. If the sensor cable includes a shield, terminate the end closest to the WSA10 as shown in the applicable wiring diagram Follow sensor manufacturer s instructions and recommendations for all sensor connections CLASS 2 WIRING: All field wiring shall be suitable for Class 1, Electric Light and, or Class 2, 3 wirings are routed separately and secured to maintain separation between: 1) Class 2 wiring and all other class wiring, and 2) limited energy circuit conductors from unlimited energy circuit conductors. 4

(WSA10) Mounting The WSA10 is designed to be mounted to a flat surface using two screws. Alternatively, the mounting tabs at the end of the WSA10 enclosure can be snapped off with pliers to make the unit length up to 0.63 (3/4 or 16mm) smaller to fit into tighter spaces. The grooves on the mounting tabs mark the snap-off point, approimately 3/8 (8mm) from each end of the unit. Note that when the tabs are removed the mounting holes are lost, so the unit has to be mounted or affied by other means, such as permanent double-sided adhesive tape. Fig. 8: Mounting Template (observe measurements, illustration may not be actual size).for DC verall Length: 7.0275 (178.5 mm) Diameter: 0.1574 (4.0mm) Diameter: 0.1574 (4.0mm) verall Width: 1.1811 (30 mm) Center from edges: 0.5905 (15 mm) Centers: 6.6929 (170 mm) Important Notices Record IEEE Addresses If you have not already done so, be sure that each WSA10 s IEEE address (last 4 or 5 digits) is recorded on the facility floor plan. You can use the 4 or 5 digit Plan label supplied with the WSA10 or you can write the last 4 or 5 digits on the floor plan. This information will be used during the commissioning process. After the system installation is complete, a marked-up copy of the facility floor plan showing the identity and location of each wireless adapter (including associated sensors) should be available. This will simplify and epedite the commissioning process. Joining the Zigbee Network After the WSA10 is powered-up, it is ready to communicate with the Daintree Area Controller (WAC) and the Daintree ControlScope Manager (CSM) webbased user interface. Upon commissioning, the WSA10 Join LED turns on solid and remains on as long as the WSA10 is included in the ZigBee Network. After joining the network, signals from the low voltage devices connected to the WSA10 pass through the WSA10 and are sent wirelessly to the ControlScope network. For more information about configuring the system, see the instructions and on-line help provided with the ControlScope Manager application. 5

(WSA10) peration with ControlScope Manager nce joined to the ZigBee network, the WSA10 and its connected devices are assigned to zones using the Zone and Device Configuration page. Notice that each connected input is listed as a separate device. The Device ID and Model columns include terminal identifiers for each connected device. These identifiers are automatic and carry over to both the Devices page and Zone Temperature Logging reports. Each connected input is also assigned a Device Profile, which determines if an alarm is generated when the sensor reports a reading outside of the designated range. Reports The Zone Temperature Analysis report displays temperature and time as reported by a temperature sensor or thermostat. It also displays a histogram representing the time spent at various temperatures over the report time period. When a time is selected on the histogram, the number of hours spent above or below the selected temperature also displays. 6

(WSA10) Alarms An input s Device Profile can be configured to generate a threshold alarm when a temperature is outside of designated limits, as shown below. When an input is shorted or open, a failure alarm is raised against the device, as shown below. Alert Emails An Email Rule can be set up to automatically send an email when a temperature alarm is generated, or when other alerts occur. See Email Alert Rules in the CSM online help for more information. 7

(WSA10) FCC warning message This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and radiates radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encourage to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna; Increase the separation between the equipment and receiver; Connect the equipment into an outlet on a circuit different from that to which the receiver is connected; Consult the dealer or an eperienced radio/tv technician for help. Specifications Voltage Battery Backup perating Life: Battery Life: s AC/VDC (10mA) Type: AA 3.6V lithium thionyl chloride, internal, not replaceable 7 years or more Min. 5,000 hours (@25oC op. temp), Backup operation only Resistance: (4), 10K Type 2 Accuracy: Voltage: Accuracy:: Radio Properties perating Environment Compliance Mounting Dimensions /- 0.5oC @-10oC to 45oC (14oF to 113oF) /- 1oC @-30oC to 65oC (-22oF to 149oF) (2) 0-1DC /- 2% of span (without calibration) 2.4 GHz, 8 dbm, Range dependent on RF propagation variables Relative humidity 5% to 95%, non-condensing Temperature: 32o to 122oF (0o to 50oC) US: FCC Part 15 Canada: IC Wall, ceiling, enclosure screw mount 1.18 W 0.98 H 7.03 L (30mm W 25mm H 178.5mm L) Industry Canada (IC) Warning Message Product complies with Part 15 of the FCC Rules. peration is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. CAN ICES-005 B / NMB-005 B ControlScope Manager compatibility Release version 3.1 or later Call 1 888 694 3533 products.currentbyge.com GE is a trademark of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. Current and GE Lighting are businesses of the General Electric Company. 2017 GE 8