MiCOM Px3x Series. Self Monitoring. Supplementary Functional Description

Similar documents
MiCOM P122C Time-Overcurrent Protection

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P111. Three phase and earth fault overcurrent relays

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

Zelio Logic 2 Online Help

MiCOM E2. Self Powered Converter USB / RS232 E2/EN FT/A11. User Guide. Software Version USBPx20 V1.01

PowerLogic power-monitoring units. iem3000 Series. Technical data sheet

HighPROTEC Troubleshooting Guide

This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays.

VIP 40/45 VIP 400/410

plc operation Topics: The computer structure of a PLC The sanity check, input, output and logic scans Status and memory types 686 CPU

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

Three phase and earth fault overcurrent relays

Modicon Premium PLCs TSX CSY 84 / 85 / 164

MiCOM P12x/y. Three phase and earth fault overcurrent relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

MiCOM Pxxx PRP. Pxxx/EN PR/B11. Update Documentation. Version Software Version See Table 2 Hardware Suffix See Table 2

IEC Engineering Process and Multi-Vendor System Configuration Tools Reduce Engineering Costs of Substation Automation Projects

L01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!

SIOX Four I/O Mini Module

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Protection Relays PHASE & RESIDUAL OVERCURRENT

Galaxy Shore Connection 500 kva. Operation 04/

Technical Manual. KNX/DALI ACTUATOR 1x8 channels Art /70100

HighPROTEC Troubleshooting Guide

PowerLogic communication devices. EGX100 Ethernet gateway EGX300 Integrated gateway-server. Technical data sheet

6-1-6 Types of Errors

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Intecom. March

Maximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays

Technical Manual. DALI GATEWAY Art A

CLSM3 Online Help. Overview of the programming workshop. Overview of the programming workshop. Overview of the Programming Workshop.

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

General characteristics of C-type relay modules

Model IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08

Smart Mode Measurements

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Acti 9 Communication System

ENABLE / DISABLE: ZONES, DEVICES, CIRCUITS, COMMUNICATION SENSE, RESET HI-LO LEVELS, WALKTEST DIAGNOSTICS

E-Series Troubleshooting Guide

COUNTIS ATv2/ATiv2 GB

AN5013 Application note

Figure 1. LCD & Keypad - RS232 Terminal

PACiS SPP DNP3. Gateway and C264 SPP/EN DNP3/D10. Slave Protocol Profile DNP3. Issue A1. PACiS V5

MultiTech Router Commissioning for Com X 200/210/510

Data communication and reporting unit

Protection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW

MODBUS Protocol for MiCOM P30 Series

Operating instructions Addressing unit AC1144

TFS 2100 Traveling Wave Fault Location System

1. Introduction. Be sure to read the release notes in section 10 before operating the Unit.

Test ROM for Zaccaria 1B1165 CPU Board

PowerLogic High Density Metering System 1-Meter Enclosure

DUAL PLATE D630 Installation and Maintenance en / a

User Manual. AQ-F215 Simulator

EL731 PROFIBUS INTERFACE

Troubleshooting & Repair

AFRecorder 4800R Serial Port Programming Interface Description For Software Version 9.5 (Last Revision )

FAULT TOLERANT SYSTEMS

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

eloprog 485EPF.. - Vers. 1.2 eloprog Configurable safety system FIELD BUS MODULES

FERGUSON BEAUREGARD. RTU-5000 Configurator User Manual

LENGTH-ANGLE-RADIUS-LOAD INDICATING SYSTEM

STEP 7 PROFESSIONAL. Function STEP 7

Data communication and reporting unit

SIPROTEC 5 Application Note

A66N2 Installation and Programming Manual

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:

SECTION 5 RESETS AND INTERRUPTS

STEP 7. Function. Page 1791 Mar 2008 Siemens ITS

Aotewell SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St

Change Report Colors and Logo

PowerLogic ION7550 RTU option

NEC 78K0- Family On-Chip Emulation

Electrical network protection Sepam series 20 Sepam series 40 Quick start

TeSys U Communication Variables

Power quality enhancements for IEC 61850

Operating instructions Diagnostic electronics for vibration sensors VSE002 / VXE002 / VXE003 VYE001 / VYE002 / VYE003 / VYE /01 05/2015

MiCOM P139 Feeder Management and Bay Control

P2M2HBVL12400xxx USER MANUAL.

TIA Portal Workshop. Unrestricted. Siemens AG All rights reserved.

Generator Performance Guide 7EN /2015

176 Diagnostics WAGO-I/O-SYSTEM Programmable Fieldbus Controller ETHERNET

Serial Communications Guide

DEH-433. Warnings, Cautions, and Notes as used in this publication

The TPU-2000R unit comes enclosed in a metal case. Follow the instructions and diagrams in this section to install the TPU-2000R.

Environmental Chamber Programmer/Controller

Let reliability and flexibility be your drive. Linergy. Distribution and connection systems from 0.5 A to 4000 A

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

Modbus Remote Communication Protocol for REM 54_. Technical Description

Boost your productivity. by upgrading your Modicon Compact 984

SIMATIC. ET 200S IM CPU Interface Module. Introduction. New features 2. Technical specifications 3. Product Information 06/2007 A5E

ACCESS 9340/9360 Meter Input/Output Module

PM130 Powermeters Reference Guide Modbus Communications Protocol

INSTRUCTION MANUAL V1. 2x A

EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted

Transcription:

MiCOM Px3x Series Self Monitoring Supplementary Functional Description Issue: 02b Release: 11 / 2011

[Self-Monitoring] MiCOM Px3x Series 2 The following document is intended to clarify the Px3x self-monitoring philosophy. It is based on the description of the self-monitoring function of Px3x devices in the technical user manuals. Self-Monitoring (Function Group SFMON) Tests during start up Comprehensive monitoring routines in the Px3x ensure that internal faults are detected and do not lead to malfunctions. After the supply voltage has been turned on, various tests are carried out to verify full operability of the Px3x. - Check memories (RAM write/read test) - Checksum test (calculate actual ROM checksum and compare with stored checksum) - Check hardware (test real time clock, test counters, test A/D converter) - Check bus and fitted modules (identify device type, verify correct modules fitted: type/version/location) - Check intelligent devices on fitted modules (if applicable) (write/read DPRAM on communication modules or transient ground fault module) - Check software (compare compatibility of device type, data model information, processor operating system and protection and control software) If the Px3x detects a fault in one of the tests, then start up is aborted. The display shows which test was running when termination occurred and -if applicable- the address of the faulty memory area, e.g. ERROR 9 03C80000H. Error number (nn) Description 1 4 RAM error (with HW address) 5 Static RAM error (with HW address) 6 Non-volatile RAM (NOVRAM) error of setting parameters (with HW address) 9 16 Flash-Eprom checksum error of device firmware (with HW address) 17 Error of timer / clock 82C54 18 Error of analog to digital (A/D-) converter 19 Flash-Eprom checksum error of bay templates (only OBS & Cx3x devices; with HW address) 30 Wrong data model version 31 Wrong version of operating system irmx386 32 Wrong software versions (combination) of protection, local operation (HMI) and communication (COMM1/2). 33 Wrong control software version (only OBS & Cx3x devices) If such error occurs and is shown on the HMI display, no control actions can be carried out. A new attempt to start up the Px3x can only be initiated by turning the supply voltage off and then on again.

[Self-Monitoring] MiCOM Px3x Series 3 Cyclic tests After startup has been successfully completed, cyclic self-monitoring tests will be run during normal operation with a cycle time of 10 s. These tests comprise: - Timeout check of protection task - Check of internal battery voltage - Checksum test of recording buffers - Checksum test of setting parameters - Checksum test of monitoring buffer - Continuity tests of output relay coils. In addition, errors (exceptions) detected by the main processor are immediately/directly handled by the operating system, e.g. zero division error or undefined op.code. Tests of external signals/ wiring are done as part of the protection tasks, e.g. monitoring of VT and CT measuring circuits or telecommunication channel of the protective signalling. System alarms and errors Self-monitoring distinguishes between system alarms and system errors. System alarms do not affect the protection and control task and therefore the device remains in operation. As an example, overflow of communication buffers or a low voltage of the internal battery result in an alarm only. System errors affect the protection and control function and require further processing. At the first instance the device will perform a warm restart to recover from the error. Was the error already present before (= already entered in the monitoring signal memory), then the device will get blocked (0 0 4. 0 6 5 M A I N : B l o c k e d / f a u l t y = y e s ). Examples for system errors are checksum errors, defective module errors etc. Both, alarms and errors, could be either spontaneous (which means that only the occurence of the alarm/error could be detected, e.g. any checksum error) or testable (which means start and end of the alarm/error condition could be detected, e.g. defective output relay). Peripheral faults like a fuse failure condition are always testable alarms.

[Self-Monitoring] MiCOM Px3x Series 4 Monitoring signal memory In the event of a positive test result, a specified monitoring signal will be issued and stored in a non-volatile memory the monitoring signal memory. Peripheral faults are only stored if selected by the user (setting parameter 021.030 SFMON: Fct. assign. warning). The monitoring signal memory can store up to 30 signals. The 30 th entry is always the overflow signal (0 9 0. 0 1 2 S F M O N : O v e r f l o w M T _ R C = y e s ). If 30 entries are present, no further new signals could be stored, where new means that this signal is not yet entered in the memory. If a monitoring signal is already entered in the monitoring signal memory, then just the counter of the entry is incremented (e.g. transient errors on the transmission channel of the protective signalling thus would cause only one signal entry). Each entry contains the following information: - Address and description text of the warning signal. - Date and time of the first occurence of the error. - Counter of detection of the error. - Flag updated = yes: the error is still present; = no: the error is no longer present. Spontaneous alarms/errors are always indicated as updated = yes. - Flag acknowledged = yes: the warning was already acknowledged, but the error is still present; = no: the warning was not yet acknowledged. Device response The response of the Px3x is a function of the type of monitoring signal. The following responses are possible: Signaling Only If there is no malfunction associated with the monitoring signal (= upon system alarms), then only a signal is issued, and there are no further consequences. This situation exists, for example, when internal data acquisition memories overflow or if the internal battery voltage is low. Selective Blocking If a system error is diagnosed solely in an area that does not affect the protective functions, then only the affected area is blocked. This would apply, for example, to the detection of a fault on the communication module or in the area of the PC interface or if an individual output relay is faulty. Warm Restart If the self-monitoring function detects a system error that might be eliminated by a system restart such as a hardware error, e.g. DPRAM read error, or a software error, e.g. zero division error, then a procedure called a warm restart is automatically initiated. During this procedure, as with any startup, the computer system is reset to a defined state. A warm restart is characterized by the fact that no stored data and, in particular, no setting parameters are affected by the procedure. A warm restart can also be triggered manually by a control action. During a warm restart sequence, both the protective functions and communication through serial interfaces will be blocked. Whether or not this measure will suffice can only be determined if the monitoring signal has not already been stored in the monitoring signal memory because of a previous fault. If it was already stored and a second fault is detected then, depending on the type of fault detected, the device will be blocked after the second warm restart. Previously this occurred independently of the time duration that had passed since the first monitoring signal was issued.

[Self-Monitoring] MiCOM Px3x Series 5 Since about 2005, a monitoring signal memory has been implemented in Px3x. The behaviour caused by sporadic faults could lead to an unwanted blocking of the device if the monitoring signal memory has not been reset in the interim, for example, because the substation is difficult to reach during wintertime or reading-out and clearing of the monitoring signal memory via the communication interfaces was not enabled. A timer stage "memory retention time" has been introduced to defuse this problem. Now device blocking only occurs, when the same internal device fault is detected twice during this time duration. Otherwise the device will continue to operate as normal after a warm restart. In the default setting this timer stage is blocked so that with a detected internal fault the device will operate the same as the previous versions. Note: Because of these changes the significance of the time tag for entries to the monitoring signal memory has been re-defined. The date and time when the device fault occurred first was previously recorded. As of versions with the settable "memory retention time" the date and time when the device fault occurred last is now recorded. Cold Restart If corrupted settings are diagnosed during the checksum test, which is part of the self-monitoring procedure, then a cold restart is carried out. This is necessary because the unit cannot identify which parameter in the subset is corrupted. A cold restart causes all internal memories to be reset to predefined default values. This means that all device settings are also erased after a cold restart. The settings that then apply are the underlined values given in the column headed Range of Values in the Address List. In order for a safe initial state to be established, the default values have been selected so that the protective functions are blocked. Both the monitoring signal that triggered the cold restart and the signal indicating parameter loss are entered in the monitoring signal memory. Beside corrupted settings, a cold restart is initiated only after a SW download procedure (either download of a new firmware version or download of a customized data model) or manually (as a means to get the device in a predefined condition). Manual cold restart can only be initiated from the local HMI. The device must be in offline mode. The initiation is password protected. Please refer to chapter 10 Troubleshooting of the Px3x manual, which lists all possible warning signals and the device response/reaction upon detection of each alarm/error.

[Self-Monitoring] MiCOM Px3x Series 6 Device status and signalling The device alarm status is indicated by the following 2 status signals: 036.070 SFMON: Warning (LED) (fixed configured on yellow LED H3) 036.100 SFMON: Warning (relay) (to be configured on any output contact) This state signal indicates, that at least one monitoring signal is entered in the monitoring signal memory. This state does not affect the protection or control function of the device. It is recommended to use this signal to inform operational personnel, that anything is wrong with the device which does not require immediate corrective actions to be taken. The different signals for LED and relay are used for different signalling. The monitoring signal is signalled via - the yellow Alarm LED (or any other LED that is configured for 036.070 SFMON: Warning (LED) ): The LED is blinking while a warning signal is in the monitoring signal memory that is not yet acknowledged. If all warning signal in the monitoring signal memory are acknowledged (but still actual/present) than the LED is permanently on. - an output relay that is configured for SF M O N : W a r n i n g ( r e l a y ). The output relay operates as long as any warning signal is stored in the monitoring signal memory. - any communication interface (COMMx, PC, HMI). 021.030 SFMON: Fct. assign. warning can be used to determine, which peripheral faults are also stored in the monitoring signal memory and consequently raise the warning signal. This is intended to inform the operational personnel about the peripheral fault so that corrective actions (like repair of VT circuit) could be scheduled.

[Self-Monitoring] MiCOM Px3x Series 7 004.065 MAIN: Blocked/faulty This state signal indicates, that the device is out of operation (all protection and control functions are blocked) and therefore should be used for high prior alarming of operational personnel to take immediate/urgent corrective actions. This state is active, if 1) The device is determined blocked/faulty by the internal self-monitoring due to a system error; 2) The device is switched offline (003.030 MAIN: Protection enabled = No (= off)); 3) The output relays are blocked (021.014 OUTP: Outp.rel.block USER = Yes); 4) The trip command is blocked (021.012 MAIN: Trip cmd.block. USER = Yes). Furthermore an user-defined part of the blocked/faulty signal is available: 021.031 MAIN: Fct. assign. fault determines, which internal alarms/errors (which do not necessarily block the device) shall raise the blocked/faulty signal for high prior alarming of operational personnel. A typical example is to configure the system alarm SFMON: Error Kxx with Kxx being the output relay on which the trip command is configured (because it s a vital problem, if the trip command cannot be issued). Please note that the configuration of any signal to 021.031 does only raise the blocked/faulty signal but does not cause any blocking of protection or control functions. The blocked/faulty status is signalled via - the yellow blocked/faulty LED (or any other LED that is configured for 004.065 MAIN: Blocked/faulty). The LED is on as long as the blocked/faulty state is present. - an output relay that is configured for 0 0 4. 0 6 5 M A I N : Blocked/faulty. The output relay operates as long as the blocked/faulty state is present. It is recommended to use a N/O (normally open) contact for signalling blocked/faulty and to set the operating mode to NE (normally energized) updating. Then the signalling takes place also if the auxiliary supply of the device fails (= normal watchdog contact application). - any communication interface (COMMx, PC, HMI).

2010 Schneider Electric. All rights resereved Schneider Electric As standards, specifications and designs change from time to time, please ask for contribution 35, rue Joseph Monier CS30323 of the information given in this publication. F - 92500 Rueil-Malmaison cedex (France) Tel: +33 (0)1 41 29 85 00 Fax: +33 (0)1 41 29 71 00 RCS Nanterre 954 503w Capital social 896 313 776 ww.schneider-electric.com Design: Schneider Electric Photos: Schneider Electric - MiCOM Px3x Series- Supplementary Functional Description - EN 11 / 2011