PROGRAMMING CONTROLLER ELIWELL IC-915 DUAL CONTROLLER Programming Manual Release Date: July 5, 2006 Publication Number: 33319INS Revision Date: April 03, 2014 Revision: C Visit the Cornelius web site at www.cornelius.com for all your Literature needs.
The products, technical information, and instructions contained in this manual are subject to change without notice. These instructions are not intended to cover all details or variations of the equipment, nor to provide for every possible contingency in the installation, operation or maintenance of this equipment. This manual assumes that the person(s) working on the equipment have been trained and are skilled in working with electrical, plumbing, pneumatic, and mechanical equipment. It is assumed that appropriate safety precautions are taken and that all local safety and construction requirements are being met, in addition to the information contained in this manual. This Product is warranted only as provided in Cornelius Commercial Warrant applicable to this Product and is subject to all of the restrictions and limitations contained in the Commercial Warranty. Cornelius will not be responsible for any repair, replacement or other service required by or loss or damage resulting from any of the following occurrences, including but not limited to, (1) other than normal and proper use and normal service conditions with respect to the Product, (2) improper voltage, (3) inadequate wiring, (4) abuse, (5) accident, (6) alteration, (7) misuse, (8) neglect, (9) unauthorized repair or the failure to utilize suitably qualified and trained persons to perform service and/or repair of the Product, (10) improper cleaning, (11) failure to follow installation, operating, cleaning or maintenance instructions, (12) use of non-authorized parts (i.e., parts that are not 100% compatible with the Product) which use voids the entire warranty, (13) Product parts in contact with water or the product dispensed which are adversely impacted by changes in liquid scale or chemical composition. Contact Information: To inquire about current revisions of this and other documentation or for assistance with any Cornelius product contact: www.cornelius.com 800-238-3600 Trademarks and Copyrights: This document contains proprietary information and it may not be reproduced in any way without permission from Cornelius. This document contains the original instructions for the unit described. CORNELIUS INC 101 Regency Drive Glendale Heights, IL Tel: + 1 800-238-3600 Printed in U.S.A.
Parameter: re1 PROCEDURE TO PROGRAM THE IC-915 CONTROLLER 1. Press and hold the SET button for at least 5 Sec, until you see the re1 prompt, to access the re1 subroutine. 2. Press and release the SET button, the screen should display HC1. 3. Press and release the SET button the screen should display H. A. Press the up arrow ( ) to change to C. B. Press the SET button again to return to HC1. 4. Press the up arrow ( ) the screen should display db1. A. Press the SET button the screen should display 3. B. Press the down arrow ( ) to set at 1. C. Press the SET button again to return to db1. 5. Press the up arrow ( ) the screen should display df1. A. Press the SET button the screen should display 3. B. Press the down arrow ( ) to set at 1. C. Press the SET button again to return to df1. NOTE: For Hot Gas units set df1 to 1 for none Hot Gas units set at 5. 6. Press the up arrow ( ) the screen should display HS1. A. Press the SET button the screen should display 170. B. Press the down arrow ( ) to set at 100. C. Press the SET button again to return to HS1. 7. Press the up arrow ( ) the screen should display LS1. A. Press the SET button the screen should display -67. B. Press the up arrow ( ) to set at 40. C. Press the SET button again to return to LS1. 8. Press the up arrow ( ) the screen should display dn1 B. Press again the SET button to return to dn1. 9. Press the up arrow ( ) the screen should display do1. B. Press the SET button again to return to do1. 10. Press the up arrow ( ) the screen should display di1. B. Press the SET button again to return to di1. 11. Press the up arrow ( ) the screen should display de1. B. Press the SET button again to return to de1. 12. Press the up arrow ( ) the screen should display on1. B. Press the SET button again to return to on1. 13. Press the up arrow ( ) the screen should display OF1. 2006-2014, Cornelius Inc. - 1 - Publication Number: 33319INS
B. Press the SET button again to return to OF1. 14. Press the fnc button to exit the (re1) subroutine. HC1 = H C Heat/Cool mode db1 = 3 1 Intervention 1 band df1 = 3 1 Differential set 1 or 5 HS1 = 170 100 Higher Set LS1 = -67 40 Lower Set dn1 = 1 1 Delay time do1 = 0 0 Delay after switch off di1 = 0 0 Delay between switch-ons de1 = 0 0 Delay between switch off On1 = 0 0 On time OF1 = 1 1 Off time HC1 = C Parameter: re2 1. Press the up arrow ( ) until you see the re2 prompt, to access the re2 subroutine 2. Press and release the SET button, the screen should display HC2. 3. Press and release the SET button, the screen should display H. A. Press the up arrow ( ) to change to C B. Press the SET button again to return to HC2 4. Press the up arrow ( ) the screen should display db2 A. Press the SET button the screen should display 3 B. Press the down arrow ( ) again to set to 1 C. Press the SET button again to return to db2. 5. Press the up arrow ( ) the screen should display df2. A. Press the SET button the screen should display 3. B. Press the down arrow ( ) to set to 1. C. Press the SET button again to return to df2. 6. Press the up arrow ( ) the screen should display HS2. A. Press the SET button the screen should display 170. B. Press the down arrow ( ) to set to 100. C. Press the SET button again to return to HS2. 7. Press the up arrow ( ) the screen should display LS2. A. Press the SET button the screen should display -67. B. Press the up arrow ( ) to set to 40. C. Press the SET button again to return to LS2. 8. Press the up arrow ( ) the screen should display dn2. B. Press the SET button again to return to dn2. Publication Number: 33319INS - 2-2006-2014, Cornelius Inc.
9. Press the up arrow ( ) the screen should display do2. B. Press the SET button again to return to do2. 10. Press the up arrow ( ) the screen should display di2. B. Press the SET button again to return to di2. 11. Press the up arrow ( ) the screen should display de2. B. Press the SET button again to return to de2. 12. Press the up arrow ( ) the screen should display on2. B. Press the SET button again to return to on2. 13. Press the up arrow ( ) the screen should display OF2. B. Press the SET button again to return to OF2. 14. Press the fnc button to exit the re2 subroutine. HC2 = C C Heat/Cool mode db2 = 3 1 Intervention 2 band df2 = 3 1 Differential HS2 = 170 100 Higher Set LS2 = -67 40 Lower Set dn2 = 1 1 Delay time do2 = 0 0 Delay after switch off di2 = 0 0 Delay between switch-ons de2 = 0 0 Delay between switch off On2 = 0 0 On time OF2 = 1 1 Off time HC2 = C Parameter: di5 1. Press the up arrow ( ) until you see the di5 prompt, to access the di5 subroutine. 2. Press and release the SET button, the screen should display LOC. 3. Press and release the SET button the screen should display n. Press the SET button to return to LOC. NOTE: To lock / Unlock Press the up arrow ( ) or the down arrow ( ) to change for y or n. 4. Press the up arrow ( ) the screen should display PA1. 5. Press and release the SET button the screen should display 0. Press the SET button to return to PA1. 6. Press the up arrow ( ), the screen should display ndt. 2006-2014, Cornelius Inc. - 3 - Publication Number: 33319INS
7. Press and release the SET button, the screen should display n. Press the SET button to return to ndt. 8. Press the up arrow ( ) the screen should display CA1. 9. Press and release the SET button the screen should display 0. Press the SET button to return to CA1. 10. Press the up arrow ( ), the screen should display dro. 11. Press and release the SET button, the screen should display F. Press the SET button to return to dro. NOTE: Press the up arrow ( ) to change to C for Celsius. 12. Press the fnc button to exit the di5 subroutine. LOC = n n Key board lock Pa1 = 0 0 Password 1 ndt = n n Number display type (decimal point) CA1 = 0 0 Calibration 1 dro = F F Display read-out select C or F Parameter: CnF 1. Press the up arrow ( ), the screen should display (CnF). 2. Press and release the SET button, the screen should display HOO. 3. Press and release the SET button, the screen should display ptc. Press the SET button to return to HOO. 4. Press the up arrow ( ), the screen should display HO1. 5. Press and release the SET button, the screen should display 0. Press the SET button to return to HO1. 6. Press the up arrow ( ), the screen should display H10. 7. Press and release the SET button, the screen should display 0. Press the SET button to return to H10. 8. Press the up arrow ( ), the screen should display REL. 9. Press and release the SET button, the screen should display 10. Press the SET button to return to REL. 10. Press the up arrow ( ), the screen should display, TAB. 11. Press and release the SET button, the screen should display, 113. Press the SET button to return to TAB. 12. Press the fnc button to exit the CnF subroutine. Publication Number: 33319INS - 4-2006-2014, Cornelius Inc.
HOO = ptc ptc Probe type selection PTC or NTC H01 = 0 0 Outputs link H10 = 0 0 Delay time in activating the outputs after switch on rel = 10 10 Release firmware Read only parameter tab = 113 113 Table of parameter Read only parameter Parameter: Fpr 1. Press the up arrow ( ), the screen should display (Fpr). 2. Press and release the SET button, the screen should display UL. 3. Press and release the SET button the screen should display n. Press the SET button to return to UL. 4. Press the up arrow ( ), the screen should display DL. 5. Press and release the SET button the screen should display n. Press the SET button to return to DL. 6. Press the up arrow ( ), the screen should display Fr. 7. Press and release the SET button, the screen should display n. Press the SET button to return to Fr. 8. Press the fnc button twice to exit the subroutine. UL = n n Up load dl = n n Down load Fr = n n Format Erasing all data in the copy card To set the SET POINT Press and release the SET button the screen should display Re1 Press the SET button the screen should display the SET POINT TEMPERATURE for level 1.Press the up or down arrows ( ) to change the SET POINT. To set the SET POINT Press and release the SET button the screen should display Re2 Press the SET button the screen should display the SET POINT TEMPERATURE for level 2.Press the up or down arrows ( ) to change the SET POINT. Press the fnc button to exit the program. 2006-2014, Cornelius Inc. - 5 - Publication Number: 33319INS