SED2 Variable Frequency Drives

Similar documents
HVAC Products. Introducing the SED2 Variable Frequency Drives

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

SED2 Variable Frequency Drives

SED2 Variable Frequency Drives

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options

BT300 HVAC Drives. Designed for HVAC. Description. Technical Specification Sheet Document No March 4, 2013

Variable Frequency Drives

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

5 MICROMASTER 420 specifications

A drive dedicated to variable speed control for HVAC applications

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

4/8/ nd Annual OTCO WW Workshop W/WW Product Overview ACQ550. ABB Slide 1

Q9 ASD LOW VOLTAGE DRIVE

5 MICROMASTER 440 specifications

PowerFlex 400 AC Drive Guide Specification

ENGINEERED SOLUTIONS. Solutions for Any Application. us.mitsubishielectric.com/fa/en/

PowerFlex 40 Sample Specification

VLT 2800 DRIVE SPECIFICATIONS

SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

It s fun to save. micromaster

TR150 DRIVE STANDARD FEATURES

ADJUSTABLE SPEED DRIVES. Q9 Series

Q-LINK SMART BYPASS. SIZING INFORMATION TABLE Q-Link Variable Frequency Drive - 3-Phase 208 VAC 230 VAC VAC HP FLA HP FLA HP FLA TECHNOLOGIES

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

VFD 4x STAINLESS STEEL ENCLOSURE WITH AC. engineering data and specifications

S-Flex Enclosed Drive

ADJUSTABLE SPEED DRIVES. QX7 Series. HVAC 18-Pulse. Phone: Fax: Web:

S-Flex Enclosed drives

Powered to Perform. Everyday Reliability. Exceptional Value. Expertise and Support

Built-in features Built-in simplicity Built for fans & pumps

Easy To Use OEMS Take Note

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

TR200 DRIVE WITH ELECTRONICALLY CONTROLLED BYPASS SYSTEM

BuildingName The Description of the Project P DOCUMENTS

E510. Compact Drive IP 20/ NEMA HP (230V) 1-75 HP (460V)

MOTOR STARTERS & VARIABLE SPEED DRIVES Variable speed drives

SSW06. Soft Starters.

Submittal Data Information SmartDRIVE HVAC Variable Speed Drives

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

ACH550 Product Overview

SECTION VARIABLE FREQUENCY DRIVES

TR200 DRIVE STANDARD FEATURES

8200 vector frequency inverter

Master the elements in building automation siemens.com/sinamics-g120x

F510 Fan & Pump AC Drive

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Submittal Data Information SmartDRIVE SP Variable Speed Drives

Submittal Data Information SmartDRIVE VP Variable Speed Drives

SSW06. Soft Starters. Applications. Standard Features. Pumps Fans Blowers Compressors Crushers Saws Grinders Mixers.

Affinity. Dedicated HVAC/R Drive for Building Automation. 1.1kW to 132kW (1.5hp to 200hp) 200V / 400V / 575V / 690V IP20 (NEMA 1) and IP54 (NEMA 12)

PowerXL DG1 Product Overview Eaton Corporation. All rights reserved.

MAKING MODERN LIVING POSSIBLE. ADAP-KOOL Drive. A New Drive for Energy Efficiency AKD 102 REFRIGERATION & AIR CONDITIONING DIVISION

AF-600 FP AC Drive AC Adjustable Frequency Drive Guide-Form Specification

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SENSORLESS VECTOR CONTROL

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

Drive inverter for asynchronous AC motors without encoder feedback. The units are not option capable.

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

SED2 Variable Frequency Drives

MP7. Uninterruptible Power Supply

EMS 1Ø, 120 ~ 230V, 1/10-25HP 3Ø, 200 ~ 600V, 1/2-300HP

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

INTRODUCING THE S V ADJUSTABLE SPEED DRIVE

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

VFD with Bypass package for HVAC Applications. Introducing the ABB E-Clipse Bypass

Motor Controllers AC Variable Frequency Drives Type VariFlex 3 RVFF

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction

160 AA02SF1 AF DS-D17

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

PART 1: GENERAL PART 2: PRODUCT. Phone: Fax: Web: -

SCC Inc. TS-D Series. Technical Instructions. Document No. TS-3000 March 10, Deaerator, Surge and/or Condensate Control Panel.

SD250 VARIABLE SPEED DRIVE

Altivar 212 Drive. A variable speed AC drive for 1 to 100 HP, three-phase asynchronous motors. Make the most of your energy SM

Motor Controllers AC Variable Frequency Drives Type VariFlex 3 RVFF

R E C T I F I E R I N V E R T E R C O N V E R T E R MP7

P7BR. Description 5-500HP P7/Bypass NEMA 3R. Phone: Fax: Page Web: 61www.clrwtr.com -

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

DRIVE H300 HVAC Drive for Building Automation

ATV212WU55N4 variable speed drive ATV kW - 7.5hp - 480V - 3ph - EMC class C2 - IP55

Submittal Schedule Details for VFD-P101, P201, P202, P310, P302, P401, P402

Smartstart Control Module

Low Voltage Drives. ABB component drives ACS55, 0.25 to 3 hp (0.18 to 2.2 kw) Catalog

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

POWER ELECTRONICS / SD700 SERIES SD700 VARIABLE SPEED DRIVES

IPS INTELLIGENT PUMP STARTER

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Operating comfort redefined Frequency Inverters M-MAX

8200 vector frequency inverter

Siemens BACnet Programmable TEC Unit Conditioner Controller

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

310SV SINGLE VALVE GOVERNOR

GS1 and GS2 Series AC Drives

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

VARIABLE FREQUENCY DRIVES

Transcription:

Building Technologies SED2 Variable Frequency Drives

More standard features Means better control of HVAC applications The global leader in Heating, Ventilation and Air Conditioning (HVAC) products and systems, Siemens delivers the SED2 family of Variable Frequency Drives, designed specifically for HVAC systems and applications. Using the latest IGBT technology, the SED2 Variable Frequency Drives are PWM drives loaded with features for HVAC variable torque applications such as speed control on fans and pumps. Since SED2 drives are preconfigured with the HVAC application parameters, startup and commissioning is faster, resulting in more cost-effective installations. Standard features that out power the competition Built-in SBT P1 and JCI N2 (Metasys ) building automation system protocols for easy network integration Optional LON, Modbus and BACnet (available 2006) interfaces Unique low harmonics design minimizing the need for external filtering Built-in PID control for fast accurate pressure/temperature control Pump controller staging/cascading for constant pressure, constant flow applications Multi-level program access Belt failure detection with or without an external sensor Essential service mode for critical applications requiring continuous, uninterruptible operation Accepts a wide variety of digital and analog I/O types, including direct Ni1000 sensor level inputs One common interface throughout all power ranges Advanced Operator Panel (AOP) for uploading/downloading of parameters Full form C relay contacts for digital outputs Total Harmonic Distortion Reduction Comparison In tests between a typical 6 pulse PWM drive with and without line reactors and DC link chokes versus the SED2 VFD, the Siemens Easy Drive demonstrated superior harmonic performance. In typical HVAC applications, the SED2 VFD can reduce harmonics by up to 25% more than other VFDs, even with line reactors and DC link chokes. Lower harmonic design eliminates problems The generation of harmonic currents on the AC line created by Variable Frequency Drives can lead to problems and increased installation costs. In addition, building design specifications often require compliance with IEEE 519 standard which limits the amount of harmonic current and voltage distortion allowed on the power system. Other products solve the problem by adding more equipment, more complexity and more cost.

The Siemens SED2 VFDs use a unique low harmonic design that eliminates the need for DC link chokes and line reactors. In addition, Siemens Harmonnee software calculates the harmonic distortions produced by the drive on your electrical system and compares them to IEEE standards to ensure compliance. The result is reduced expenses and the ability to use a smaller drive. That adds up to dollars and sense. Complete offering, backed by Siemens Siemens offers the most complete line of Variable Frequency Drives from a single source UL/NEMA Type 1, 12, 3R, electronic bypass and conventional bypass options. In addition, Siemens delivers a comprehensive line of HVAC products, including valves and valve actuators, damper actuators, room and specialized thermostats and sensors, controllers and switches and relays. All products are backed by Siemens expert technical support. Key features and benefits The SED2 VFDs power traditional variable torque fan and pump applications. Modular construction allows maximum flexibility in configuration Quiet motor operation Complete inverter and motor protection Main power and motor cable connections are separated for optimum electromagnetic capability Detachable operator panels for flexibility in installation Latest IGBT technology Digital microprocessor control for accuracy Flying restart eliminates the need for a mechanical break Automatic restart after power failure or fault to get you back up and running fast Auto-tuning PID controller for fast, accurate setup Programmable acceleration/deceleration, 0 to 650 seconds Ramp smoothing Fast current limit (FCL) for tip free operation Fast, repeatable digital input response time Fine speed adjustment using two highresolution 10-bit analog inputs Slip compensation

General specifications Input voltage and 200 to 240 Vac ± 10% 1/2 to 60 HP power ranges (3 phase) 380 to 480 Vac ± 10% 1/2 to 125 HP 500 to 600 Vac ± 10% 1 to 125 HP Input frequency Output frequency 47 to 63 Hz 0 to 150 Hz Total power factor 0.9 Displacement power factor 0.98 VFD efficiency Overload capability Control method PWM frequency Fixed frequencies Skip frequency bands Setpoint resolution Digital inputs (sink/source) Analog inputs Relay outputs Analog outputs Serial interface Protection level Temperature range Storage range Humidity Operational altitudes Protection features Standards CE marked 96 to 97% or greater 110% for 60 seconds Linear V/f, parabolic V/f (fan curve); flux current control (FCC) low-power mode 4 to 16 khz (adjustable in 2 khz increments) 15: programmable 4: programmable 0.01Hz digital 0.01Hz serial 10 bit analog 6: fully programmable and scalable isolated digital inputs, switchable 2: 0 to 10 VDC, 0/4 to 20 ma, can also be configured as digital inputs or Ni1000 input 2: configurable 30 VDC/5A (resistive), 250 VAC 2A (inductive) 2: programmable 0 to 10 VDC or 0/4 to 20 ma RS-485, SBT-P1; JCI-N2, Siemens USS bus (optional Modbus, LON, BACnet ) IP20 (NEMA Type 1 with protective shield and gland plate installed); IP54 (NEMA Type 12) 14 to 104 F (-10 to +40 C) -40 to +158 F (-40 to +70 C) 95% RH non-condensing Up to 1000 m above sea level without derating Under-voltage Over-voltage Ground Fault Short circuit Stall prevention Locked motor Motor over temperature l 2t, PTC VFD over-temperature Parameter PIIN protection UL, cul, CE, C-tick Conformity with EC Low Voltage Directive 72/23/EEC and 89/336/EEC

More connections for greater flexibility in applications Power and control interface connection diagram 200-240VAC 380-480VAC 500-600VAC DC/R+ DC/B+ N L1 L2 L3 PE L1 L2 L3 PE U V W PE PE M 3 ~ 1 2 +10 VDC +0 VDC Numbers shown represent the terminal number on control board shown below. Ni1000 V: 0-10 V 2-10 V I: 0-20 ma 4-20 ma Ni1000 4 2 10 V 3 AIN1 4 11 2 A / D D / A D / A AOUT1 AOUT2 + 12-13 + 26-27 V: 0-10 V 2-10 V I: 0-20 ma 4-20 ma V: 0-10 V 2-10 V I: 0-20 ma 4-20 ma V: 0-10 V 2-10 V I: 0-20 ma 4-20 ma 11 0 V 10 AIN2 Isolated 0 V (output) 28 Isolated 50 ma@18-32 VDC 9 (output) DIN 1 5 DIN 2 6 DIN 3 7 DIN 4 5 DIN 5 16 DIN 6 17 A / D opto isolated CPU 20 21 22 23 24 25 Relay Output 1 Relay Output 2 Motor PTC 14 14 BOP (Standard) AOP (Optional) RS-485 + - 29 30 SBT-P1 JCI-N2 Control terminals of the VFD shown with cover removed.

Configuration guides Instructions To select a part number, perform the following with the chart provided. Example: SED2-0.75/21X VFD only, 0.75 kw, 200 to 240V, NEMA Type 1 VFD Product Number S E D 2-0. 7 5 / 2 1 X Model SED2 = VFD Only kw 0.37, 0.55, 0.75, 1.1, 1.5, 2.2, 3, 4, 5.5, 7.5, 11, 15, 18.5, 22, 30, 37, 45, 55, 75, 90 (Uses 2 to 4 spaces plus / divider) Voltage 2 = 200 to 240V 3 = 380 to 480V 4 = 500 to 600V NEMA 2 = (IP20) 1 = NEMA Type 1 5 = NEMA Type 12 (IP54) Filter X = Factory required designator Example: VBA340.F120X VFD with bypass, 480V, 40 HP, fused disconnect, NEMA 1, 2-contractors Ordering Notes For ordering bypass-door mounted control devices, the following options are available: 2-Contractor units Drive-Off-Bypass selector Bypass pilot light Bypass VFD Product Number Model Series VB = VFD with Bypass A = Conventional Bypass E = Electronic Bypass Voltage 1 = 208V 2 = 230 to 240V 3 = 380 to 480V 4 = 500 to 600V HP Rating 0.5, 0.7, 1.0, 1.5, 2.0, 3.0, 4.0 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125 Disconnect D = Disconnect F = Fused Disconnect B = Circuit Breaker NEMA 1 = NEMA Type 1 3 = NEMA type 3R Contractors Reactor 2 = 2 Contractors 3 = 3 Contractors 0 = None 3 = Line Reactor L = Load Reactor V B A 3 4 0. F 1 2 0 X 3-Contractor units Drive-Off-Bypass selector Bypass pilot light Drive Test On/Off selector Filter Options X = Factory required designator HA1 = High amp rating HT1 = High temp rating (NEMA 3R only)

Variable Frequency Drives Designed specifically for HVAC applications, the SED2 family of VFDs supports a wide variety of digital and analog inputs and outputs for maximum control flexibility. Built-in PID features control pumps and fans, and an integral system protocol can interface P1/N2 networks. Using the SED2 multi-level parameter access, operators can quickly pinpoint relevant data. Features Built-in SBT P1 and JCI N2 (Metasys ) building automation system protocols for easy network integration Low harmonics design reduces noises and interference eliminates the need for filters/ reactors in most installations Built-in PID for fast and accurate pressure control Pump staging for open loop, constant pressure, and constant flow-type applications Multi-level program access Belt failure detection with or without an external sensor Service mode for applications requiring continuous, uninterruptible operation Accepts a wide variety of digital and analog I/O types, including direct Siemens Ni1000 RTD sensor level inputs One common interface throughout all power ranges Full form C relay contacts for digital outputs Options LON Interface Modbus Interface BACnet Interface Advanced Operator Panel (AOP) Module

VFD with Electronic (E) Bypass Option Electronic (E) Bypass Options are companion packages for SED2 Variable Frequency Drives that provides electronic control and simple keypad operation to streamline installation, simplify control wiring, and improve system reliability. E-Bypass Features Enhanced visual interface for improved monitoring and diagnostics E-Bypass guarantees continuous operation even it VFD fails Electronic touch-sensitive keypad Service mode isolates drive from the control scheme Six relay outputs for indication of operation LED indicators for monitoring and operation Six digital inputs Contactors electrically and mechanically interlocked 2-Contactor: Output and Bypass with overload protection in bypass mode 3-Contactor (optional): Output, Bypass and Input providing drive test function and complete electrical isolation of drive Input Device includes: disconnect, fused disconnect (optional) and circuit breaker (optional). All doors are interlocked and padlockable. Reactor Options include: Line reactor mounted in bypass option enclosure; line reactor (in NEMA 1 enclosure) supplied separately; load reactor mounted in bypass option enclosure and load reactor (in NEMA 1 enclosure) supplied separately. E-Bypass Control Features Auto Bypass allows user to send the motor to bypass mode based on the drive s programmable relay, typically set to fault. Two Enable Inputs are generally used for safety tie-ins; the motor will not operate in drive or bypass when open. Common Remote Start/Stop can be used in both drive and bypass mode. Essential Services Mode is typically used for smoke purge; the motor goes to bypass regardless of the selected mode. No call to stop will have an effect, including open safety or stop commands. Only turning the power off or opening this contact will stop the motor. Options LON Interface Modbus Interface BACnet Interface Advanced Operator Panel (AOP) Module

VFD with Conventional (A) Bypass Option Conventional Bypass Options are companion packages for SED2 Variable Frequency Drives that streamlines installation and simplifies control wiring. Bypass Power Features 2-Contactor: Output and Bypass provides overload protection in bypass mode with a step-down transformer with fused primary and secondary. Contactors are electrically and mechanically interlocked. In addition to the 2-Contactor features, 3-Contactor (optional): Output, Bypass and Input, providing drive test function and complete electrical isolation of drive. Input Device includes: disconnect, fused disconnect (optional) and circuit breaker (optional). All doors are interlocked and padlockable. Reactor Options include: Line reactor mounted in bypass option enclosure; line reactor (in NEMA 1 enclosure) supplied separately; load reactor mounted in bypass option enclosure and load reactor (in NEMA 1 enclosure) supplied separately. Bypass Control Features Auto Bypass allows user to send the motor to bypass mode based on the drive s programmable relay, typically set to fault. Enable Input is generally used for safety tie-ins; the motor will not operate in drive or bypass when open. Common Remote Start/Stop can be used in both drive and bypass mode. Essential Services Mode is typically used for smoke purge; the motor goes to bypass regardless of the selected mode. No call to stop will have an effect, including open safety or stop commands. Only turning the power off or opening this contact will stop the motor. Bypass-Door-Mounted Control Devices Features 2-Contactor Units include: Drive-Off-Bypass selector and bypass pilot light 3-Contactor Units include: Drive-Off-Bypass selector, Bypass pilot light and Drive Test On/ Off selector. Options LON Interface Modbus Interface BACnet Interface Advanced Operator Panel (AOP) Module

VFD with NEMA 3R (A) Bypass Option or VFD only The NEMA Type 3R Bypasses are companion packages for the family of SED2 Variable Frequency Drives. NEMA Type 3R enclosed bypasses are manufactured for outdoor locations. The 3R rating provides a degree of protection to the enclosed SED2 VFD and electrical control components. A heater is supplied to protect against condensation. Bypass Power Features 2-Contactor: Output and Bypass provides overload protection in bypass mode with a step-down transformer with fused primary and secondary. Contactors are electrically and mechanically interlocked. In addition to the 2-Contactor features, 3-Contactor (optional): Output, Bypass and Input, providing drive test function and complete electrical isolation of drive. Input Device includes: disconnect and fused disconnect (optional). All doors are interlocked and padlockable. Reactor Options include: Line reactor mounted in bypass option enclosure; line reactor (in NEMA 3R enclosure) supplied separately; load reactor mounted in bypass option enclosure and load reactor (in NEMA 3R enclosure) supplied separately. Bypass Control Features Auto Bypass allows user to send the motor to bypass mode based on the drive s programmable relay, typically set to fault. Enable Input is generally used for safety tie-ins; the motor will not operate in drive or bypass when open. Common Remote Start/Stop can be used in both drive and bypass mode. Essential Services Mode is typically used for smoke purge; the motor goes to bypass regardless of the selected mode. No call to stop will have an effect, including open safety or stop commands. Only turning the power off or opening this contact will stop the motor. Bypass-Door-Mounted Control Devices 2-Contactor Units include: Drive-Off-Bypass selector and bypass pilot light 3-Contactor Units include: Drive-Off-Bypass selector, Bypass pilot light and Drive Test On/ Off selector. 3R Units available with no bypass Options LON Interface Modbus Interface BACnet Interface Advanced Operator Panel (AOP) Module

SED2 Options Description Quantity Part No. BOP/AOP Door Mounting Kit Allows remote mounting of operator panels and provides IP56 protection. No special cables needed. Single VFD 1 SED2-DOOR-KIT1 Multiple VFDs 1 SED2-DOOR-KIT2 Modbus Interface Cable Converts VFDs USS bus to Modbus RTU; 3 in length. 1 SED2-MODBUS1 LON Interface Module 1 SED2-LONI/F Provides direct connection to LON network and communication with LONMARK devices. Module allows read/write access to more than 40 parameters; mounts compactly behind operator panel and provides simple wiring access. Advanced Operator Panel (AOP) 1 SED2-AOP1 Plain text LCD display for reading VFD data in seven languages Allows uploading and downloading of parameters from multiple VFDs Up to 10 parameter sets can be stored and downloaded into separate VFDs Includes an integrated scheduler function EasyComm Drive Programming Software 1 SED2-EASYCOMM (requires PC Interface) PC Interface 1 SED2-PC-KIT Harmonee Software 1 SED2-HARMONEE

www.sbt.siemens.com/hvp/drives Building Technologies Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel 847 215 1000 Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario, Canada L6T 5E4 Tel 905 799 9937 Copyright 2006 Siemens Building Technologies, Inc. All product and company names herein are trademarks of their respective owners. All rights reserved. Printed in the USA. 153-887P10 (01/2006)