Cycle and response times SIMATIC. S Cycle and response times. Preface. Documentation guide. Program processing 2. Cyclic program processing 3

Similar documents
ST (6ES7132-6FD00-0BB1)

Readme SiVArc V14 SP1 Update 6

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library 1. Deleting program block Main [OB1]

Counting, measurement and position. detection SIMATIC. S7-1500, ET 200MP, ET 200SP Counting, measurement and position detection.

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

SIMATIC. Process Control System PCS 7 VT Readme V8.2 (online) Security information 1. Overview 2. Notes on Installation 3. Notes on usage 4.

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0)

Optional package printer driver V1.4

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide

SIMATIC/SINAMICS. Getting started with SINAMICS V90 PN on S Motion Control. Fundamental safety instructions 1. Introduction

IO-Link Master (6ES7147-4JD00-0AB0) SIMATIC. ET 200pro IO-Link Master (6ES7147-4JD00-0AB0) Preface. Documentation guide. Product overview.

Use with 0 to 70 C ambient. temperature SIMATIC. Process Control System PCS 7 Use with 0 to 70 C ambient temperature. Preface 1. Product combination 2

Digital output module. DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC

SIMATIC. Process Control System PCS 7 PCS 7 system documentation - Readme V8.0 SP2 (Update 1) Options for Accessing Documentation 1

Power module PM-E DC24V HF SIMATIC. ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface. Properties.

Class documentation. COMOSKDictionary COMOS. Platform Class documentation COMOSKDictionary. Trademarks. General. KDictionary. Programming Manual

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview.

CM PtP RS422/485 BA communication. module (6ES7540 1AB00 0AA0) SIMATIC. S7-1500/ET 200MP CM PtP RS422/485 BA communication module (6ES7540 1AB00 0AA0)

SIMATIC. S7/HMI SIMATIC Automation Tool V3.1 SP1 product information. SIMATIC Automation Tool features 1. Known problems. Product Information

MindSphere. Visual Explorer. Introduction. User roles for "Visual Explorer" Connecting "Visual Explorer" to MindSphere data. Creating Visualizations

SIMATIC. Process Control System PCS 7 CFC Readme V9.0 (online) Security information 1. Overview 2. Notes on Installation 3. Notes on usage 4.

Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties.

SIMATIC. Process Control System PCS 7 PCS 7 Documentation (V8.1) Options for Accessing Documentation 1. Documentation for the Planning Phase 2

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

SITOP UPS1600 under STEP 7 V13. SITOP UPS1600 under STEP 7 V13. Introduction. Safety notes. Description. Assigning the IP address

S7-300 Getting Started - Commissioning a CPU 31xC: Closed-loop control

SIMATIC. SIMATIC Energy Manager V1.0 App for ios and Android. Preface. SIMATIC Energy Manager app. Establish connection to SIMATIC Energy Manager PRO

Configuration limits for products of the SIMATIC NET PC Software V8.1 SIMATIC NET

Performance data abgn SCALANCE W770/W730 SIMATIC NET. Industrial Wireless LAN Performance data abgn SCALANCE W770/W730.

SIMATIC. Industrial software WinAC RTX F Introduction 1. Selecting suitable hardware 2. Installing/removing the WinAC RTX F 2009 software

ST (6ES7522-1BH00-0AB0)

Siemens Spares. Setting up security in STEP 7. Professional SIMATIC NET. Industrial Ethernet Security Setting up security in STEP 7 Professional

Performance data abgn PCIe Minicard MPCIE-R1-ABGN-U3 SIMATIC NET

SIMATIC. Process Control System PCS 7 Configuration McAfee Endpoint Security Security information 1. Preface 2.

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Readme

Configuration limits for products of the HARDNET-PB DP-Base 1

COMOS. Platform Class documentation RevisionMaster_dll. Class: RevisionInfo 1. Class: RevisionMaster 2. Programming Manual

RF-MANAGER simulator SIMATIC. RFID-Systems RF-MANAGER simulator. Simulating projects. Compact Operating Instructions 06/2010 A5E

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

Siemens Drives & PLCs

SIMATIC. Process Control System PCS 7 OS Process Control (V8.1) Security information 1. Preface 2. Additional documentation 3

SIMATIC. Process Control System PCS 7 Advanced Process Functions Operator Manual. Preface. Security information 1. Overview 2. Material management 3

SIMATIC. PCS 7 Licenses and configuration limits (V9.0) Security information 1. Preface 2. Selecting the correct license keys 3


SIMOTION. SIMOTION SCOUT Reading and Writing Drive Data. Preface. Fundamental safety instructions 1. Description 2.

Siemens Drives & PLCs

Key Panels Library SIMATIC HMI. Key Panels Library. Preface 1. Installation of Key Panels Library. Working with the Key Panels Library

Digital output module. DQ 16x230VAC/2A ST Relay (6ES7522-5HH00-0AB0) SIMATIC

ST (6ES7522-5HF00-0AB0)

SIMATIC. S7-1500/ET 200MP DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Preface. Documentation guide. Product overview.

Siemens Automation Products

SIMATIC NET. Industrial Ethernet / PROFINET Primary Setup Tool (PST) Preface. Functions 1. Software installation 2. Operation. Configuration Manual

Digital input module. DI 16x24VDC 8xM12 6ES7141-5AH00-0BA0) SIMATIC. ET 200AL Digital input module DI 16x24VDC 8xM12 6ES7141-5AH00-0BA0) Preface

SIMATIC IPC Wizard for. Widescreen devices with multitouch SIMATIC. Industrial PC SIMATIC IPC Wizard for. Preface.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

SIMATIC. ET 200SP Open Controller Product information on CPU 1515SP PC. Preface. Product Information. Technical update. Technical specifications 3

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

PD PA AP How To Configure Maxum II TimeServer Access

SIMATIC NET. Industrial Ethernet Security SCALANCE S615 Getting Started. Preface. Connecting SCALANCE S615 to the WAN 1

SIMATIC. S7-1500/ET 200MP Digital input module DI 16x24VDC BA (6ES7521-1BH10-0AA0) Preface. Documentation guide. Product overview.

Siemens Industrial SIMATIC. Process Control System PCS 7 Configuration Trend Micro OfficeScan Server XG. Security information 1.

SIMATIC. S7-1500, ET 200SP, ET 200pro Structure and Use of the CPU Memory. Preface. Documentation guide. Memory areas and retentive memory

SINEMA Remote Connect - Client SIMATIC NET. Industrial Remote Communication SINEMA Remote Connect - Client. Preface. Requirements for operation

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Primary Setup Tool (PST) SIMATIC NET. Industrial Ethernet / PROFINET Primary Setup Tool (PST) Preface. Description. Software installation 2

SIMATIC. Industrial PC Microsoft Windows 7 (USB stick) Safety instructions 1. Initial startup: Commissioning the operating system

SIMATIC. Process Control System PCS 7 OS Process Control (V8.1) Preface 1. Additional documentation 2. Functions of the PCS 7 OS in process mode 3

Continuous Function Chart Getting. Started SIMATIC. Process Control System PCS 7 Continuous Function Chart Getting Started.

SIMATIC. Process control system PCS 7 Operator Station (V9.0 SP1) Security information 1. Preface 2

SIMOTION. Motion Control Task Trace. Preface 1. Overview 2. Configuring 3. Working with the SIMOTION Task Profiler 4.

Operator Station (V8.0) SIMATIC. Process Control System PCS 7 Operator Station (V8.0) Preface 1. The PCS 7 Operator Station

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.

Technological Functions SIMATIC. ET 200S Technological Functions. Preface 1. 1Count24V. 1Count5V 3 1SSI 4 2PULSE. Operating Instructions

Preface. Guide SIMATIC. System overview. Integration into the automation system 3. IO-Link system. Function Manual 12/2017 A5E AB

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. Process Control System PCS 7 Software update with utilization of new functions. Security information 1. Preface 2.

SIMATIC. Industrial PC Microsoft Windows 7. Safety instructions 1. Initial startup: Commissioning the operating. system

Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) SIMATIC. ET 200SP Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) Preface

party software COMOS Platform Third-party software Trademarks 1 Requirements for the system environment Third-party software releases Operating Manual

SIMATIC. Process Control System PCS 7 Trend Micro OfficeScan (V8.0; V8.0 SP1) Configuration. Using virus scanners 1.

SIMATIC. STEP 7 (TIA Portal) Global library "Sample Library for Instructions" Disclaimer. Basic information on the library.

SIMATIC. Process Control System PCS 7 Configuration Symantec Endpoint Protection V14. Security information 1. Preface 2.

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting.

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

SIMOCODE pro. Read me SIMOCODE ES. Introduction 1. Installation notes 2. Installation/License key/ Uninstallation 3.

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)

SIMATIC. PCS 7 Process Control System SIMATIC Logon Readme V1.6 (Online) Security information 1. Overview 2. Notes on installation 3.

Industrial Controls. SIMOCODE pro SIMOCODE pro PCS 7 Library. Preface. Security information. Product specific security. information.

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V (6ES7138-4CA50-0AB0) Preface. Properties 1. Parameters 2. Diagnostics 3.

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

SIMATIC. WinCC Readme Runtime Professional. Validity 1. Improvements in Update 7 2. Improvements in Update 6 3. Improvements in Update 5 4

SIMATIC. WinCC Readme Runtime Professional. Validity 1. Improvements in Update 2 2. Improvements in Update 1 3

Process Historian Administration SIMATIC. Process Historian V8.0 Update 1 Process Historian Administration. Basics 1. Hardware configuration 2

Deckblatt. APL Operator Guide SIMATIC PCS 7. Application description June Applikationen & Tools. Answers for industry.

SIMATIC. Modifying the System during Operation via CiR. Requirements and Overview 1. CiR Objects and CiR Modules. User Interface 3

Transcription:

Preface Documentation guide 1 SIMATIC S7-1500 Program processing 2 Cyclic program processing 3 Event-driven program processing 4 Function Manual 02/2014 A5E03461504-02

Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: Trademarks WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY A5E03461504-02 P 02/2014 Technical data subject to change Copyright Siemens AG 2013-2014. All rights reserved

Preface Purpose of the documentation The control system offers various options for program execution with different run priorities. Cyclic and time-driven program execution have the largest share. The response times of a control system are therefore significantly determined by the processing cycles. Additionally there is also the possibility of event-driven program execution. The event-driven program execution is normally limited to a few selected events. This manual provides information on the following topics: Types of program execution Run priorities, and the influences to which they are subject Configuration options for the optimization of your user program Basic knowledge required The following knowledge is required in order to understand the documentation: General knowledge of automation technology Knowledge of the industrial automation system SIMATIC Knowledge about the use of Windows-based computers Knowledge about how to use STEP 7/TIA Portal Conventions STEP 7: We refer to the configuration and programming software as "STEP 7" in this documentation synonymously for "STEP 7 V12 (TIA Portal)" and subsequent versions. Please also observe notes marked as follows: Note A note contains important information on the product described in the documentation, on the handling of the product and on the section of the documentation to which particular attention should be paid. Function Manual, 02/2014, A5E03461504-02 3

Preface Scope of the documentation This documentation mainly includes the CPU components of the cycle and reaction times of the S7-1500 automation system. You can find references at the corresponding instances for more information on the ET 200MP and ET 200SP distributed I/O systems. Additional support Additional information on SIMATIC products is available on the Internet. The associated documentation is likewise available on the Internet. You can find the available technical documentation for the individual SIMATIC products and systems in the internet (http://www.siemens.com/simatic-tech-doku-portal). The online catalog and the ordering system are available on the Internet (http://mall.automation.siemens.com). Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. You can find more information about industrial security on the Internet (http://www.siemens.com/industrialsecurity). To stay informed about product updates as they occur, sign up for a product-specific newsletter. You can find more information on the Internet (http://support.automation.siemens.com). 4 Function Manual, 02/2014, A5E03461504-02

Table of contents Preface... 3 1 Documentation guide... 6 2 Program processing... 8 3 Cyclic program processing... 11 3.1 Cycle... 11 3.2 Cycle time... 12 3.2.1 Different cycle times... 12 3.2.2 Influences on the cycle time... 16 3.2.2.1 Update time for process images... 16 3.2.2.2 User program processing time... 17 3.2.2.3 Extension of cycle time due to communication load... 19 3.3 Time-driven program processing in cyclic interrupts... 21 3.4 Response time for cyclic and time-driven program processing... 23 3.5 Summary of response time with cyclic and time-controlled program execution... 26 4 Event-driven program processing... 27 4.1 Response time of the CPUs when program execution is event-controlled... 27 4.2 Process response time when program execution is event-driven... 29 Glossary... 30 Index... 31 Function Manual, 02/2014, A5E03461504-02 5

Documentation guide 1 Introduction This modular documentation of the SIMATIC products covers diverse topics concerning your automation system. The complete documentation for the S7-1500 system consists of a system manual, function manuals and device manuals. The STEP 7 information system (Online Help) also helps you configure and program your automation system. Overview of the additional documentation on the topic of cycle and response times The following table lists additional documentation which supplements this description of cycle and response times. Table 1-1 Documentation of cycle and response times Topic Documentation Most important contents System description CPU System manual S7-1500 Automation System (http://support.automation.siemens.com/ww/vi ew/en/59191792) System manual ET 200SP distributed I/O system (http://support.automation.siemens.com/ww/vi ew/en/58649293) System manual ET 200MP distributed I/O system (http://support.automation.siemens.com/ww/vi ew/en/59193214) Device manual CPU 1511-1 PN (http://support.automation.siemens.com/ww/vi ew/en/68020492) Device manual CPU 1513-1 PN (http://support.automation.siemens.com/ww/vi ew/en/59186494) Device manual CPU 1515-2 PN (http://support.automation.siemens.com/ww/vi ew/en/81162167) Application planning Installation Wiring Commissioning Block diagram Wiring Parameter assignment/ addressing Diagnostics alarms/ interrupts Technical specifications Dimensional drawings Function Manual, 02/2014, A5E03461504-02 6

Documentation guide Topic Documentation Most important contents Device manual CPU 1516-3 PN/DP (http://support.automation.siemens.com/ww/vi ew/en/59191914) Device manual CPU 1518-4 PN/DP (http://support.automation.siemens.com/ww/vi ew/en/81164632) Isochronous mode for PROFINET Isochronous mode for PROFIBUS Function manual PROFINET with STEP 7 V13 (http://support.automation.siemens.com/ww/vi ew/en/49948856) Function manual PROFIBUS with STEP 7 V13 (http://support.automation.siemens.com/ww/vi ew/en/59193579) Isochronous mode for PROFINET Instructions "SYNC_PI" and "SYNC_PO" Isochronous mode for PROFIBUS Instructions "SYNC_PI" and "SYNC_PO" SIMATIC manuals All current manuals for the SIMATIC products are available for download free of charge from the Internet (http://www.siemens.com/automation/service&support). Function Manual, 02/2014, A5E03461504-02 7

Program processing 2 Introduction You often program your user program with a cyclic OB, usually in OB 1. With complex applications, problems are often encountered in complying with the response time required by the application. You can often solve the response time requirements by splitting the user program up into several parts with different response time requirements. The CPU offers a number of different OB types for this purpose, the properties (priority, frequency, etc.) of which can be adapted to meet the requirements. Program organization You can choose from the following types of program execution for running your user program: Program execution in the cyclic program of the CPU: In the simplest case, you execute the entire user program in the cyclic program of the CPU. All tasks in the user program are then processed with equal rank. This also results in the same response times for all tasks. In addition to program execution in the cyclic program, there is time-driven and event-driven program execution. Time-driven processing: In a complex user program, there are frequently portions with different response time requirements. You can optimize the response times by taking advantage of these differences in the requirements. To do so you can move the program parts with higher response time requirements to higher-priority OBs with shorter cycles, for example cyclic interrupt OBs. The processing of these parts can thus occur with different frequencies and priorities. Event-driven processing: Depending on the I/O modules used, you can configure hardware interrupts for specific process events (such as an edge change of a digital input) that result in the call of the assigned hardware interrupt OB. The hardware interrupts have a higher priority and interrupt the cyclic program of the CPU. You can achieve very short response time in the CPU with hardware interrupts by directly triggering program execution. Keep in mind that the time characteristics of your application becomes less predictable with intense use of hardware interrupts. The reason being that the time at which the triggering events occur can result in drastically different response times. Tip: Use hardware interrupts only for a few, select events. Function Manual, 02/2014, A5E03461504-02 8

Program processing Using process image partitions If a program is distributed to various OBs, for example, due to differing response time requirements, it is advisable and often necessary to assign the update of the used I/O data directly to these OBs. You can use process image partitions for this purpose. You group the input and output data in a process image partition according to their use in the program and assign the data to the corresponding OB. You optimize the response times this way, because the update of the affected I/O modules is directly synchronized with the processing in the program. A process image partition of the inputs (PIPI) permits the associated input data for an OB program to be updated immediately before the OB program starts. A process image partition of the outputs (PIPQ) permits the output data associated with an OB program to become effective on the outputs immediately after the OB program runs. You have 32 (0 31) process image partitions at your disposal. The default assignment for the I/O is process image partition 0 (setting: "Automatic updating"). Process image partition 0 is permanently assigned to cyclic processing. You have to configure this "system-side update of process image partitions". You can find additional information on configuration of process image partitions in the online help for STEP 7 under the keyword "Assign process image/process image partition". Interruptability of program run Each organization block is processed with a priority. You can adapt the priority according to the response time requirements for most organization blocks. All cycle OBs always have the lowest priority of 1. The highest priority is 26. Communication tasks always have priority 15. If necessary, you can change the priority of your blocks and select a higher priority than the communication. Organization blocks or system activities with higher priority interrupt those with lower priority, and thus extend the run time of the interrupted organization blocks or system activities. If two pending tasks have the same priority, these tasks are processed in the order in which the tasks occurred. Note Higher priority OBs Communication functionality is strongly influenced by too many or runtime-intensive OBs with a priority > 15. When using OBs with a priority > 15, you should consider the runtime load that they cause in order to keep communication functionality at a reasonable level. Function Manual, 02/2014, A5E03461504-02 9

Program processing Reference You can find additional information on the subject of priorities in the system manual for the S7-1500 Automation System (http://support.automation.siemens.com/ww/view/en/59191792), in the Events and OBs section. 10 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3 3.1 Cycle Introduction In this section, you will learn about the concept of the "cycle". Definition of cycle A cycle in the S7-1500 automation system encompasses the following: Update of process image partition 0 of the inputs (PIPI 0) Processing of the cyclic program Update of process image partition 0 of the outputs (PIPQ 0) The process image partition 0 is permanently assigned to the cycle. You assign I/O addresses to this process image partition using the "Automatic updating" setting (default) in the TIA Portal in HW Config for the I/O modules. The figure below illustrates the phases that are passed through during a cycle. 1 2 3 4 5 Figure 3-1 The operating system starts measurement of the cycle time. The CPU reads the status of the inputs at the input module and writes the input data to the process image partition of the inputs. The CPU processes the user program and executes the instructions specified in the program. The CPU writes the states from the process image outputs to the output modules. The operating system evaluates the determined cycle time and starts the measurement again. Cycle Function Manual, 02/2014, A5E03461504-02 11

Cyclic program processing 3.2 Cycle time 3.2 Cycle time Introduction In this section you will learn about the concept of "cycle time", and how to estimate the cycle time. Definition of cycle time The cycle time is the time the CPU need to execute the cyclic program, to update the process image of the inputs and outputs as well as for all program parts and system activities that interrupt this cycle. 3.2.1 Different cycle times Introduction The cycle time (Tcyc) is not equally long for every cycle, because the processing times can vary. Causes for this are, for example: Different program runtimes (e.g. program loops, conditional commands, conditional block calls, or different program paths) Lengthening due to interruptions (e.g. time-driven interrupt processing, processing of hardware interrupts or communication) 12 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.2 Cycle time Causes for different cycle times The cycle time Tcyc2 is longer than Tcyc1, because the cyclic program is interrupted by a cyclic interrupt OB in this example (e.g: OB 30). The cyclic interrupt OB in turn is interrupted by communication. The figure below shows the different cycle times Tcyc1 and Tcyc2. Figure 3-2 Possible causes of differing cycle times Minimum cycle time In STEP 7, you can set a minimum cycle time for a CPU. The default for the minimum cycle time is one millisecond. It may be advisable to increase this setting in the following cases: To reduce the cycle time's fluctuation range. To make remaining computing time available for communication tasks. Function Manual, 02/2014, A5E03461504-02 13

Cyclic program processing 3.2 Cycle time Maximum cycle time The cycle time is monitored by the CPU. By default, the maximum cycle time is 150 ms. This value can be changed by setting CPU parameters. When the cycle time is longer than the maximum cycle time, the time error OB (OB 80) is called. You have the option of restarting the maximum cycle time using the "RE_TRIGR" instruction, and thus extending it. With the user program in OB 80 you specify how the CPU responds to the time error. Under the following conditions the CPU goes to STOP. If you have not loaded an OB 80. If the cycle is still not completed after an additional maximum cycle time Keep in mind that the cycle time is extended by interruptions as shown in the previous figure. 14 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.2 Cycle time Cycle time statistics In STEP 7 and in the TIA Portal, you have the option of viewing the cycle time statistics, and of determining the minimum and maximum cycle time with the instruction "RT_INFO". You need this information to determine the response times of the user program in the cycle. To view the cycle time statistics, follow these steps: 1. Establish an online connection with the TIA Portal. 2. Select the Online tools task card on the very right. Result: The diagram of the cycle time statistics is displayed in the cycle time section. The following figure shows an extract from the TIA Portal with the cycle time statistics. In this example, the cycle time ranges from 7 ms to 12 ms. The current cycle time is 10 ms. The maximum cycle time that can be set in this example is 40 ms. Figure 3-3 Cycle time statistics You can find additional information on the runtime characteristics of the CPU with the "RT_INFO" instruction in the user program. You can read the utilization of the CPU in percentage with the control program and communication, and you can also read the runtime statistics of individual OBs. Reference You can find additional information on the "RT_INFO" instruction in the STEP 7 online help. Function Manual, 02/2014, A5E03461504-02 15

Cyclic program processing 3.2 Cycle time 3.2.2 Influences on the cycle time 3.2.2.1 Update time for process images Introduction In this section, you will learn how you can estimate the update time of process image partitions. Update time for process image partitions The update time of the process image partitions depends on the quantity of assigned central and distributed I/O module data. You can estimate the update time using the following formula: Base load for process image update + Number of words in the process image x copy time for central I/O modules + Number of words in the process image via DP x copy time for PROFIBUS I/O + Number of words in the process image via PROFINET x copy time for PROFINET I/O = Update time of the process image partition The following table includes the times for estimating the typical update time of the process image partitions. Table 3-1 Components Data for estimating the typical update time of the process image partition Update time of the CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Base load for process image partition update Copy time for central I/O modules Copy time for distributed I/O modules via PROFIBUS Copy time for distributed I/O modules via PROFINET 35 μs 35 μs 30 μs 30 μs 5 μs 9 μs/word 9 μs/word 8 μs/word 8 μs/word 4 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.3 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.3 μs/word 16 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.2 Cycle time 3.2.2.2 User program processing time Introduction Organization blocks or system activities with higher priority interrupt those with lower priority, and thus extend the run time of the lower-priority organization blocks or system activities. Program execution time without interruptions The user program has a certain runtime without interruptions. The length of the run time depends on the number of operations that are executed in the user program. The following table contains the times for how long an operation lasts. Table 3-2 Duration of an operation CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Bit operations, typ. Word operations, typ. Fixed-point arithmetic, typ. Floating-point arithmetic, typ. 60 ns 40 ns 30 ns 10 ns 1 ns 72 ns 48 ns 36 ns 12 ns 2 ns 96 ns 64 ns 48 ns 16 ns 2 ns 384 ns 256 ns 192 ns 64 ns 6 ns Note Instruction "RUNTIME" You can measure the run times of program sequences with the instruction "RUNTIME". Function Manual, 02/2014, A5E03461504-02 17

Cyclic program processing 3.2 Cycle time Extension due to nesting of higher-priority OBs and/or interrupts The interruption of a user program by a higher-priority OB causes a certain basic time expenditure. Take account of this basic time expenditure in addition to the update time of the assigned process image partitions and the processing time of the contained user program. The following tables include the corresponding times for the various interrupts and error events. Table 3-3 Basic time expenditure for an interrupt CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Hardware interrupt Time-of-day interrupt Time-delay interrupt 90 μs 90 μs 80 μs 80 μs 12 μs 90 μs 90 μs 80 μs 80 μs 12 μs 90 μs 90 μs 80 μs 80 μs 12 μs Cyclic interrupt 90 μs 90 μs 80 μs 80 μs 12 μs Table 3-4 Basic time expenditure for an error OB CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Programming error 90 μs 90 μs 80 μs 80 μs 12 μs I/O access error 90 μs 90 μs 80 μs 80 μs 12 μs Time error 90 μs 90 μs 80 μs 80 μs 12 μs Diagnostic interrupt Module failure/recovery CPU stop/ recovery 90 μs 90 μs 80 μs 80 μs 12 μs 90 μs 90 μs 80 μs 80 μs 12 μs 90 μs 90 μs 80 μs 80 μs 12 μs Reference You can find additional information on the subject of error handling in the system manual for the S7-1500 Automation System (http://support.automation.siemens.com/ww/view/en/59191792), in the Events and OBs section. 18 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.2 Cycle time 3.2.2.3 Extension of cycle time due to communication load Impact of communication on the cycle time In the sequence model of the CPU, communication tasks are processed with priority 15. All program parts with priority > 15 are not influenced by communication. Configured communication load The CPU operating system provides the maximum specified percentage of total CPU processing power for communication tasks. The default setting for the communication load of the S7-1500 automation system is 50% in the TIA Portal. If the processing power is not needed for communication, then the processing power is available to the operating system and the user program. Communication is allocated the requisite processing time in 1-ms increments, with priority 15. At 50% communication load, 500 μs of each 1 millisecond are used for communication. The following formula may be used to estimate the extension of the cycle time by communication. Figure 3-4 Formula: Impact of communication load With a complete use of the communication load of 50% (default), the following value results: Figure 3-5 Extension of cycle time due to communication load The actual cycle time is up to twice as long as the cycle time without communication when you use the default communication load. Function Manual, 02/2014, A5E03461504-02 19

Cyclic program processing 3.2 Cycle time Dependency of maximum cycle time on the configured communication load The diagram shows the nonlinear relationship between maximum cycle time and configured communication load with a pure cycle time of 10 ms, which means without interruptions. Figure 3-6 Maximum cycle time depending on the configured communication load The shown influence of the communication load on the processing time applies to all OBs with a priority 15. Reducing the cycle time through low communication load You can reduce the setting for the communication load in the hardware configuration. If you set a communication load of 20%, for example, instead of the default 50%, the cycle time is reduced from 2 x cycle time without communication to 1.25 x cycle time without communication. 20 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.3 Time-driven program processing in cyclic interrupts Effect on the actual cycle time Communication is only one cause for extension of the cycle time. All cycle time extending settings lead to the result that more asynchronous events can occur within a cycle, which additionally extend the cyclic program. This extension depends on the number of events that occur in the cyclic program and the time required to process these events. Note Checking parameter changes Check the effects of a value change on the "Cycle load due to communication" parameter during system operation. To prevent time errors, take account of the communication load when setting the maximum cycle time. Tips Whenever possible, use the default setting for the configured communication load. If you reduce the value of the communication load, keep in mind that communication tasks are interrupted by higher-priority OBs. This means it will also take longer to process the communication. 3.3 Time-driven program processing in cyclic interrupts With a cyclic interrupt, you can have a particular program processed in a defined cycle. This program is run at a higher priority (user-assigned) and is thus independent of the execution time of the cyclic program. Tip: By shifting program sections to cyclic interrupts, you can reduce the corresponding response times or better adapt them to your requirements. In STEP 7, the organization blocks OB 30 to OB 38 are provided for the processing of cyclic interrupts. You can create additional cyclic interrupts starting with organization block OB 123. The number of available organization blocks depends on the CPU used. Definition A cyclic interrupt is an interrupt initiated according to a defined cycle that causes a cyclic interrupt OB to be processed. Function Manual, 02/2014, A5E03461504-02 21

Cyclic program processing 3.3 Time-driven program processing in cyclic interrupts Cycle of a cyclic interrupt The cycle of a cyclic interrupt is defined as the time from the call of a cyclic interrupt OB to the next call of a cyclic interrupt OB. The following figure shows an example of the cycle of a cyclic interrupt. Figure 3-7 Call interval of a cyclic interrupt Accuracy of a cyclic interrupt If a cyclic interrupt is not delayed by a higher-priority OB or communication activities, the accuracy with which it is started is nevertheless subject to system-dependent fluctuations. The following table shows the accuracy with which a cyclic interrupt is triggered: Table 3-5 Accuracy of cyclic interrupts CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Cyclic interrupt ±90 μs ±90 μs ±80 μs ±80 μs ±25 μs 22 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.4 Response time for cyclic and time-driven program processing 3.4 Response time for cyclic and time-driven program processing Introduction In this section you will learn about the concept of "response time", and how to calculate the response time. Definition The response time in the case of cyclic or time-controlled program execution is the time between the detection of an input signal and the change of a connected output signal. Fluctuation of the response time of the CPU The actual response time of the CPU fluctuates between one and two cycle times for cyclic program execution and between one and two cyclic interrupt cycles for time-controlled program execution. You must always reckon with the longest response time when configuring your system. The following figure shows the shortest and longest response times of the CPU to an event. Figure 3-8 Shortest and longest response times of the CPU Function Manual, 02/2014, A5E03461504-02 23

Cyclic program processing 3.4 Response time for cyclic and time-driven program processing Factors To determine the process response time, you must take account of the following factors in addition to the CPU response time described above: Delay of the inputs and outputs at the I/O module Update times for PROFINET IO or DP cycle times on PROFIBUS DP Switching times of the sensors and actuators used Delay at the inputs and outputs of the modules Delays in the response time occur at the inputs and outputs of the modules and as a result of device-internal delays (e.g., interface modules). The delay and cycle times can be found in the technical specifications for the I/O modules. Update time with distributed I/O When distributed I/O are used, the maximum response time is also extended by the bus transmission times of PROFIBUS or PROFINET. These bus transmission times occur when process image partitions are read in and output. The bus transmission times correspond to the bus update cycle of the distributed device. PROFINET IO If you use STEP 7 to configure your PROFINET IO system, STEP 7 calculates the update time. Select the PROFINET interface of the I/O module. In the General tab, select "Advanced options > Real time settings > I/O cycle". The update time is displayed in the field "Update time". PROFIBUS DP If you use STEP 7 to configure your PROFIBUS DP master system, STEP 7 calculates the DP cycle time. Select the PROFIBUS subnet in the network view. In the Inspector window, navigate to the bus parameter in the General tab. The DP cycle time is typically displayed in the "Parameters" field at "Ttr typical". The following figure illustrates the additional bus runtimes using distributed I/O. Figure 3-9 Additional bus runtimes with distributed I/O You can achieve a further optimization of the response times using isochronous mode. 24 Function Manual, 02/2014, A5E03461504-02

Cyclic program processing 3.4 Response time for cyclic and time-driven program processing Reference The following links provide additional information: Tool for calculating the reaction time on PROFINET (http://support.automation.siemens.com/ww/view/en/21869080) Tool for calculating the reaction time on PROFIBUS (http://support.automation.siemens.com/ww/view/en/21178141) Transmission times and isochronous mode in Function Manual PROFINET with STEP 7 V13 (http://support.automation.siemens.com/ww/view/en/49948856); note also the chapter "Tips on assembly" Transmission times and isochronous mode in Function Manual PROFIBUS with STEP 7 V13 (http://support.automation.siemens.com/ww/view/en/59193579); note also the chapter "Network settings" Delays at the input or output of the modules can be found in the manual for the respective device. Device-internal delays can be found in the manuals for the ET 200MP and ET 200SP distributed I/O systems. Function Manual, 02/2014, A5E03461504-02 25

Cyclic program processing 3.5 Summary of response time with cyclic and time-controlled program execution 3.5 Summary of response time with cyclic and time-controlled program execution Estimation of the shortest and longest response time The following formulas may be used to estimate the shortest and longest response time: Estimation of the shortest response time The shortest response time is the sum of: 1 x delay in the I/O module for inputs + 1 x (update PROFINET IO or PROFIBUS DP)* + 1 x transfer time of the process image inputs + 1 x processing of the user program + 1 x transfer time of the process image outputs + 1 x (update PROFINET IO or PROFIBUS DP)* + 1 x delay in the I/O module for outputs = Shortest response time * Time is dependent on the configuration and the extent of the network. The shortest response time is equivalent to the sum of the cycle time plus the input and output delay times. Estimation of the longest response time The longest response time is comprised of: 1 x delay in the I/O module for inputs + 2 x (update PROFINET IO or PROFIBUS DP)* + 2 x transfer time of the process image inputs + 2 x processing of the user program + 2 x transfer time of the process image outputs + 2 x (update PROFINET IO or PROFIBUS DP)* + 1 x delay in the I/O module for outputs = Longest response time * Time is dependent on the configuration and the extent of the network. The longest response time is equivalent to the sum of twice the cycle time plus the delay times of the inputs and outputs. The longest reaction time includes twice the update time for PROFINET IO or twice the DP cycle time on PROFIBUS DP. 26 Function Manual, 02/2014, A5E03461504-02

Event-driven program processing 4 4.1 Response time of the CPUs when program execution is eventcontrolled Introduction In order to detect events in the process immediately in the user program and to react to them with an appropriate program, you use hardware interrupts. In STEP 7, organization blocks OB 40 to OB 47 are provided for processing a hardware interrupt. You can create additional hardware interrupts starting with organization block OB 123. The number of available organization blocks depends on the CPU used. Definition A hardware interrupt is an interrupt that occurs during the running program processing, due to an interrupt-triggering process event. The operating system calls the assigned interrupt OB; as a result, the processing of the program cycle or of lower priority program parts is interrupted. Interrupt response times of the CPUs The interrupt response times of the CPUs start with the occurrence of a hardware interrupt event in the CPU and end with the start of the assigned hardware interrupt OB. This time is subject to system-inherent fluctuations, and this is expressed using a minimum and maximum interrupt response time. The following table contains the length of the response times of the CPUs for hardware interrupts. Table 4-1 Response times of the CPUs for hardware interrupts CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP Interrupt response times Min. 100 μs 100 μs 90 μs 90 μs 20 μs Max. 400 μs 400 μs 360 μs 360 μs 90 μs Note that the times are extended if higher-priority interrupts are queued up for processing, and if the hardware interrupt OB is assigned to a process image partition. You can find these times in the table Times for interrupts (Page 18). Function Manual, 02/2014, A5E03461504-02 27

Event-driven program processing 4.1 Response time of the CPUs when program execution is event-controlled Impact of communication on interrupts Communication tasks are always processed by the CPU with priority 15. If you do not want the interrupt processing to be delayed or interrupted by communication, configure the interrupt processing with priority > 15. The default setting for interrupt processing is priority 16. Reference You can find additional information on the number of available organization blocks in the S7-1500 Automation System (http://support.automation.siemens.com/ww/view/en/59191792) system manual, in the Events and OBs chapter. You can find additional information on the topic of "Configuring hardware interrupts" in the STEP 7 online help. See also User program processing time (Page 17) 28 Function Manual, 02/2014, A5E03461504-02

Event-driven program processing 4.2 Process response time when program execution is event-driven 4.2 Process response time when program execution is event-driven When program execution is event-driven, the process response time is determined by the following: Delay times of the input and output modules used Update times for PROFIBUS/PROFINET, if distributed modules are used Interrupt response time of CPU Runtimes of the interrupt OB including update of the process image partition The following figure shows the individual processing steps for event-driven program processing. Figure 4-1 Schematic representation of event-driven program processing Function Manual, 02/2014, A5E03461504-02 29

Glossary Automation system An automation system in the context of SIMATIC S7 is a programmable logic controller. Cycle time The cycle time represents the time a CPU requires to process the user program once. Cyclic interrupt A cyclic interrupt is generated periodically by the CPU in a configurable time pattern. At this point in time the corresponding organization block is processed. Diagnostic interrupt Modules capable of diagnostics operations report detected system errors to the CPU by means of diagnostic interrupts. Hardware interrupt A hardware interrupt is started by interrupt-triggering modules when a specific event occurs in the process. The hardware interrupt is reported to the CPU. The assigned organization block will be processed according to interrupt priority. Interrupt The CPU's operating system distinguishes between various priority classes that control the processing of the user program. These priority classes include interrupts, e.g. hardware interrupts. When an interrupt occurs, the operating system automatically calls an assigned organization block, in which the user programs the desired response. Process image The process image is part of CPU system memory. At the start of the cyclic program the signal states of the input modules are transmitted to the process image of the inputs. At the end of the cyclic program the process image of the outputs is transmitted as signal state to the output modules. Function Manual, 02/2014, A5E03461504-02 30

Index C Communication Interrupts, 28 Communication load, 19 CPU Interrupt response times, 27 Cycle, 11 Definition, 11 Cycle time, 12 Definition, 12 Different, 13 Process image partition, 16 Update, 16 Cycle time statistics, 15 Cyclic interrupt, 22 Accuracy, 22 Definition, 21 E Error OB Basic time expenditure, 18 H P Process image partitions, 9 processing Time-driven, 8 Processing Event-driven, 8 Program execution, 8 Program execution in the cyclic program, 8 Program execution times Without interruption, 17 Program organization, 8 R Response time Definition, 23 Update time, 24 Response time of CPU, 23 Fluctuation, 23 T Times For one operation, 17, 18 Hardware interrupt, 27 I Impact Communication, 28 Interrupt Basic time expenditure, 18 Interrupt response times CPU, 27 Interruptibility, 9 M Maximum cycle time, 14 Minimum cycle time, 13 Function Manual, 02/2014, A5E03461504-02 31