Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Similar documents
Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Operating Instructions

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Speed monitor D / / 2014

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Documentation. Mains filter AX2090-NF50. Version: Date:

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Operating instructions for AX5801. TwinSAFE drive option card for the AX5000 servo drive. Version: Date:

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Operating instructions Enabling switch (handle switch) ZSD5 ZSD6. 1. About this document. Content. 7 Appendix 7.1 Wiring example...

Original operating instructions Fail-safe inductive sensor GI712S

Original operating instructions Fail-safe inductive sensor GG711S

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

MSI-RM2 Safety Relays

Operating instructions Safety-monitoring module SE-304 C. 1. About this document. Content

User's Manual. english

SNO 4003 K plus. Areas of application for the unit. Connection circuit diagrams. Intended use. Competent persons. Equipment and functional description

SR103AM. User Information for SR103AM. Correct Use

Operating instructions Enabling switch (handle switch) ZSD5 ZSD6. 1. About this document. Content. 7 Appendix 7.1 Wiring example...

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content

English. Operating manual. Limit switch GS125. Keep for future reference. Ventures / brands of GHM

Operating Instructions VEGAMET 381

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

SR101A. User Information for SR101A. Correct Use

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave

Operating manual. Diagnostic adapter VAS Operating manual Diagnostic adapter VAS Client documentation Revision: 00 Version: 05/2018

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Operating Instructions Differential Pressure Transducer PS27

PSR DC/ESP4/2X1/1X2

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Power manual for MACX Analog, MACX Analog Ex, MACX PL, MINI Analog, and MINI Analog Pro signal conditioners. User manual

Vital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit.

PNOZ s1. Safety relays. Operating Manual EN-07

Operating instructions Safety-monitoring module SRB 301ST-230V. 1 About this document

Electronic Temperature Controller. Instruction Manual Version

Installation manual plugs and connectors with screw connection (16/32 A)

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions

PTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions

Operating instructions Hinge safety switch TV.S 335 TV.S About this document. Content

Contact protection relay

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

Extension module for lighting control

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

Original operating instructions Photoelectric safety sensors (safety light grid) with active / passive system OY90xS

Siemens Spares. Preface 1. Scope of Delivery 2 SIPLUS CMS4000. Product Characteristics 3 ION PROFIBUS DP SPY T001 Installation and Maintenance 4

Operating Instructions

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

FACTORY AUTOMATION. MANUAL VAA-2E-G4-SE Original Instructions Version 1.1

BT50(T) Safety relay / Expansion relay

MANUAL VAA-2E2A-G12-SAJ/EA2L Original Instructions Version 1.0

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

DALI Professional Controller-4. Control unit Operating instructions

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5

PSR UC/ESAM4/3X1/1X2/B

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Operating instructions Safety-monitoring module SRB 301MC SRB 301MC-ST. 1. About this document. Content

RТTH DUAL ROOM SWITCH

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Datasheet - SRB 301LC/B-24V

SolConeX extra-low voltage flange socket

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Isolating repeater IRU 420

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Mounting Instruction. Industrial Ethernet Workgroup Switch MACH104 Full Gigabit Family. Mounting Instruction MACH104 Release 07 07/2014

Operating instructions. Monitor FD / / 2013

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

System manual AS-i safety monitor AC041S /00 05/2013

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

Digital ac/dc (24V) Input Module

Industrial motor controller for brushed DC motors 24 VDC

MDM 011-Z1 Regen Resistor

Replacement and Calibration of Electronic Spare (PCB) Cassettes - Rosemount 2120 Vibrating Fork Liquid Level Switch

Documentation KM2002, KM2004, KM2008. Terminal modules with digital outputs, 24 V, 0.5 A. Version: Date:

MANUAL Functional Safety

Installation- and Operating instructions for CU Ethernet Controller with USB Input. Version: 1.4 Date:

PROCESS AUTOMATION. MANUAL Z-System. Zener Barriers ISO9001

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

Operating instructions Door handle switch BNS-B About this document. Content. 6 Disassembly and disposal 6.1 Disassembly Disposal...

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

PRO-1250D CT MID DIN rail three phase four wire energy meter.

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

Transcription:

Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger Straße 1 3 89073 Ulm GERMANY Tel.: +49 731 2061-0 Fax: +49 731 2061-222 E-Mail: info.ulm@mayser.com Internet: www.mayser.com

Contents About these operating instructions... 3 Intended use... 4 Safety instructions... 4 Parts supplied... 5 Transport and storage... 6 Packaging and transport... 6 Storage... 6 Product overview... 6 Connections... 6 LEDs information... 6 Function, installation and commissioning... 7 Function... 7 Installation... 7 Automatic reset... 8 Manual reset... 9 Commissioning... 9 Test function: automatic reset... 9 Test function: manual reset... 10 Recommissioning... 10 Automatic reset... 10 Manual reset... 10 Connection examples... 11 Contacts continued in two-channel mode... 11 Contact duplication for automatic reset... 11 Contact duplication for manual reset... 11 Maintenance and cleaning... 12 Maintenance... 12 Cleaning... 12 Troubleshooting and remedies... 13 Replacement parts... 13 Disposal... 13 Conformity... 14 EC Design Test... 14 Technical Data... 14 Copyright The reproduction, distribution and utilization of this document as well as the communication of its contents without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design. Mayser Ulm 2016 Page 2/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

About these operating instructions These operating instructions are part of the product. Mayser Polymer Electric accepts no responsibility or warranty claims for damage and consequential damage due to failure to observe the operating instructions. Read operating instructions carefully before use. Keep operating instructions for the complete service life of the product. Pass operating instructions on to every subsequent owner or user of the product. Add any supplement received from the manufacturer to the operating instructions. Validity Target group Other applicable documents These operating instructions are only valid for the products specified on the title page. The target group of these operating instructions are operators and trained specialist personnel who are familiar with installation and commissioning. In addition to the operating instructions, observe the following documents: Drawing of the sensor system (optional) Wiring diagram (optional) Installation instructions of the sensors used Symbols used Symbol Meaning Ä Ä... 1.... 2.... 3.......... (see section Installation) Action with one step or with more than one step where the order is not relevant. Action with more than one step where the order is relevant. Bullets first level Bullets second level Cross-reference 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 3/15

Danger symbols and information Symbol DANGER Meaning Immediate danger leading to death or serious injury. WARNING Imminent danger which may lead to death or serious injury. CAUTION Possible danger which may lead to minor or moderate injuries. Information on easier and safer working practices. Intended use The Control Unit is designed for signal processing of a pressure-sensitive protective device (PSPD). It evaluates the output signals of sensors with monitoring resistor 8k2. The integrated output signal switching device (OSSD) transmits the evaluated safety signals directly to the downstream control. The Control Unit complies with ISO 13849-1:2006 Category 3 PL e. So that the safety classification is retained, the downstream control must be of the same or a higher category. Safety instructions Ä Ä Do not open the Control Unit Never open, tamper with or alter the Control Unit. Check supply voltage Check supply voltage. It must correspond with the connecting voltage U S on the type plate. Observe protection class Only use the Control Unit in rooms with a minimum degree of protection of IP54 (e.g. switch cabinet). Maintain distance When installing in the switch cabinet, ensure sufficient distance from heat sources (at least 2 cm). Page 4/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

Observe pin assignment Observe pin assignment when connecting the supply voltage. Protect relay contacts Risk of welding: Protect the relay contacts externally. Fit spark absorbers When connecting inductive loads, fit spark absorbers (RC modules) to the consumer. Do not cross link Control Unit Do not cross link the Control Unit with other Control Units. Terminals Y1, Y2 and 5, 6 and 7, 8 are not voltage free. Do not overload Control Unit Ensure that the specified switching current is not exceeded. Continue redundancy Make sure you wire the unit directly in the control circuit or that the downstream control is also in dual channel mode. In the event of a fault, put out of operation In the event of malfunctions and visible damage, put the Control Unit out of operation. Do not use in ATEX zones Do not use the Control Unit in potentially explosive environments (ATEX). The Control Unit is not authorised for use in these zones. Parts supplied 1 Control Unit Enclosure with electronics module and plug-in connectors. 1 Operating Instructions 1 Declaration of Conformity Upon receipt of the parts supplied, check immediately for completeness and good condition. 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 5/15

Transport and storage Packaging and transport The Control Units are packed individually in cardboard boxes. Several Control Units are stacked in one large cardboard box. The documents are enclosed separately. Storage Store the Control Units in the original packaging in a dry place. Observe the storage temperatures given in the technical specifications. Product overview Connections Connections: Terminals: Supply voltage A1, A2 channel 1 (Channel 1) 13, 14 channel 2 (Channel 2) 23, 24 Signal circuit 31, 32 Reset 5, 6 Auto-Reset 7, 8 Sensor Y1, Y2 LEDs information yellow LED K1 ON : Sensor not activated yellow LED K2 ON : Sensor not activated Page 6/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

Function, installation and commissioning Function The single-fault-safe electronics module has dual channels (redundant). Each channel controls a forceguided relay and additionally monitors the relay of the other channel. The electronic system monitors the electrical resistance of the sensor with a defined zero signal current. When the sensor is not actuated and after a reset, the relays K1 and K2 are energised. The yellow LEDs K1 ON and K2 ON are on, the switching channels 1 and 2 are closed and the signal circuit is open. When the sensor is actuated, the K1 and K2 relays are de-energised. The yellow LEDs K1 ON and K2 ON go out, the switching channels 1 and 2 are open, and the signal circuit is closed. If the sensor cable breaks, relays K1 and K2 are de-energised. The yellow LEDs K1 ON and K2 ON go out, the switching channels 1 and 2 are open, and the signal circuit is closed. The signal circuit works opposed to the switch channels 1 and 2. Installation WARNING Danger of injury due to electrocution! Disconnect all devices and live parts in the immediate environment of the power supply and protect them against being switched on again (see relevant operating instructions). Check that all devices and parts are disconnected from the power supply. CAUTION Impaired operation due to overheating or incorrect degree of protection The operation of the protective device may be impaired due to overheating of the Control Unit or due to incorrect choice of degree of protection. When installing in the switch cabinet, ensure sufficient distance from hest sources (at least 2 cm) Only use the Control Unit in zones that have a min. protection class of IP54 (eg. switch cabinet) 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 7/15

1. The enclosure of the Control Unit can be mounted in any position on a 35 mm IEC 60715 rail. CAUTION Overall safety endangered The quality and reliability of the interface between the protective device and the machine influences the overall safety. Install the interface very carefully 2. Wire the sensors, switching channels, signal circuit and supply voltage to the terminals. channel 1 channel 2 Signal circuit Reset Auto-Reset Sensor Automatic reset A bridge is necessary for automatic reset (without reset). The unit is supplied with a bridge already connected between cable terminals 7 and 8. Check if the bridge is set between cable terminals 7 and 8. Page 8/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

Manual reset For manual reset (with reset), a switch must be connected between cable terminals 5 and 6. The control unit reacts when the switch changes from not activated to activated, i.e. if the switch sticks, no reset command is initialised. Remove the bridge between cable terminals 7 and 8. Wire up a switch between cable terminals 5 and 6. Commissioning 1. Make sure the plug connections are firmly attached. 2. Connect the supply voltage. WARNING Danger of injury due to electrocution! Never disconnect terminals with the power on. Never unplug plug connections with the power on. Test function: automatic reset 1. Make sure no sensors are activated. yellow LEDs K1 ON and K2 ON are on contacts of switching channels 1 and 2 closed signal circuit open 2. Activate a sensor. yellow LEDs K1 ON and K2 ON go off contacts of switching channels 1 and 2 open signal circuit closed 3. Repeat step 1. 4. Disconnect the sensor. yellow LEDs K1 ON and K2 ON go off contacts of switching channels 1 and 2 open signal circuit closed 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 9/15

Test function: manual reset 1. Make sure no sensors are activated. yellow LEDs K1 ON and K2 ON are out contacts of switching channels 1 and 2 open signal circuit closed 2. Activate the reset switch. yellow LEDs K1 ON and K2 ON are on contacts of switching channels 1 and 2 closed signal circuit open 3. Activate a sensor. yellow LEDs K1 ON and K2 ON go off contacts of switching channels 1 and 2 open signal circuit closed 4. repeat steps 1 and 2. 5. Disconnect the sensor. yellow LEDs K1 ON and K2 ON go off contacts of switching channels 1 and 2 open signal circuit closed Recommissioning WARNING Danger of injury! Never start your machine as long as the risk remains. Automatic reset The Control Unit works without reset. If the sensor is enabled after actuation, relays K1 and K2 re-energise after a delay t w Check for proper functioning after recommissioning (see section Commissioning) Manual reset The Control Unit works with reset. Relays K1 and K2 are only energised after the reset switch is actuated. Check for proper functioning after recommissioning (see section Commissioning) Page 10/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

Connection examples Contacts continued in two-channel mode channel 1 channel 2 Contact duplication for automatic reset channel 1 channel 2 Contact duplication for manual reset channel 1 channel 2 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 11/15

Maintenance and cleaning Maintenance The Control Unit is maintenance-free. Repeat the operational test monthly. Cleaning WARNING Danger of injury due to electrocution! Disconnect the Control Unit as well as all devices and live parts in the immediate environment of the power supply and protect them against being switched on again (see relevant operating instructions). Check that all devices and parts are disconnected from the power supply. Clean the outside of the enclosure with a dry cloth. Page 12/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

Troubleshooting and remedies Prerequisite: the Control Unit is connected to the supply voltage and sensor. No sensor is activated. Fault display Possible cause Remedy yellow LEDs K1 ON No or incorrect supply voltage 1. Check supply voltage, compare with and K2 ON are out type plate Incorrect monitoring resistor on sensor If monitoring resistor is correct: sensor is faulty No sensor connected Sensor incorrectly connected Cable break Manual reset: reset switch not actuated 2. Check terminal connections Connect sensor with monitoring resistor 8k2 Replace sensor Connect sensor Check terminal connections Replace sensor Actuate reset switch Manual reset: reset switch sticks Automatic reset: bridge missing Control Unit is faulty Replace switches on terminals 5 and 6 Connect bridge between terminals 7 and 8 Replace Control Unit Only one LED is on Incorrect supply voltage Check supply voltage, compare with type plate Control Unit is faulty Replace Control Unit Fault can still not be detected? Contact Mayser-Support: Tel. +49 731 2061-0. Replacement parts CAUTION Overall safety endangered If the sensor and Control Unit are not replaced with original parts from Mayser, operation of the protective device may be impaired. Only use original parts from Mayser. Disposal The devices produced by Mayser are professional electronic tools exclusively intended for commercial use (so-called B2B devices). Unlike devices mainly used in private households (B2C), they may not be disposed of at the collection centres of public sector disposal organisations (e.g. municipal recycling depots). At the end of their useful life, the devices may be returned to us for disposal. WEEE reg. no. DE 39141253 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 13/15

Conformity The design type of the product complies with the basic requirements of the following directives: 2006/42/EC (Safety of Machinery) 2004/108/EC (EMC) The Declaration of Conformity is available in the Downloads section of the website: www.mayser-sicherheitstechnik.de EC Design Test The product was tested by an independent institute. An EC design type test certificate confirms conformity. The EC design type test certificate is available in the Downloads section of the website: www.mayser-sicherheitstechnik.de Technical Data SG-EFS 1X4 ZK2/1 8k2 AC 24 V / DC 24 V AC 230 V Testing basis EN 12978, ISO 13849-1, ISO 13856-1, ISO 13856-2, ISO 13856-3 Supply voltage U S Voltage tolerance Nominal current Nominal frequency External protection Short-circuit current (max.) Power consumption Times Reaction time t a Re-start time t w Safety classifications ISO 13856: Reset ISO 13849-1:2006 MTTF d PFH d DC avg B 10d (Load: DC 24 V / 2 A) n op (estimate) CCF EN 60664-1: Creep distance and air gap -15% to +10% / -15% to +20% 220 ma / 112 ma 48 to 62 Hz / 250 ma slow-acting < 6 VA / < 4 W < 10 ms < 190 ms with/without Category 3 PL e 313 years 4.29 10-8 1/h 90% 2 10 6 52560 per year Requirements fulfilled soiling degree 2, overvoltage category II / 230 V, basic insulation -15% to +10% 28 ma 48 to 62 Hz 250 ma slow-acting < 7 VA < 10 ms < 190 ms with/without Category 3 PL e 313 years 4.29 10-8 1/h 90% 2 10 6 52560 per year Requirements fulfilled soiling degree 2, overvoltage category II / 230 V, basic insulation Page 14/15 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 130116 v3.2

SG-EFS 1X4 ZK2/1 8k2 AC 24 V / DC 24 V AC 230 V Inputs Sensor Monitoring resistor Short-circuit resistance Line resistance Line length (max.) thresholds Sensor activated Cable break Outputs channel 1 and 2 (NO contact) Utilization category as per EN 60947-5-1 voltage (max.) current (max.) current (min.) capacity (max.) operations, mechanical operations, electrical Contact fuse protection external Signal circuit (NC contact) voltage (max.) current (max.) operations, mechanical operations, electrical Contact fuse protection external Mechanical operating conditions Cable terminals solid wire strand without sheath strand with sheath Degree of protection as per IEC 60529 max. humidity (23 C) Operating temperature Storage temperature Impact resistance in operation Impact resistance transport Dimensions (W H D) Weight Y1, Y2 8k2 Ohm 400 Ohm 100 Ohm 100 m < 3k9 Ohm > 12k5 Ohm 13, 14 / 23, 24 AC-12: 250 V / 2 A DC-12: 24 V / 2 A AC 250 V DC 24 V 2 A 2 A 10 ma 10 ma 500 VA 48 W > 5 10 7 > 3 10 5 (AC 250 V / 2 A) 2 A quick-acting 31, 32 AC 42 V DC 42 V 100 ma 100 ma > 5 10 6 > 1 10 6 (AC 42 V) 0.1 A quick-acting 1 2.5 mm 2 or 2 1 mm 2 1 2.5 mm 2 or 2 1.5 mm 2 1 2.5 mm 2 or 2 1 mm 2 IP20 95% -20 to +50 C -20 to +50 C 2.5 g 10 g 45 75 105 mm 180 g Y1, Y2 8k2 Ohm 400 Ohm 100 Ohm 100 m < 3k9 Ohm > 12k5 Ohm 13, 14 / 23, 24 AC-12: 250 V / 2 A DC-12: 24 V / 2 A AC 250 V DC 24 V 2 A 2 A 10 ma 10 ma 500 VA 48 W > 5 10 7 > 3 10 5 (AC 250 V / 2 A) 2 A quick-acting 31, 32 AC 42 V DC 42 V 100 ma 100 ma > 5 10 6 > 1 10 6 (AC 42 V) 0.1 A quick-acting 1 2.5 mm 2 or 2 1 mm 2 1 2.5 mm 2 or 2 1.5 mm 2 1 2.5 mm 2 or 2 1 mm 2 IP20 95% -20 to +50 C -20 to +50 C 2.5 g 10 g 45 75 105 mm 282 g 130116 v3.2 Operating Instructions SG-EFS 1X4 ZK2/1 8k2 Page 15/15