GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner

Similar documents
EX200-HART. Compact Electronic Actuator Positioner for use in EX2010A System. Features. Simple two-step calibration

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

SX90 Process Controller

Proportional Control Unit (PCU)

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

PEAKTRONICS DHC-100 FEATURES. Digital High-Resolution Controller

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

BA505C 2-wire 4/20mA manual setpoint station Issue 6

High Performance Tension Controller HPTC Electrical Connection Manual

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

LC2300 Level Controller Installation and Maintenance Instructions

Operating and Maintenance Instructions

Controller module. Brief description. Features. Block structure. Page 1/7. Data Sheet

LCI User Manual mantracourt.com

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016

Controller module. Brief description. Features. Block structure. Data Sheet Page 1/7

POSITION MONITOR USERS MANUAL POM-M2 / POM-M3. Content

EM2020 Selectable AC transducer A (UK)

TVC Positioner OPERATING & MAINTENANCE MANUAL

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview

9823 Multifunction Calibrator Calibration Adjustment Procedure

SLIMCON-6 24V DC POWERED ISOLATING SIGNAL CONVERTER

J3C-H20DPS 25Nm Smart Electric Actuator Type: J3C Model: H20DPS

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Series 8000 RF Signal Switch Solution

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

E-STOP relays, safety gate monitors

4100 and 4100/R Controllers

VA-7700 Series. Electric Valve Actuators. Product Bulletin

DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

MAINS DISTRIBUTION UNIT MDU14-CO

Installation, Operation and Maintenance Instructions

Operating Manual. Dynisco /8 DIN Indicator Concise Product Manual

For full product information, visit Use the SpeedSpec code or scan the QR Code for quick access to the specific web page.

Panel Installation Datasheet

E-STOP relay, safety gate monitor

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

MP-2000 Dual Channel LVDT/RVDT Readout/Controller

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

Electromotive actuators for combi valves

Series 8000 RF Signal Switch Solution

DELOMATIC - MULTI-FUNCTION SYSTEM PART 2 INSTALLATION INSTRUCTION

E-STOP relays, safety gate monitors

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd

VISY-Output 8. Technical Documentation. 8-Channel relay output module. Version: 3 Edition: Art. no.:

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

Electric Actuators and Control Systems. Established Leaders in Valve Actuation AD Instruction Manual. Publication P972E Issue 08/09

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

DEEP SEA ELECTRONICS PLC

Assembly instruction / User manual

RT4B-110V/12A RECTIFIER

LED indicators for normal/fault operating conditions, setup mode, loss of analog signal, and solid-state motor control output.

STUDIO 1800 OPERATING INSTRUCTIONS MANUFACTURED IN THE UK

Tempco Instruction Manual

Electric Actuator Smart Controller

DEEP SEA ELECTRONICS PLC

Operating Instructions. For. Level Control Module. Model SSR 1000

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

MINI MCR-SL-PT100-UI(-SP)(-NC)

Safe monitoring relays

ACT-1B Series Panel Tachometer

MODCELL 2050R Single Loop Controllers

ATS Automatic transfer switches Advanced version

Electric Actuators Type 5824 (without fail-safe action) Type 5825 (with fail-safe action)

Input Frequency: 650 range 50/60Hz 675 range Hz Input Ranges in Amps: Measurement Maximum Inrush

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

I/O module, analogue outputs and universal inputs

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

PTC/PT100 board 2.0 Option

********SERVICE MANUAL******** MODELS:

E-STOP relays, safety gate monitors

Isolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

INSTALLATION & OPERATING MANUAL

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications

BVRD Network. Installation Instructions

CM Series. Most Diverse and Flexible Line of Coded Magnetic Safety Interlock Switches and Controllers. Description. Safety Interlock Switches

HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control

DALI Professional Controller-4. Control unit Operating instructions

HAT260 ATS (Automatic Transfer Switch) Controller USER MANUAL. Smartgen Technology

9000C INDEX APPLICATION EXAMPLE 1 SPECIFICATION 2 SAFETY AND WARNING... 3 CONNECTION 3 INSTALLATION.. 4 ORDERING CODE 4 TROUBLE SHOOTING 4

Sound Analyser Real Time 1/1 & 1/3 Octave band Analysis

Operating Instructions VEGAMET 381

/8 DIN Motorized Valve Controller

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

IQM & IQML RANGE CONTROL AND MONITORING FACILITIES. Publication E420E issue 7/02

Line Impedance Stabilization Network (LISN)

Up to two expansion cards can be added; these cards may either add an additional 4 analogue or 8 digital inputs.

Sollatek SVS Range Voltage Stabilisers User Manual

Installation Manual for D244X Series 24-volt Power Supplies

Operating instructions. Standstill monitor A / / 2011

Transcription:

GS400 Electronic Auto-Ranging DIN Panel Mounted Positioner Features * AC (115/230V) and DC (24V) versions available. * Accepts either current or voltage command signal and either current, voltage, or three wire potentiometer feedback signal (type and range to be stated when ordering). * Quick, four step, calibration sequence. * An internally excited 4-20mA current output proportional to the actuator position. * Manual mode which allows positioning by operation of front panel switches. * Manual and Calibration mode entry protection. * Housed in a DIN 43700, 72mmx72mm panel mount case - optional IP66 front cover. * End of travel limit switch interlock and indication. Operation The GS400 is designed to be used for the closed loop positioning of reversing actuators. The instrument compares two analogue signals, one representing the desired position (command signal) and the other representing the actual position (feedback signal) of the actuator. A difference between these two signals will cause the outputs to operate, driving the actuator to the desired position. A positional dead band may be adjusted to overcome instability associated with mechanical overrun of the actuator. Wiring The GS400 rear terminals should be wired by a competent person to accepted electrical practices. Special attention should be given to the safe connection, routing, and fusing of the instrument supply and the actuator supply. AN EARTH CONNECTION MUST ALWAYS BE MADE TO TERMINAL 1. To ensure RFI compliance the analogue signals MUST be routed in copper braided screened cables with a fill factor density of at least 0.7. The screens should be terminated at the rear panel earthing block end only. Signal cables should be routed separately from power and switching conductors. The use of a bulk supply filter on the general system supply, including that to the actuator is recommended. Declaration of Conformity EMC Directive 89/336/EMC Relevant Standards EN50081-1 (Emissions) EN50082-1 (Immunity) This product has been successfully tested to the relevant parts of the above standards. In order to retain this conformity the user must fully comply with the wiring instructions. Orange Instruments Limited Lower Farm Rd, Moulton Park, Northampton, NN3 6XF. U.K. Tel : +44 (0)1604 790490 Fax: +44 (0)1604 790690 8911/997 Iss:D Modlog 1507 Date: 27/04/00 Author:AGM File: GS400\Handb\8911D.doc Page : 1 of 6

First time operation WARNING!! The GS400 will always power-up into AUTO mode and therefore, the actuator and associated mechanical equipment connected to it could possibly move in an unpredictable manner during first time use and initial calibration. Ensure that all personnel take appropriate precautions. 1. Ensure that end of travel limit switches and mechanical stops are correctly adjusted before operation. 2. Check the GS400 rear data label details for compatibility with the site supply, command, feedback, and re-transmitted position signals. 3. Make all connections. If the re-transmitted position signal is not required then terminals 16 and 17 will need to be connected together to complete the loop and display the position on the front panel. 4. If an external manual/calibration mode enable contact has been wired to terminals 11 and 18, then this contact should be closed (enabled). Alternatively, temporarily connect terminals 11 and 18 together. 5. Apply the instrument supply. The GS400 will always power-up into AUTO mode and actuator movement may be observed. In AUTO mode either or both the LOW and HIGH lights should be lit continuously. Press and release the centre button to enter MANUAL mode In MANUAL mode either or both the LOW and HIGH lights should be extinguished continuously. 6. In MANUAL mode operate the Increase and Decrease buttons. Check for the correct operation of the actuator. The appropriate light should show and as the actuator operates the front panel display should change in sympathy. If at any stage the LOW or HIGH lights are flashing then this indicates that the relevant limit switch has been activated and the GS400 will prevent the actuator from operating in that direction. A feint flickering of the HIGH and LOW lights during manual operation is normal. If there is no actuator movement or the actuator direction is reversed, then remove the supplies and check the wiring - particularly the actuator motor and the feedback potentiometer connections. Calibration These procedures require access to the rear of the GS400 whilst power is connected, and should therefore only be undertaken by suitably trained personnel. Direct connections are made to the internal microprocessor so the user is advised to take anti-static precautions to minimise damage due to body charge. To enter the calibration mode the external enable contact should be made or alternatively terminals 11 and 18 should be connected together. The following steps form a complete sequence. If the sequence is interrupted (e.g. power supply failure) then the calibration will have to be re-started. 1. Connect a command signal source to terminals 11 (-ve) and 12 (+ve). Connect a DVM (set to 200mA range) to terminals 16 (+ve) and 17 (-ve) to monitor the re-transmitted position signal. 2. Apply the instrument power. CAUTION - The GS400 will always power-up in AUTO mode 3. Press and hold the centre button (for approx. 5 seconds) until both the LOW and HIGH lights extinguish. Release the button. AUTO mode will be suspended during calibration. 8911/997 Iss : D Modlog 1507 Date : 27/04/00 Author : AGM File : GS400\Handb\8911D.doc Page : 2 of 6

STEP A - Positional Calibration (Minimum) i Check that the LOW light is pulsing (flashing if the limit switch is activated). ii Set the command signal source to the desired minimum value (e.g. 4mA). iii Operate the Increase and Decrease buttons to drive the actuator to the desired minimum position. iv Press and release the centre button to store the settings into memory and to advance to step b. STEP B - Positional Calibration (Maximum) i Check that the LOW light is lit continuously (flashing if the limit switch is activated). ii Set the command signal source to the desired maximum value (e.g. 20mA). iii Operate the Increase and Decrease buttons to drive the actuator to the desired maximum position. iv Press and release the centre button to store the settings into memory and to advance to step c. STEP C - Re-transmitted Position Signal Calibration (Minimum) i Check that the HIGH light is pulsing (flashing if the limit switch is activated). ii Adjust the command signal source until the desired reading is obtained on the DVM (e.g. 4mA), for the actuator minimum position. Note : The actual output of the command signal source should be ignored as it will be different to the reading on the DVM. iii Press and release the centre button to store the settings into memory and to advance to step d. STEP D - Re-transmitted Position Signal Calibration (Maximum) i Check that the HIGH light is lit continuously (flashing if the limit switch is activated). ii Adjust the command signal source until the desired reading is obtained on the DVM (e.g. 20mA), for the actuator maximum position. Note : The actual output of the command signal source should be ignored as it will be different to the reading on the DVM. iii Press and release the centre button to store the settings into memory and to exit the calibration sequence. CAUTION - After exiting the calibration sequence the GS400 will return to the AUTO mode. 4. Adjust the command signal source over the desired range and check that the actuator positions accordingly. Check that the correct re-transmitted position signal is also obtained. 5. The actuator may hunt about the desired position and not settle. The dead-band trimmer potentiometer (located on the right hand side of the GS400) should be adjusted (clockwise to increase) to overcome this hunting, but not too much so as to impair the positional accuracy. The dead-band is factory set at approximately 0.5% of the command signal span. This setting should give stable positioning for medium speed (20-40 second transit) actuators. Faster actuators, or those with significant mechanical backlash in the feedback sensor, may require a wider dead band. Slow, precision actuators may well perform better with an even narrower dead band. Note however, that the dead band can be set to zero when any stable positioning will be impossible. 6. The front panel display is factory set to read 0-100 over a re-transmitted signal range of 4-20mA. If any other display range is required or another re-transmitted signal range is used, then the display will require recalibrating. Two trimmer potentiometers are located on the left hand side of the instrument. The forward adjustment sets the display zero and the rear adjustment sets the display span. The adjustments are optimised for the 0-100 range, but it is possible to display as low as 0-20 although there will be an increase in coarseness of the adjustment. The zero and span adjustments have a significant interaction, so re-calibration can be a tedious process. Maintenance The GS400 is not user serviceable. It is recommended that the instrument and the actuator supplies are suitably protected by fuses or circuit breakers rated for the instrument and the full load current of the actuator If a fault occurs then please return the unit to Orange Instruments, describing the nature and circumstances of the problem. 8911/997 Iss : D Modlog 1507 Date : 27/04/00 Author : AGM File : GS400\Handb\8911D.doc Page : 3 of 6

Connections LOWER TERMINAL BLOCK 1 Supply : EARTH 2 Supply : LIVE (AC) or +(DC) 3 Supply : NEUTRAL (AC) or 0V (DC) 4 Supply select : For 115VAC supply link terminal 4 to terminal 5. 5 Supply select : For 230VAC supply - link terminal 5 to terminal 6. 6 Supply select : For 230VAC supply - link terminal 5 to terminal 6. 7 Supply select : For 115VAC supply - link terminal 6 to terminal 7. 8 Output : Decrease output switched Live (AC) or + (24VDC). 9 Output : Increase output switched Live (AC) or + (24VDC) 10 Common : Actuator supply Live (230VAC max.) or + (24VDC) UPPER TERMINAL BLOCK 11 Command signal : Current/Voltage -ve Manual/Cal. Enable : Connect to terminal 18 to enable entry to Manual and Calibration modes. 12 Command signal : Current/Voltage +ve 13 Feedback Signal : Pot Minimum or Current/Voltage -ve Limit switch : Common return 14 Feedback Signal : Pot Wiper or Current/Voltage +ve 15 Feedback Signal : Pot Maximum (No connection if Current/Voltage) 16 Position Output : Current +ve 17 Position Output : Current -ve 18 Manual/Cal. Enable : Connect to terminal 11 to enable entry to Manual and Calibration modes. 19 High limit switch : Switch made during normal operation, opens at limit. 20 Low limit switch : Switch made during normal operation, opens at limit. NOTE - The LOWER terminal block carries the high voltage instrument supply and load switching connections. DO NOT swap the upper and lower connectors - double-check when re-connecting the plug-in terminals. ACTUATOR SUPPLY Fuse and filter up to 2A max. N (0V) L (+) INSTRUMENT SUPPLY Fuse and filter to 100mA L (+) N (0V) E 230VAC Link 10 2 3 1 6 5 Connections shown for a 230VAC supply instrument with potentiometer feedback Increase 9 Actuator Motor wiper Decrease 8 14 16 17 +ve -ve Re-transmitted Position Signal min Feedback Pot max 15 13 Earth Block 12 11 +ve -ve Command Signal 19 High limit Low limit 20 18 Manual/ Calibrate Enable 8911/997 Iss : D Modlog 1507 Date : 27/04/00 Author : AGM File : GS400\Handb\8911D.doc Page : 4 of 6

Front Panel Indicator Descriptions Auto/Manual Modes HIGH LOW Description On On Auto mode. Neither limit switch activated On Flashing Auto mode. Low limit switch activated Flashing On Auto mode. High limit switch activated Off Off Manual mode. Neither limit switch activated Off Flashing Manual mode. Low limit switch activated Flashing Off Manual mode. High limit switch activated Calibration Mode HIGH LOW Description Off Pulsing Step 1. Position zero Off On Step 2. Position span Pulsing Off Step 3. Re-transmitted position signal zero On Off Step 4. Re-transmitted position signal span Note : If a limit switch is activated then the relevant light will flash and not pulse or be on Fault Finding Guide SYMPTOM The display and lights do not function The buttons have no effect The display shows -25.0 The display reading travels in the opposite direction to that expected Both the LOW and HIGH lights flash The actuator does not operate in either Auto or Manual modes The actuator does not operate in Auto but does operate in Manual. The INC and DEC lights are always operating and the actuator does not settle at the desired position ACTION Check the instrument supply fuse Check all connections are correct and secure Check that the feedback connections are correct and secure Check that the feedback connections are correct Check that the limit switches are correctly adjusted and correctly connected Check the actuator supply fuse Check that all connections are correct and secure Calibrate the instrument Increase the Dead-band 8911/997 Iss : D Modlog 1507 Date : 27/04/00 Author : AGM File : GS400\Handb\8911D.doc Page : 5 of 6

Specification Instrument Supply AC : 115V or 230V (+/- 10%) 50/60Hz. Instrument only loading 3VA maximum DC : 24V (18-36V) Instrument only loading 4VA maximum Command Signal Input Voltage : In the range 0 to 10V DC (Input Impedance 66K) Current : In the range 4 to 20mA DC (Input Impedance 200R) Feedback Signal Input Potentiometer : In the range 1K0 to 100K, 3 wire type Voltage : In the range 0 to 10V DC (Input Impedance 66K) Current : In the range 4 to 20mA DC (Input Impedance 200R) Re-transmitted Position Signal Output (Internally Excited) Current : In the range 0 to 20mA DC (Maximum Load 750R) Switched Outputs AC outputs - Solid State Relays with an external common supply feed Rated at 2A, 70V to 250V AC @ 50/60Hz isolated from the instrument to 4000V rms. CR Suppression network incorporated DC outputs - High side FET switches 2A maximum each, with an external common supply feed. Adjustments Auto / Manual selection button. Positional Dead-Band adjustment Manual Increase / Decrease buttons Display zero and span adjustments Environmental Rating (with module secured in panel) - IP51 (IP66 with optional cover) Operating Temperature : 0 to 50 deg. C. Microprocessor operating frequency - approx 30KHz (RC oscillator) Theoretical accuracy Analogue to digital / digital to analogue conversion - 12bits (range of 1 in 4096) Comparator resolution - +/- 1bit Typical positional accuracy (mainly mechanical backlash and inertia) - +/-1% 8 12 GS400 100.0 LOW DEC INC HIGH 72 DEAD-BAND Adjustment 67 11 20 EARTH BLOCK DEC MAN INC 1 10 up POSITIONER 72 100 67 Display span Display zero 8911/997 Iss : D Modlog 1507 Date : 27/04/00 Author : AGM File : GS400\Handb\8911D.doc Page : 6 of 6