f) Telecommunications Equipment Rooms

Similar documents
Communications. UNM IT/Telecommunications Guide Specification Communications

Tarleton State University. Specifications

SPECIFICATION STANDARD

Copper Riser And Intrabuilding Cabling

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

Communication

ANSI/TIA/EIA-568-B Cabling Standard

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

Telecommunications Structured Cabling Systems

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

The six major components of a structured wiring system are:

Peter Sharp RCDD IBI Group

The Riser as a Contract Document. Peter Sharp, RCDD

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Design Guidelines for Facilities Construction:

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

Atras Network Communications

Los Angeles Community College District Design Standards

Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.

Chapter 1 Introduction to Outside Plant

Division 27 Master Specification for

Bonding and grounding NETCONNECT copper cabling systems

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

Cabling a Data Center to TIA-942 Standard

DIVISION 27 COMMUNICATIONS

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS

Data Center Design and the ANSI/TIA-942 Standard

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

SECTION FARE COLLECTION SYSTEM

ANSI/TIA/EIA-568-B Cabling Standard

PANGEN SYSTEM WARRANTY. Warranty Guide

Cabling Infrastructure

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

Standards-based Labelling: The Key to Effective Network Cabling Plan. Lin Huanyu Market Development, Regional Manager Brother International Singapore

Structured Cabling Guidelines

SECTION COMMUNICATIONS BACKBONE CABLING

Physical Layer V What does the physical layer provide?

17. Microwave Collocation 17.1 General

Connectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture

Classroom WiFi Network Infrastructure Plan

Structured Cabling Guidelines For The State Of Oregon

Technology Standards

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Computer Network Design Guide Existing Systems 1 / 6

University of Arkansas at Little Rock

APPENDIX B GLOSSARY. ADAAG: Americans with Disabilities Act Accessibility Guidelines.

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Leveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee

USER GUIDE. AXIS T8120 Midspan 15 W 1-port ENGLISH

Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution

United Telephone Company of Indiana, Inc. d/b/a CenturyLink Section 1 CENTURYLINK GUIDEBOOK EXPLANATION OF TERMS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

PIONEERS OF The Structured Cabling Systems

Newark, Delaware Architectural Engineering Senior Thesis Portfolio

ANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions

BICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS

How You Can Optimize Passive Optical LAN Through Structured Cabling

PN Telecommunications Infrastructure Standard for Data Centers Draft 2.0 July 9, 2003

Request for Proposal George West Independent School District ERate

Wire Communications Design jfm 07. An Inside Look at Outside Plant

Master Format Division 27 - Communications

Communications Updated April

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

Anixter Standards Reference Guide

Cabling Infrastructure

INTERNATIONAL STANDARD

ANSI/TIA/EIA-568-B Cabling Standard NOTE

Communications Infrastructure Specification

LACCD IT Design Standards

With the publication. Make the right connection: Bonding a shielded system. installation

THE INTERCONNECTED NETWORK

Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"

2 Telecommunications Data Center Facility Requirements

IoT and Intelligent Building Challenges in ICT

CERTIFICATION PLUS SM

Cables and Connectors

Liebert MPX Rack Power Distribution Unit (PDU) Guide Specifications 1.0 GENERAL 1.1 SUMMARY

Canadian Codes & Standards Updates

Get Labels for your Cables

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template.

SPECIAL SPECIFICATION 1303 Lifelink

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

The following pages contain a guide for the installation

Mayhew Technology Solutions

INTERNATIONAL STANDARD

Transcription:

SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of the installation. The approved contractor, installation entity or agent is held responsible to be familiar with the provisions contained herein and is assumed to possess the knowledge, manpower, and materials applicable to the completion of the installation. B. PROJECT SCOPE OF WORK 1. Related Sections from Division 27: Communications a) 27 05 26 Grounding and Bonding for Communications Systems b) 27 05 28 Pathways for Communications Systems c) 27 05 36 Cable Trays for Communications Systems d) 27 05 44 Sleeves and Sleeve Seals for Communications Pathways and Cabling e) 27 05 53 Identification for Communications Systems f) 27 1100 Telecommunications Equipment Rooms g) 27 11 16 Communications Cabinets, Racks, Frames, and Enclosures h) 27 11 19 Communications Termination Blocks and Patch Panels i) 27 13 23 Communications Optical Fiber Backbone Cabling j) 27 15 13 Communications Copper Horizontal Cabling k) 27 15 33 Communications Coaxial Horizontal Cabling 1) 27 15 43 Communications Faceplates and Connectors m) 27 51 16 Public Address and Mass Notification Systems 2. Related Sections from Division 28: Electronic Safety and Security a) 28 16 00 Intrusion Detection b) 28 23 19 Digital Video Recorders c) 28 23 29 Video Surveillance Devices and Sensors 3. Related Sections from Division 01: General Requirements a) 01 11 00 Summary of Work b) 01 25 13 Product Substitution Procedures c) 01 33 00 Submittal procedures d) 01 43 00 Quality Assurance e) 01 45 00 Quality Control f) 01 60 00 Product Requirements 14.14.001 COMMUNICATIONS 270000-1

g) 01 86 29 Communications Performance Requirements 1.2 SECTION/PROJECT INCLUDES A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, testing and labeling of all telecommunications infrastructure as described on the Drawings and/or required by these Project specifications. 1.3 INTENT OF DRAWINGS AND SPECIFICATIONS A. These Specifications, together with the Drawings accompanying them, are intended to depict the installation requirements necessary to support this Project. Contractor shall furnish materials shown and/or called for on the Drawings but not mentioned in the Specifications, or vice versa, that are necessary for the installation and support of communications cabling whether or not specifically called for in both documents. In addition, the Contractor shall provide incidental equipment and materials required for the completion of systems included in this contract whether or not specified or shown on the drawings. 1.4 DEFINITIONS A. Building/Main Distribution Frame - (BDF)/(MDF): The BDF/MDF is designated as the point where the outside plant cable terminates on the building entrance terminal (first level backbone). See references to Main Telecommunications Equipment Room (MTER) for supporting functions B. Main Telecommunications Equipment Room (MTER) or Equipment Room (ER): An environmentally controlled centralized space for telecommunications that houses a main or intermediate cross-connect. An ER can contain equipment to support all of the following: entrance protection, cable infrastructure pathway, data and voice services, PBX, demarcation point, wireless, paging, fire /smoke detection, security alarm systems, radio, area of rescue assistance equipment, CATV and video conferencing. C. Intermediate Distribution Frame - (IDF): A frame, rack or termination block that connects to the BDF/MDF with copper and optical fiber riser cables and distributes horizontal wiring to the rooms (Second Level). In some situations, a BDF may serve this function. See references and definition for Telecommunications Equipment Room (TER) for supporting functions D. Telecommunications Equipment Room (TER) or Telecommunications Room (TR): A TER is a special purpose room designed to serve a single floor. In buildings with multiple floors, TER's shall be vertically stacked to form a backbone pathway. The TR is the point in the voice and data infrastructure that the backbone and horizontal distribution systems are connected to each other. A TER can contain equipment to support all of the following: cable infrastructure, data and voice communications, wireless, satellite, paging, fire /smoke detection, security alarm systems, radio, CATV and video conferencing. E. Telecommunications Outlet - (TO): The standard telecommunications outlet. A connecting device in the work area on which horizontal cable or outlet cable terminates. This outlet is typically provisioned with two to four ports (maximum capacity is six ports) of Category 6 (and other related technology cabling) and typically terminates in a designated Telecommunications Room (TR) at an IDF patch panel. 14.14.001 COMMUNICATIONS 270000-2

F. Protector: A device used to protect facilities from and equipment from abnormally high voltages or currents. G. Outside Plant: Telecommunications infrastructure designed for installation exterior to buildings. H. Riser Cable: Telephone, data, video, coaxial and other structured cabling system cables extending vertically (or horizontally, in some cases) between the BDF and each area IDF to support low voltage systems. 1. Horizontal Cable: The cabling between and including the work area telecommunications outlet/connector and the horizontal cross-connect/patch cord in the telecommunications room. This is typically a Category 6 or 6 Augmented 4 pair cable, but can also include multiple fiber cables for the desktop, coaxial cables and other multi media type cables that provide service to a end user device. J. Inter Building Cable Plant: Outside plant cable or infrastructure connecting two or more buildings together for the distribution of telephone, data, video or control signals. K. Intra Building Cable Plant: Inside cable plant or infrastructure within a building for the distribution of telephone, data, video or controls signals. L. Approved / Approval: Written permission to use a material or system by Ownership/Midtown Technologies. M. Should: A recommended best practice, procedure, or method. N. Shall: A required practice, procedure or method 0. Backbone: A facility (e.g., pathway, cable or conductors) between telecommunications ( rooms, or floor distribution terminals, the entrance facilities and equipment rooms within or between buildings. P. Connector (Jack): A female telecommunications connector that may be keyed or unkeyed and may have six or eight contact connector that may be positions, but not all the positions need to be equipped with jack contacts. Jacks are typically used to terminate cable at the user end and are inserted into faceplates to create a connection point for the user's equipment cord. Q. Electromagnetic Interference - (EMI): Radiated or conducted electromagnetic energy that has an undesirable effect on electronic equipment of signal transmission. R. Furnish: Supply and deliver to installation location. S. Install: Mount and connect equipment and associated materials ready for use. T. Provide: Furnish, install and connect ready for use. U. Pull Point: Space used to transition between floors for backbone and horizontal cabling within a building riser system V. Structured Cabling System: The complete collective configuration of a telecommunications cabling and associated hardware at a given location. W. Telecommunications: A branch of technology concerned with the transmission, emission, and reception of signs, signals, writing, images, and sounds; that is, information, of any nature by cable, radio, optical, or other electromagnetic systems. 14.14.001 COMMUNICATIONS 270000-3

X. Universal Cabling System -(UCS): A UCS attempts to wire a building for information needs without knowing specifically what equipment will be utilized. A UCS is geared for long-term stability and flexibility and is based on the idea of wiring a building once. Y. Wireless Access Point (WAP or AP): Wireless access points are specially configured nodes on wireless local area networks (WLANs). Access points act as a central transmitter and receiver of WLAN radio signals. Z. Power Over Ethernet - (POE): Power-over-Ethernet (PoE) eliminates the need to run 110/220 VAC power to Wireless Access Points and other devices on a wired LAN. Using Power-over-Ethernet system installers need to run only a single CAT6 Ethernet cable that carries both power and data to each device. This allows greater flexibility in the locating of AP's and network devices and significantly decreasing installation costs in many cases. AA. 1.5 ACRONYMS Voice Over Internet Protocol - (VoIP): VoIP (Voice over Internet Protocol) is the transmission of voice traffic over IP-based networks. A. AMPE - Architectural, Mechanical, Plumbing, Electric B. PBX - Private Branch Exchange (Phone Switch) C. ER - Equipment Room D. TER - Telecommunications Equipment Room E. TR - Telecommunications Room F. EMI - Electromagnetic Interference G. PP - Pull Point H. PB - Pull Box I. CAT - Category J. UTP - Unshielded Twisted Pair K. CATV - Community Antenna Television (cable television) L. TGB - Telecommunications Grounding Busbar M. TMGB - Main Telecommunications Grounding Busbar N. AFF - Above the Finished Floor 0. MH - Maintenances Hole P. HH - Handhole Q. TO - Telecommunications Outlet R. WAP - Wireless Access Point S. UTP - Unshielded Twisted Pair 1.6 SYMBOLS A. Refer to the reference drawing set and legends for symbols and definitions. 1.7 NORMATIVE REFERENCES A. The following organizations publish telecommunications construction standards with provisions that, through reference in this text, constitute provisions of this Document. At 14.14.001 COMMUNICATIONS 270000-4

the time of publication of this Document, the editions of the standards published by the organizations indicated were valid. Designers and/or installers of telecommunications and networking services at the property must adhere to the telecommunication standards published by the these organizations, all standards are subject to revision; parties to agreements based on this Document shall apply the most recent editions of the standards published by the organizations indicated 1. Federal Communications Commission (FCC) 2. Institute of Electrical and Electronics Engineers, Inc (IEEE) 3. National Fire Protection Association (NFPA) 4. National Electrical Safety Code (NESC) 5. American National Standards Institute (ANSI) 6. Telecommunications Industry Association (TIA) 7. Electronic Industries Alliance (EIA) 8. Building Industry Consulting Service International (BICSI) 1.8 APPLICABLE STANDARDS A. The following list of methods and standards included in the Normative References are considered part of this specification. This is a list of primary references and does not limit the applicability of other standards that are incorporated into the list of Normative References applicable to the work described in these specifications. They incorporate generally accepted communications infrastructure practices described in Standards documents (and addenda) published by recognized standards bodies and organizations. These include standards published by the Telecommunications Industry Association/Electronics Industries Alliance (TIA/EIA) and Building Industry Consultant Services International (BICSI). 1. ANSI/TIA/ EIA 568B, Commercial Building Telecommunications Cabling Standard. This prescribes the requirements for Intra-building copper and optical fiber cable performance, installation and testing. 2. ANSI/TIA/EIA 569B, Telecommunication Standard for Pathways and Spaces. This standard includes specifications for the design and construction of pathways and spaces within buildings required to support information technology equipment and cable media. 3. ANSI/TIA/EIA 607, Commercial Building Grounding and Bonding Requirement. This document includes the components of an effective grounding system for communication systems within public and commercial buildings. 4. ANSI/TIA/EIA 758, BICSI Customer Owned Outside Plant Telecommunications Cabling Standard. This standard provides specifications for Inter-building communication facilities that include cable media, pathways and spaces. 5. ANSI/TIA/EIA 862, Building Automation Systems Cabling Standard for Commercial Buildings. This standard describes the generic cable system for building automation systems (BAS) that are intended to support a multi-product, multi-vendor automation environment within public and commercial buildings. 6. Building Industry Consulting Services International (BICSI) Telecommunications Distribution Methods Manual, 1 OthEdition. This is a 14.14.001 COMMUNICATIONS 270000-5

manual of proven design guidelines and methods accepted by the telecommunications industry. 7. ANSI/NFPA 70, National Electrical Code, (NEC) Current Edition. In addition to standards related to electrical safety, the NEC has several sections that specifically address low voltage cable installation. PART 2 - PRODUCTS 2.1 PRODUCT STANDARDS A. All materials shall conform to the current applicable industry standards including, but not limited to: 1. NEMA (National Electrical Manufacturers' Association) 2. ANSI (American National Standards Institute) 3. ASTM (American Society for Testing and Materials) 4. ICEA (Insulated Cable Engineers Association) 5. IEEE (Institute of Electrical and Electronic Engineers) 6. National Electrical Safety Code 7. Telecommunications Industry Association (TIA) 8. Electronic Industries Alliance (EIA) B. In addition, all Material shall be Underwriters Laboratories Listed unless otherwise indicated C. All products must be new. D. Product substitutions shall be managed according to the following guidelines: 1. Where specified only by reference standards, select any product meeting standards by any manufacturer. 2. Where specified by naming several products or manufacturers, select any product and manufacturer named that meets the specified requirements. Other products and manufacturers will not be considered. 3. Where specified by naming one or more products or manufacturers, but indicating "or equivalent" after specified listing, the specified product is the preferred quality standard. The Contractor may submit a request for another product for acceptance. 4. Where specified by naming only one product and manufacturer: "There is no option and no substitution" will be allowed. 5. Submit requests for substitutions within 10 days of contract award, or sooner if required to maintain the construction schedule 6. The Contractor must submit sufficient information to show that a proposed substitute is equivalent to the item specified. 7. Acceptance of substitutions is at Owner's discretion: the Owner reserves the right to determine suitability of the substitute product and reject any and all materials submitted for substitution. 14.14.001 COMMUNICATIONS 270000-6

PART 3 - EXECUTION 3.1 EXAMINATION 8. All substitute products and materials must be approved for substitution by the Owner in writing prior to installation 9. Products rejected or otherwise judged unsatisfactory by the Owner will not be authorized for use in completing the work. Any unapproved products discovered as part of the installation will be removed and replaced with Owner-specified and approved products at the Contractor's expense 10. Project Drawings may be based on equipment configuration of a particular manufacturer. If a substitution is approved, the Contractor shall make changes needed to accommodate the substitution at no expense to Ownership, including work under other divisions. A. Each Contractor shall be knowledgeable of work to be performed by other trades and take necessary steps to integrate and coordinate their work with other trades. B. The Contractor shall be responsible for furnishing all materials on the drawings or as specified herein for a complete telecommunications system. C. All telecommunications infrastructure shall be installed in an aesthetically pleasing fashion. D. All telecommunications infrastructure shall be installed for optimal performance. E. All telecommunications infrastructure shall be installed for easy moves, adds, and changes in the future. F. All work performed in occupied spaces shall be in a manner that allows the owner to operate the facilities on a continuous basis. G. All user outages, including network equipment, shall be submitted to Ownership for approval two week before starting work that will affect user connectivity. H. All TER's must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic. I. Each contractor is to provide a Manufacturers Warranty of not less than 20 years on structured cabling system. J. All work by the contractor must comply with the manufacturer's product recommended installation instructions and warranty requirements. K. All work by the contractor must comply with the standards listed in the Normative and Applicable Standards listed in this specification. L. The contractor is required to obtain all permits from the proper jurisdiction for all work associated with this specification. M. The Contractor is to provide all station documentation and test results at the substantial completion. END OF SECTION 270000 14.14.001 COMMUNICATIONS 270000-7