Andover ContinuumTM Infinet II

Similar documents
BACnet. b3810 Series Local Controllers

Andover ContinuumTM Infinet II

Andover ContinuumTM Infinet II

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM. b3850 Series Terminal Controllers

BACnet. b3867 Terminal Controllers

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

ACX Series. Access Controller for Ethernet

Andover ContinuumTM Infinet II

lighting control. Each controller switches up to 48 high voltage, 20-amp lighting circuits, using

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed

Andover Continuum. Power Supplies with or without UPS

Andover ContinuumTM. Family of Controllers. BACnetTM

Installation Instructions for UL Rev A

Andover ContinuumTM. Family of Security Products

XT-9100 Technical Bulletin

TAC I/NETTM 1284, 1280, Security Control Unit

Andover Continuum. Family of Security Products

Quick Start Installation Guide

FX Input/Output (I/O) Modules XM07 and XM14

clarity 3 Programmable Controller

TAC Xenta 301. Controller, Freely Programmable

TALON Network Manager- 2 & 6 Express

Specification Sheet For electronically commutated motors

TAC Xenta 121-FC Programmable Fan Coil Application

AIR HANDLING UNIT CONTROLS

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

DS Type: MAXIM III Controller

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

TAC Xenta 121-HP Programmable Heat Pump Application

Room Controllers. SC3000 Relay Pack

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

LX Series Free Programmable Controllers

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

DS October MAXIM 1010 Controller

GreenEye Monitor Specifications

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

PXC Modular Series. Features. Description. Technical Specification Sheet Document No Rev. 1.1, May 2007

Datasheet. ECB-600 and ECx-400 Series. ECB-600 & ECx-400. Overview. Applications. Features & Benefits.

DX-9100 Digital Controller, Version 2

FX06 Field Controller

1.6. Counters, Panel Meters, Tachometers and Timers. Contents Description Fusion Integrated Machine Control Standards and Certifications...

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Neon pr. ph/ ORP measurement. Applications. Description

6222 Two Door Module Technical Operations Manual

DS BAS /99 UNC 596 BUILDING AUTOMATION SYSTEM UNIVERSAL NETWORK CONTROLLER FEATURES

RTD-W Installation Instructions

NF760 Batch Controller

Measure & Control Temperature & CO2 levels with analog & digital I/O

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

Medium User Interface (MUI) Version 3

IQ21x Series Controllers

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

BUILDING MANAGEMENT. OpenBAS-HV-NX10 SERIES CATALOG NUMBER. Description. Features

EA500. Installation Instructions Transponder

SE7600E Series Application Guide

TM221CE24R controller M IO relay Ethernet

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

TM221M16R controller M IO relay

8 channel universal input and 4 channel Form C digital output

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

TC Modular Series for BACnet Networks

Power Panel. Terminal block, 12 pin, 20 pcs., cage clamps. Table 5: Order data for PP41

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

BACnet Controller for General-purpose Building Applications

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

Advant OCS. The Compact and Cost Effective Advant Controller. Advant Controller 210. Open Control System

InteliLite MRS17 Click Here to Learn More

SEZ7000 Series. Wireless Commercial Zoning System

Power Panel Integrated control, operation and visualization

TM221CE40T controller M IO transistor PNP Ethernet

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

TM221CE40R controller M IO relay Ethernet

PXC Modular Series. Features. Description. Technical Specification Sheet Document No July 24, 2012

FCU-MULTI Modbus Fan Coil Unit Controller

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

TM221ME32TK controller M IO transistor PNP Ethernet

Hotel Room Controller

Architectural Controllers

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

G303 RIO (REMOTE I/O) AND LOW END RTU

Extended Digital Controller

clarity 3 VAV Programmable Controller

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

SCADAPack Smart RTU

Batch Controller with numerical keypad, remote control inputs and 3 control / alarm / pulse outputs

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers

Metered Rack PDU Rack PDU, Metered, Zero U, 20A, 120V, (24) NEMA 5-20R

TX-I/O Product Range. Features. Description. Document No January 24, 2007

MICROFUSION FEATURES OPTIONS CERTIFICATIONS (PENDING) THREE PHASE SCR POWER CONTROLLERS

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

TC Compact Series Unitary Equipment Controller

FCU-4 FAN COIL CONTROLLER

Transcription:

Andover ContinuumTM Infinet II The i80 Series controllers are designed for control of Air Handling Units, Roof Top Units, and other mechanical plant equipment.

Features 0 Choose the i80 model with the configuration that matches your application: The i80, designed for stand-alone equipment control of Roof Top Units, Air Handling Units, or other packaged mechanical equipment, features eight universal inputs, one Smart Sensor/Room Sensor input, plus eight program-controlled digital outputs. The i8, designed for stand-alone equipment control of Roof Top or Air Handling Units, features eight universal inputs, one Smart Sensor/Room Sensor input, plus four program-controlled digital outputs and four analog outputs for direct control of devices requiring 0-0 volt control signals. Note: The i8 is only compatible with Andover Continuum. PRODUCT AT A GLANCE Powerful, Flexible Local Controller for the Most Demanding Applications Expandable I/O Meets Additional Point Count Needs Non-Volatile Flash Memory Provides Utmost Reliability Stores Both Application Program and Operating System Optional Display/Keypad Provides Easy Operator Interface (Mounted Separately) Local, Extended Storage of Log Data View and Modify Information with Optional Smart Sensor Display Local, On-Board Service Port Both models feature an additional room sensor input, which supports Andover Continuum Smart Sensor, or any standard room temperature sensor. The i80 Series also features universal inputs, a real-time clock, override switches on all outputs, two-piece removable connectors, and the ability to expand the I/O for additional points. The i80 Series features Flash memory, increased user memory, and a fast (-bit) processor for faster scan times, with plenty of memory available for data logging of your critical data. The i80 communicates with the entire Andover Continuum Infi net RS-8 fi eld bus (i.e. both Andover Infi net and Andover Infi net II controllers) and is compatible with both the Andover Continuum CyberStation and Infi nity SX 8000 frontends. The i8 is only compatible with Andover Continuum. Up to Andover Continuum Infi net devices can be networked to any Andover Continuum network controller. Schneider Electric One High Street, North Andover, MA 08 USA Telephone: + 978 97 9600 Fax: + 978 97 967 www.schneider-electric.com/buildings SDS-I80-US.BU.N.EN..0.0.00.CC

Features (continued) 0 Increased Reliability with Flash Memory The i80 s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application will be restored when power is returned. In addition, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out proms. The i80 controllers include an on-board battery to safeguard your runtime data protecting all point data and log data from being lost if power is removed. Inputs The input configuration on the i80 Series consists of eight full range, -bit universal inputs that accept voltage (0-0VDC), digital (on/off), counter signals (up to Hz), temperature signals, or supervised alarm circuits for security applications or broken wire detection. The i80 Series offers an additional input to support the Andover Continuum Smart Sensor, or any standard room temperature sensor. Outputs The i80 contains eight Form C relay outputs, each rated for VAC/0 VDC, amp, while the i8 contains four Form C relay outputs and four analog outputs (0-0V). Both the relay and analog outputs have manual override switches, with software feedback of the switch position. I/O Expansion The i80 contains an I/O expansion port for the addition of up to two Andover Continuum xp expansion modules directly on the bottom of the controller. The xp family of modules includes the xpui, xpdi8, xpdo, xpdo, xpao, and xpao. In addition to two input/output modules, the I/O bus supports the xp Local Display Module, which allows the user to view and change point values. Dimensional Drawings Schneider Electric One High Street, North Andover, MA 08 USA Telephone: + 978 97 9600 Fax: + 978 97 967 www.schneider-electric.com/buildings SDS-I80-US.BU.N.EN..0.0.00.CC

Features (continued) 0 Software Capabilities The dynamic memory of the i80 can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Continuum Plain English programming language. Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the i80 using the Andover Continuum CyberStation. Programs are then stored and executed by the i80 controllers. Programming multiple i80 Series controllers is inherently easy with Plain English. A complete copy of one i80 controller s programs can be loaded directly into other i80 controllers without changing any point names or programs. Smart Sensor Interface The i80 provides a built-in connection for Andover Continuum Smart Sensor. The Smart Sensor provides a -character LED display and a 6-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a -digit custom LCD that provides the following icons: PM, %,, Setpoint, Cool, Heat, CFM, Fan, OA, and SP. Local Display The local display with keypad (xp-display) allows for the addition of a fully programmable local display module that can be mounted within 0 feet ( meters) of the controller. Connected via a ribbon cable, the xp-display easily allows the Operator Interface to be mounted on the door of an enclosure or on a wall below or next to the controller. Dimensional Drawings N L 6 SHLD AC POWER VAC 0 VA 0/60 HZ + DC POWER -8 VDC 0W Power Drawing + - RS-8 Communication Drawing UNIVERSAL INPUTS 7 RET 8 IN 9 IN 0 RET OFF ON IN IN RET 6 7 IN 8 IN 6 6 RET 7 IN 7 8 IN 8 SMART SENSOR 9 SPWR 0 RET IN 9 6 7 8 0 9 8 7 6 0 9 8 7 6 i80 6 7 8 0 9 8 7 6 I V GND I 0 V 9 GND 8 I 7 V 6 GND I V GND i8 Optional Wireless Andover Continuum Infinet The i80 Series Andover Continuum Infinet controllers can also communicate using a wireless mesh network. Simply plug Andover Continuum Wireless Adapters into the service ports of these controllers with wireless compatible firmware to create a wireless mesh network that sends and receives Andover Continuum Infinet messages. Smart Sensor and Inputs Drawing Outputs Drawing Schneider Electric One High Street, North Andover, MA 08 USA Telephone: + 978 97 9600 Fax: + 978 97 967 www.schneider-electric.com/buildings SDS-I80-US.BU.N.EN..0.0.00.CC

Specifications 0 Electrical Power VAC, -VDC - auto sensing, +0% -%, 0/60 Hz Power Consumption 0 VA Overload Protection Fused with amp fuse. MOV protected Real-Time Clock Battery-backed real-time clock Mechanical Operating Environment 0 F (0 9 C), 0 9% RH (non-condensing) Size 9. H x 7.6 W x. D ( H x 8 W x D) mm Weight.6 lbs. (0.7 kg) Enclosure Type UL Open class, IP 0. Flammability rating of UL9-V Mounting Panel mount Battery Battery Backup Replaceable, non-rechargeable, lithium battery. Provides years typical accumulated power failure backup of RAM memory Communications Communications Interface Through Andover Andover Continuum Infinet RS-8 field bus to network controller Communications Speed 00 to 9.K baud Bus Length,000 ft. (,0m) standard for Andover Continuum Infinet, i Infilink module allows extension to longer distances and is required after every group of units on the network. Bus Media Andover Continuum Infinet: twisted, shielded pair, low capacitance cable RS-8 port for implementing Wireless Infinet II connection, including: Standard service port, four-position shrouded connector Comm. Error Checking International Standard CRC 6 Compatibility Andover Continuum Cyberstation and Infinity SX 8000 systems Note: The i8 is compatible with Andover Continuum software version. (or later). Inputs/Outputs Inputs 8 Universal inputs: Voltage (0-0 VDC); Temperature -0 F to 0 F (- C to 0 C), Digital (on/off), Counter (up to Hz at 0% duty cycle, ms min. pulse width). Supervised Alarm (single or double resistor). Current input (0-0 ma) using external 00 ohm resistor Smart Sensor Temperature Input ( F to 0 F) (0 C to C) Input Voltage Range 0-0 volts DC Input Impedance 0.K ohm to 0V or M ohm with pull-up resistor disabled Input Resolution. mv Input Accuracy ±7.mV (±0. C from - C to + C) or (±0.6 F from -0 F to +0 F) Digital Outputs 8 single pole single throw (SPST) Form C relays ( Form C on i8) (Any two consecutive Form C outputs can be configured as one Form K Tri-state) Output Rating Maximum A, VAC/0VDC, ±00V transients (Tested according to EN6000--) Output Accuracy 0. sec. for pulse width modulation Schneider Electric One High Street, North Andover, MA 08 USA Telephone: + 978 97 9600 Fax: + 978 97 967 www.schneider-electric.com/buildings SDS-I80-US.BU.N.EN..0.0.00.CC

Specifications (continued) 06 Analog Outputs analog outputs (i8 only) Output Rating 0-0V or 0-0mA For 0-0V: ma maximum source, ma maximum sink K ohm minimum impedance (sourcing only), For 0 0mA: 70 ohm maximum +/-000V transients (Tested according to EN6000--). Fuse-protected only on the i8. Output Resolution 0.V for 0-0V, 0.mA for 0-0mA Output Overrides Each output is equipped with a manual override switch. Software feedback of the switch position is provided, for display and alarming Expansion Bus Interfaces to optional xp I/O Expansion Modules Connections Power -position fixed screw terminal connector Inputs Removable two-piece terminal strip Outputs Removable two-piece terminal strip Smart Sensor Removable two-piece terminal strip Communications Removable -position terminal connector Expansion Port 6-position shrouded connector Service Port -position shrouded connector User LEDs/Switches Status Indicator LEDs CPU CPU Active TD Transmit Data RD Receive Data Output Output Status (per output) (Digital only) EXPANSION PORT PWR Power Status Switches RESET Input Pull-up Resistor Switch (per input) Individual Output Override Switches General Memory 6K SRAM, MB FLASH Processor Motorola -Bit Coldfire Agency Listings UL/CUL 96, FCC CFR 7 Part, ICES-00, EN0, ASINS 8, Class A, CE Models i80 Infinet II i80 Local Controller i80-wl Wireless Infinet II i80 Local Controller i8 Infinet II i8 Local Controller i8-wl Wireless Infinet II i8 Local Controller All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. Schneider Electric One High Street, North Andover, MA 08 USA Telephone: + 978 97 9600 Fax: + 978 97 967 www.schneider-electric.com/buildings 007-0 Schneider Electric. All rights reserved. SDS-I80-US.BU.N.EN..0.0.00.CC November 0