Communication Register Map - Uniflair Cooling

Similar documents
Modbus Register Map: InRow ACRD60x / ACRC60x

DESCRIPTION OF MODBUS CONNECTION

The Carel driver connects to a network of Carel air-conditioning and refrigeration packaged controls. Available for Commander and ObSys.

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER

4-step Chiller and Heat Pump Controller

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Rack cooling solutions for high density racks management, from 10 to 75 kw

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

BACnet MS/TP Interface User s Guide

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

Temperature Controller

CommandCenter Operator Panel

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

FX 2 Instruction Manual

MOLLIER DIAGRAM CAN BE IMPROVED!

Application program: description and examples

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

Data Center Optimized Controls

idigit CONTROL INSTALLER MANUAL Digital thermostat for fan coil units Rev100

CCM-204 MULTI-PURPOSE TEMPERATURE CONTROLLER

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Register Map: Ecoflair Indirect Air Economizer

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

VTR8300 User Interface Guide VTR8300 Room Controller Series

ERC 21X Modbus parameter

OP10. Pre-programmed, configurable controller for simple applications

SYSTEM L PROGRAMMABLE CONTROLLER -USER MANUAL-

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

IntesisBox ModBus RTU Fujitsu Air Conditioning

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

IntesisBox PA-AW-MBS-1 v.2.0

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB

ES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

Pocket Quick Reference Guide On the TOSHIBA

USER S MANUAL. DAS-G01 The Power of Tomorrow

UNIFLAIR Instruction manual PROGRAMME OF REGULATION FOR UNIT ISA/ISC

V0STAT51P-2 Programmable Wired Controller

Modbus Integration Integration for Modbus Functionality for VTR8300 Series

Submittal Data Sheet intelligent Touch Manager DCM601A71

Multi Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual

Precision Cooling Mission Critical Air Handling Units

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller

EXD-TEVI Economizer Controller for Tandem Compressors

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

FCU-MULTI Modbus Fan Coil Unit Controller

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone

Supplied with. Calibration certificate. HD 200 Hygrometer

IT Air Conditioning Units

Instruction Manual HID-2

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

1/7. Field settings table [6.8.2] =... ID66F2 / ID66F3. Applicable indoor units. *GSQH10S18AA9W ThermaliaC12* Notes 4P E

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

IntesisBox DK-RC-MBS-1 v.0.2

The Basics of HVAC Operation and the Role of Automation. Mr. Jay Zaino GxP Automation, LLC

IntesisBox DK-RC-MBS-1 v.0.8

Condensing Unit Controller

Allows detailed and easy monitoring and operation of VRV systems (maximum 2 x 64 groups / indoor units)

WALL MOUNTED PACKAGE AIR CONDITIONER REPLACEMENT PARTS MANUAL. Models: WA181, WA241. Contents. General Notes. Important

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.

Retro-Commissioning Report

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

* Options * ** Siemens Building Technologies HVAC Products POLYCOOL. for chillers, air conditioning units, etc.

What is the Carrier ChillerVu series counterflow application?

Corrigo E. Version 3.0 (ventilation), 3.0 (heating), 1.1 (boiler). Controllers for heating, boiler and ventilation applications in buildings.

System User Manual. AKC 55 Rack Controller

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

RGX COMMUNICATIONS GATEWAY

Introducing the Heat Wheel to the Data Center

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions

REMOTE CONTROL MYSYSTEM

GrowControl TM GC-Pro Cultivation Control System

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

PROGRAMMABLE CONTROLLER

AIR CONDITIONING CATALOGUE

Wiring Diagrams DIAGRAM INDEX. POWER SCHEMATICS Unit 30GXN,R Voltage Figure Number

Thermostat KP. Data sheet. The KP Thermostats are single-pole, doublethrow (SPDT) temperature-operated electric switches.

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

INTRODUCTION. FX-1 Operations Manual. Standard Features. Optional Features. Read This Manual Completely Before Proceeding!

OWNER S MANUAL WIRE CONTROLLER OF AIR CONDITIONER. MODEL: KJR-12B/DPBG(T)-E Brivis Part No:B026000


VT8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

Temperature Controller (Heat Pumps)

System 450 Modular Electronic Controls Catalog

UNIT CONTROLLER 8 (UC8) Modbus RTU communications

USER S GUIDE. Contents. NetworkAIR FM. Introduction--1. Control Console--9

Measuring and control system H-Control OPERATING MANUAL

Transcription:

DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R DIGITAL 5 6 6 Compressor 4 0 or 1 boolean R DIGITAL 6 7 7 El. Heater 1 0 or 1 boolean R DIGITAL 7 8 8 El. Heater 2 0 or 1 boolean R DIGITAL 8 9 9 - - - - DIGITAL 9 10 10 Hot gas ON 0 or 1 boolean R DIGITAL 10 11 11 Dehumidification 0 or 1 boolean R DIGITAL 11 12 12 Humidification 0 or 1 boolean R DIGITAL 12 13 13 Emergency Working 0 or 1 boolean R DIGITAL 13 14 14 - - - - DIGITAL 14 15 15 - - - - DIGITAL 15 16 16 - - - - DIGITAL 16 17 17 - - - - DIGITAL 17 18 18 - - - - DIGITAL 18 19 19 - - - - DIGITAL 19 20 20 - - - - DIGITAL 20 21 21 Wrong Password Alarm 0 or 1 boolean R DIGITAL 21 22 22 High Room Temperature Alarm 0 or 1 boolean R DIGITAL 22 23 23 Low Room Temperature Alarm 0 or 1 boolean R DIGITAL 23 24 24 High Room Humidity Alarm 0 or 1 boolean R DIGITAL 24 25 25 Low Room Humidity Alarm 0 or 1 boolean R DIGITAL 25 26 26 Room Temp. And Humidity Limits by External Sensors 0 or 1 boolean R DIGITAL 26 27 27 Clogged Filter Alarm 0 or 1 boolean R DIGITAL 27 28 28 Flooding Alarm 0 or 1 boolean R DIGITAL 28 29 29 Loss of Air Flow Alarm 0 or 1 boolean R DIGITAL 29 30 30 Heater Overheating Alarm 0 or 1 boolean R DIGITAL 30 31 31 Circuit 1 High Pressure Alarm 0 or 1 boolean R DIGITAL 31 32 32 Circuit 2 High Pressure Alarm 0 or 1 boolean R DIGITAL 32 33 33 Circuit 1 Low Pressure Alarm 0 or 1 boolean R DIGITAL 33 34 34 Circuit 2 Low Pressure Alarm 0 or 1 boolean R DIGITAL 34 35 35 Circuit 1 Electronic Valve Failure 0 or 1 boolean R DIGITAL 35 36 36 Circuit 2 Electronic Valve Failure 0 or 1 boolean R DIGITAL 36 37 37 Wrong Phase Sequence Alarm 0 or 1 boolean R DIGITAL 37 38 38 Smoke-Fire Alarm 0 or 1 boolean R DIGITAL 38 39 39 Interrupted LAN Alarm 0 or 1 boolean R DIGITAL 39 40 40 Humidifier: High Current Alarm 0 or 1 boolean R

DIGITAL 40 41 41 Humidifier: Low Current Alarm 0 or 1 boolean R DIGITAL 41 42 42 Humidifier: Water Loss Alarm 0 or 1 boolean R DIGITAL 42 43 43 CW Temperature too High for Dehumidification (circ.1) 0 or 1 boolean R DIGITAL 43 44 44 CW Valve Failure or Water Flow too Low 0 or 1 boolean R DIGITAL 44 45 45 Loss of Water Flow Alarm 0 or 1 boolean R DIGITAL 45 46 46 High Chilled Water Temperature Alarm (circ.1) 0 or 1 boolean R DIGITAL 46 47 47 Room Air Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 47 48 48 Hot Water Temp. Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 48 49 49 Chilled Water Temp. Sensor (c.1) Failed/Disconnected 0 or 1 boolean R DIGITAL 49 50 50 Outdoor Temperature Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 50 51 51 Delivery Air Temp. Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 51 52 52 Room Humidity Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 52 53 53 Chilled Water Outlet Temp.Sensor (circ.1) Failed/Disconnected 0 or 1 boolean R DIGITAL 53 54 54 Compressor 1: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 54 55 55 Compressor 2: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 55 56 56 Compressor 3: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 56 57 57 Compressor 4: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 57 58 58 Air filter: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 58 59 59 Heater 1: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 59 60 60 Heater 2: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 60 61 61 Humidifier: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 61 62 62 Air conditioning unit: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 62 63 63 Alarm by Digital Input 2 0 or 1 boolean R DIGITAL 63 64 64 Alarm by Digital Input 4 0 or 1 boolean R DIGITAL 64 65 65 Alarm by Digital Input 6 0 or 1 boolean R DIGITAL 65 66 66 Humidifier General Alarm 0 or 1 boolean R DIGITAL 66 67 67 Unit on Alarm 0 or 1 boolean R DIGITAL 67 68 68 Unit on Rotation Alarm 0 or 1 boolean R DIGITAL 68 69 69 Unit on Alarm Type A 0 or 1 boolean R DIGITAL 69 70 70 Unit on Alarm Type B 0 or 1 boolean R DIGITAL 70 71 71 Unit on Alarm Type C 0 or 1 boolean R DIGITAL 71 72 72 DX/CW Switch on TC Units 0 or 1 boolean R/W DIGITAL 72 73 73 Summer/Winter Switch 0 or 1 boolean R/W DIGITAL 73 74 74 - - - - DIGITAL 74 75 75 - - - - DIGITAL 75 76 76 Unit ON/OFF Switch 0 or 1 boolean R/W DIGITAL 76 77 77 Buzzer and Alarm Unit Reset 0 or 1 boolean R/W DIGITAL 77 78 78 Filter Run Hours Reset 0 or 1 boolean R/W DIGITAL 78 79 79 Compressor 1 Run Hours Reset 0 or 1 boolean R/W DIGITAL 79 80 80 Compressor 2 Run Hours Reset 0 or 1 boolean R/W

DIGITAL 80 81 81 Compressor 3 Run Hours Reset 0 or 1 boolean R/W DIGITAL 81 82 82 Compressor 4 Run Hours Reset 0 or 1 boolean R/W DIGITAL 82 83 83 Compressor 1 Starting Reset 0 or 1 boolean R/W DIGITAL 83 84 84 Compressor 2 Starting Reset 0 or 1 boolean R/W DIGITAL 84 85 85 Compressor 3 Starting Reset 0 or 1 boolean R/W DIGITAL 85 86 86 Compressor 4 Starting Reset 0 or 1 boolean R/W DIGITAL 86 87 87 Heater 1 Run Hours Reset 0 or 1 boolean R/W DIGITAL 87 88 88 Heater 2 Run Hours Reset 0 or 1 boolean R/W DIGITAL 88 89 89 Heater 1 Starting Reset 0 or 1 boolean R/W DIGITAL 89 90 90 Heater 2 Starting Reset 0 or 1 boolean R/W DIGITAL 90 91 91 Humidifier Run Hours Reset 0 or 1 boolean R/W DIGITAL 91 92 92 Humidifier Starting Reset 0 or 1 boolean R/W DIGITAL 92 93 93 Unit Run Hours Reset 0 or 1 boolean R/W DIGITAL 93 94 94 - - - - DIGITAL 94 95 95 - - - - DIGITAL 95 96 96 Setback Mode (Sleep Mode) 0 or 1 boolean R/W DIGITAL 96 97 97 Sleep Mode Test 0 or 1 boolean R/W DIGITAL 97 98 98 Local/Mean Usage of Values 0 or 1 boolean R/W DIGITAL 98 99 99 No. of Stand-by Units 0 or 1 boolean R DIGITAL 99 100 100 - - - - DIGITAL 100 101 101 Unit 2 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 101 102 102 Unit 3 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 102 103 103 Unit 4 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 103 104 104 Unit 5 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 104 105 105 Unit 6 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 105 106 106 Unit 7 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 106 107 107 Unit 8 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 107 108 108 Unit 9 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 108 109 109 Unit 10 on Rotation Alarm (Only for LAN Unit Number 1) 0 or 1 boolean R DIGITAL 109 110 110 AFPS: Air Pressure Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 110 111 111 AFPS: Low Air Pressure Alarm 0 or 1 boolean R DIGITAL 111 112 112 Expansion Board Offline 0 or 1 boolean R DIGITAL 112 113 113 EEPROM Failure 0 or 1 boolean R DIGITAL 113 114 114 Compensation Enabled (with delivery temp. regulation) 0 or 1 boolean R/W DIGITAL 114 115 115 High Delivery Temperature Alarm 0 or 1 boolean R DIGITAL 115 116 116 Humidifier: High Conductivity Alarm 0 or 1 boolean R DIGITAL 116 117 117 Humidifier: Low Production 0 or 1 boolean R DIGITAL 117 118 118 Humidifier: Drain Malfunction (lock) 0 or 1 boolean R DIGITAL 118 119 119 Humidifier: Bottle Full Of Water Alarm (lock) 0 or 1 boolean R DIGITAL 119 120 120 Humidifier: Mandatary Maintenance (lock) 0 or 1 boolean R

DIGITAL 120 121 121 CW Temperature too High for Dehumidification (circ.2) 0 or 1 boolean R DIGITAL 121 122 122 High Chilled Water Temperature Alarm (circ.2) 0 or 1 boolean R DIGITAL 122 123 123 Dual Coil: Expansion Board Not Connected 0 or 1 boolean R DIGITAL 123 124 124 Chilled Water Temp.(c.2) Sensor Failed/Disconnected 0 or 1 boolean R DIGITAL 124 125 125 CW Outlet Temp.Sensor (circ.2) Failed/Disconnected 0 or 1 boolean R DIGITAL 125 126 126 Manual Mode 0 or 1 boolean R DIGITAL 126 127 127 Supply Frequency Not Detected Alarm 0 or 1 boolean R DIGITAL 127 128 128 Exclude from Rotatation 0 or 1 boolean R/W DIGITAL 128 129 129 MODE CW+DX: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 129 130 130 MODE DX: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 130 131 131 MODE CW: hour counter threshold Alarm 0 or 1 boolean R DIGITAL 131 132 132 MODE CW+DX: Run Hours Reset 0 or 1 boolean R/W DIGITAL 132 133 133 MODE DX: Run Hours Reset 0 or 1 boolean R/W DIGITAL 133 134 134 MODE CW: Run Hours Reset 0 or 1 boolean R/W DIGITAL 134 135 135 Cond. Pressure Sensor (circ.1) Failed/Disconnected 0 or 1 boolean R DIGITAL 135 136 136 Cond. Pressure Sensor circ.2 Failed/Disconnected 0 or 1 boolean R ANALOG 0 1 1 - - - - ANALOG 1 2 2 Room Temperature - F x 10 R ANALOG 2 3 3 Outdoor Temperature - F x 10 R ANALOG 3 4 4 Delivery Air Temperature - F x 10 R ANALOG 4 5 5 Chilled Water Temperature (circ.1) - F x 10 R ANALOG 5 6 6 Hot Water Temperature - F x 10 R ANALOG 6 7 7 Room Relative Humidity - rh% x 10 R ANALOG 7 8 8 Outlet Chilled Water Temperature - F x 10 R ANALOG 8 9 9 Circuit 1 Evaporating Pressure - psi x 10 R ANALOG 9 10 10 Circuit 2 Evaporating Pressure - psi x 10 R ANALOG 10 11 11 Circuit 1 Suction Temperature - F x 10 R ANALOG 11 12 12 Circuit 2 Suction Temperature - F x 10 R ANALOG 12 13 13 Circuit 1 Evaporating Temperature - F x 10 R ANALOG 13 14 14 Circuit 2 Evaporating Temperature - F x 10 R ANALOG 14 15 15 Circuit 1 Superheat - F x 10 R ANALOG 15 16 16 Circuit 2 Superheat - F x 10 R ANALOG 16 17 17 Cold Water Valve Ramp (circ.1) - % x 10 R ANALOG 17 18 18 Hot Water Valve Ramp - % x 10 R ANALOG 18 19 19 Evaporating Fan Speed - % x 10 R ANALOG 19 20 20 - - - - ANALOG 20 21 21 Cooling Setpoint w/ Return Air Temperature Control 170-350 F x 10 R/W ANALOG 21 22 22 Cooling Setpoint w/ Delivery Air Temperature Control Cooling Sensitivity w/ Return Air Temperature Control Cooling Sensitivity w/ Delivery Air Temperature Control 140-350 5-99 60-500 F x 10 R/W

ANALOG 22 23 23 Second Cooling Setpoint w/ Return Air Temperature Control 170-350 Second Cooling Setpoint w/ Delivery Air Temperature Control 60-500 F x 10 R/W ANALOG 23 24 24 Heating Setpoint 120-300 F x 10 R/W ANALOG 24 25 25 Second Heating setpoint 120-300 F x 10 R/W ANALOG 25 26 26 Heating Sensitivity 5-99 F x 10 R/W ANALOG 26 27 27 High Room Temperature Alarm Threshold 20-40 F R/W ANALOG 27 28 28 Low Room Temperature Alarm Threshold 0-32 F R/W ANALOG 28 29 29 Setback Mode: Cooling Setpoint 200-350 F x 10 R/W ANALOG 29 30 30 Setback Mode: Heating Setpoint 50-240 F x 10 R/W ANALOG 30 31 31 CW Setpoint to Start Dehumidification 50-200 F x 10 R/W ANALOG 31 32 32 CW High Temperature Alarm Threshold (c.1) 50-800 F x 10 R/W ANALOG 32 33 33 CW Setpoint to start CW Operating Mode (Only TC Units) 70-250 F x 10 R/W ANALOG 33 34 34 Radcooler Setpoint in Energy Saving Mode 50-240 F x 10 R/W ANALOG 34 35 35 Radcooler Setpoint in DX Mode 15-40 F R/W ANALOG 35 36 36 Delivery Temperature Low Limit Setpoint(1) 10-25 F R/W ANALOG 36 37 37 Delta Temperature for Automatic Mean/Local Changeover 0-99 F R/W ANALOG 37 38 38 - - - - ANALOG 38 39 39 - - - - ANALOG 39 40 40 - - - - ANALOG 40 41 41 - - - - ANALOG 41 42 42 - - - - ANALOG 42 43 43 - - - - ANALOG 43 44 44 - - - - ANALOG 44 45 45 - - - - ANALOG 45 46 46 - - - - ANALOG 46 47 47 - - - - ANALOG 47 48 48 - - - - ANALOG 48 49 49 - - - - ANALOG 49 50 50 - - - - ANALOG 50 51 51 LAN Unit 2 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 51 52 52 LAN Unit 3 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 52 53 53 LAN Unit 4 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 53 54 54 LAN Unit 5 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 54 55 55 LAN Unit 6 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 55 56 56 LAN Unit 7 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 56 57 57 LAN Unit 8 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 57 58 58 LAN Unit 9 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 58 59 59 LAN Unit 10 Room Temperature (Only for LAN Unit Number 1) - F x 10 R ANALOG 59 60 60 - - - - ANALOG 60 61 61 LAN Unit 2 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R

ANALOG 61 62 62 LAN Unit 3 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 62 63 63 LAN Unit 4 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 63 64 64 LAN Unit 5 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 64 65 65 LAN Unit 6 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 65 66 66 LAN Unit 7 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 66 67 67 LAN Unit 8 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 67 68 68 LAN Unit 9 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 68 69 69 LAN Unit 10 Room Humidity (Only for LAN Unit Number 1) - rh% x 10 R ANALOG 69 70 70 AFPS: Air Pressure - Pa x 10 R ANALOG 70 71 71 AFPS: Setpoint 0-1000 Pa x 10 R/W ANALOG 71 72 72 AFPS: Dead Band 0-1000 Pa x 10 R/W ANALOG 72 73 73 AFPS: Regulation Band 0-9999 Pa x 10 R/W ANALOG 73 74 74 AFPS: Alarm Threshold 0-1000 Pa x 10 R/W ANALOG 74 75 75 Compensation: Room Temperature (T1) (With Delivery Temp. Regulation) 170-350 F x 10 R/W ANALOG 75 76 76 Compensation: Setpoint 2 (SP2) (With Delivery Temp. Regulation) 170-350 F x 10 R/W ANALOG 76 77 77 Compensation: Room Temperature (T2) (With Delivery Temp. Regulation) 170-350 F x 10 R/W ANALOG 77 78 78 Cold Water Valve Ramp (circ.2) - % x 10 R ANALOG 78 79 79 CW High Temperature Alarm Threshold (c.2) 50-800 F x 10 R/W ANALOG 79 80 80 Humidifier 0-10V Ramp - % x 10 R ANALOG 80 81 81 Chilled Water Temperature (circ.2) - F x 10 R ANALOG 81 82 82 Room Temperature Mean Value - F x 10 R ANALOG 82 83 83 Room Relative Humidity Mean Value - rh% x 10 R ANALOG 83 84 84 Room Absolute Humidity - g/kg x 10 R ANALOG 84 85 85 Dehumidification Setpoint 10-200 g/kg x 10 R/W ANALOG 85 86 86 Dehumidification Prop.Band 1-99 g/kg x 10 R/W ANALOG 86 87 87 Setback Mode: Dehumidification Setpoint 93-200 g/kg x 10 R/W ANALOG 87 88 88 High Humidity Alarm Threshold 75-200 g/kg x 10 R/W ANALOG 88 89 89 Humidification Setpoint 10-200 g/kg x 10 R/W ANALOG 89 90 90 Humidification Prop.Band 1-99 g/kg x 10 R/W ANALOG 90 91 91 Setback Mode: Humidification Setpoint 10-110 g/kg x 10 R/W ANALOG 91 92 92 Low Humidity Alarm Threshold 10-120 g/kg x 10 R/W ANALOG 92 93 93 Condensing Pressure (Circuit 1) psi x 10 R ANALOG 93 94 94 Condensing Pressure Circuit 2 - psi x 10 R ANALOG 94 95 95 Condensing Temperature (Circuit 1) - F x 10 R ANALOG 95 96 96 Condensing Temperature (Circuit 2) - F x 10 R INTEGER 0 209 5001 - - - - INTEGER 1 210 5002 Air Filter Run Hours - h R INTEGER 2 211 5003 Unit Run Hours - h R INTEGER 3 212 5004 Compressor 1 Run Hours - h R INTEGER 4 213 5005 Compressor 2 Run Hours - h R

INTEGER 5 214 5006 Compressor 3 Run Hours - h R INTEGER 6 215 5007 Compressor 4 Run Hours - h R INTEGER 7 216 5008 Heater 1 Run Hours - h R INTEGER 8 217 5009 Heater 2 Run Hours - h R INTEGER 9 218 5010 Humidifier Run Hours - h R INTEGER 10 219 5011 - - - - INTEGER 11 220 5012 - - - - INTEGER 12 221 5013 Dehumidification Prop.Band 3-15 rh% R/W INTEGER 13 222 5014 Humidification Prop.Band 3-20 rh% R/W INTEGER 14 223 5015 High Humidity Alarm Threshold 40-99 rh% R/W INTEGER 15 224 5016 Low Humidity Alarm Threshold 0-65 rh% R/W INTEGER 16 225 5017 Dehumidification Setpoint 10-90 rh% R/W INTEGER 17 226 5018 Setback Mode: Dehumidification Setpoint 50-90 rh% R/W INTEGER 18 227 5019 Humidification Setpoint 10-90 rh% R/W INTEGER 19 228 5020 Setback Mode: Humidification Setpoint 20-60 rh% R/W INTEGER 20 229 5021 Restart Delay 0-300 sec R/W INTEGER 21 230 5022 Regulation Start Transitory 15-200 sec R/W INTEGER 22 231 5023 Low Pressure Delay 30-240 sec R/W INTEGER 23 232 5024 Temp./Humid.Limits Alarm Delay 0-99 min R/W INTEGER 24 233 5025 Anti-Hunting Constant 0-30 min R/W INTEGER 25 234 5026 Stand-by Cycle Base Time 0-999 h R/W INTEGER 26 235 5027 - - - - INTEGER 27 236 5028 Number of LAN Units 1-10 n R/W INTEGER 28 237 5029 Fan: Cicle Time (Sleep mode) 15-99 min R/W INTEGER 29 238 5030 Circuit 1 Electronic Valve Position - step R INTEGER 30 239 5031 Circuit 2 Electronic Valve Position - step R INTEGER 31 240 5032 AFPS: Integral time 0-999 s R/W INTEGER 32 241 5033 AFPS: Derivative Time 0-999 s R/W INTEGER 33 242 5034 AFPS: Fan Min. Speed (mode CW) 40-100 % R/W INTEGER 34 243 5035 AFPS: Fan Max Speed 40-100 % R/W INTEGER 35 244 5036 AFPS: Alarm Delay 0-999 s R/W INTEGER 36 245 5037 High Delivery Temp. Alarm Threshold 10-40 F R/W INTEGER 37 246 5038 Day - - R INTEGER 38 247 5039 Month - - R INTEGER 39 248 5040 Year - - R INTEGER 40 249 5041 - - - - INTEGER 41 250 5042 - - - - INTEGER 42 251 5043 Hour - - R INTEGER 43 252 5044 Minute - - R INTEGER 44 253 5045 AFPS: Fan Min. Speed (mode DX) 40-100 % R/W

INTEGER 45 254 5046 - - - - INTEGER 46 255 5047 - - - - INTEGER 47 256 5048 - - - - INTEGER 48 257 5049 MODE CW+DX Run Hours - h R INTEGER 49 258 5050 MODE DX Run Hours - h R INTEGER 50 259 5051 MODE CW Run Hours - h R Note 1: Analog and Integer data will display in units based on language selection