M-BUS PROTOCOL for ML 311

Similar documents
0xc1 (Mass) 0xc2 (Flow) 0xc3 (Reserved) 0xc4 (BDE) 0xc5 (AMTRON X-50) 0xc6 (AMBILL) 0xc7 (TGR) 0xc8 (BDV) 0xc9 (DTF)

M-Bus protocol CALEC energy master

COMMUNICATION M-BUS PROTOCOL PR 118

SF-586x: M-Bus Extension

COMMUNICATION M-BUS PROTOCOL CE4DMID0M (MBus meter)

1 ABBREVIATIONS VERSION M-BUS PROTOCOL SUMMARY OF M-BUS DATA TYPES...15

M-BUS Standard acc. EN AE.05:04.01: Protocol Specification

BACnet PROTOCOL CONVERTER ML 311

EEM230-D-M. Energy meters. Electrical Energy Meter with integrated M-Bus interface

EEM230-D-M. Energy meters. Electrical Energy Meter with integrated M-Bus interface

SCYLAR INT 7. Communication description. Software Version 01

OMS Vol.2 Primary Elster Implementation

SONOMETER 1100 Communication description MBus ID = 0x2F

SHARKY BR773. Communication Description. Software Version 28

M-Bus Pulse Collector Twin-Pulse Instruction Manual

Singlephase Energy meter with M-Bus interface

Heat meter PolluStat M-bus communication protocol description

3-phase energy meters with M-Bus interface

Flex M-Bus for F3/4 1(11) SVM Implementation of M-Bus in F3/4 meter

Technical Description. Wired M-Bus. Water Meters flowiq 2101/3100

GmbH, Stettiner Str. 38, D Paderborn

Assembly. Assembly. Connections Main circuit. Connections Control circuit. Insulation properties

TS2M-Bus Protocol Converter / User Manual

M-Bus Slaves for MULTICAL 601

GNM1D M-BUS COMMUNICATION PROTOCOL. Revision 0

EM111-EM112 M-BUS COMMUNICATION PROTOCOL. Revision 4.0

GNM3D M-BUS COMMUNICATION PROTOCOL. Revision 1

FLOW 38 v8.x. M-Bus communication protocol specification

GmbH, Stettiner Str. 38, D Paderborn. PadPuls M4L. Art.-No. IM002G: (Valid from M-Bus generation: $12)

jmbus User Guide Fraunhofer Institute for Solar Energy Systems ISE openmuc.org

FALCON PR6/PR7 Operating instructions M-Bus module for Elster water meter with Falcon register

Venstar Thermostat Adapter

M-BUS/MODBUS CONFIGURATION SOFTWARE FOR GINEERS MMCR-64

GmbH, Stettiner Str. 38, D Paderborn. PadPuls M2. Art.No.: IM003G + IM003GB. (Valid from M-Bus generation: $40)

DRT-205C M-Bus Protocol V1.1

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

WIRELESS RECEIVER WRM-TS. Rev. 1.0c

FALCON MJ Pulse/M-Bus operating instructions M-Bus module for Honeywell / Elster M100i and M120i waters meters

PADPULS2 M-BUS Pulse Input Modules

Supercom 636. Manual Radio Modem. Issue: Rev Document: Manual Supercom 636 R+W rev

CLOCKAUDIO. MR88 Automatic Microphone Mixer RS232 Programming Version 4.2

T230 heat meter or cold meter

Instruction manual EFR4000IP

B Interface description 12.01/

RelAir R2M PRO / HOME

User manual. Actuator with RS485/SIKONETZ5 interface AG03/1

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

AFRecorder 4800R Serial Port Programming Interface Description For Software Version 9.5 (Last Revision )

Version Action Author Date

INSTEON Hidden Door Sensor

COMMUNICATION MODBUS PROTOCOL

Operating Instructions RMx621

1. Implemented CM11 protocol

User guide. SonoMeter 30. Ultrasonic energy meter for heating and cooling applications. Danfoss VUIGI102 1

BA00216R/09/EN/ MS Word

Elotech Standard Protocol. for Single R8200 SC

For more information Contact with details of the application.

Specifications Manual

MTR-4. C8 Command to MODBUS Bridge User Manual F-1, No. 631, Chung Der Road, Sec 1, Taichung Taiwan.

SC2004MBS 20x4 Characters MODBUS RTU Slave LCD

Mounting instruction Gateway M-Bus Master AMB8466-M-GMM Release 1.2

INNOVATIVE TECHNOLOGY LTD CC2. Communications Protocol Manual GA863. Issue version Page 1 of 108

Application Note BDLxxxx RS232 SERIAL INTERFACE COMMUNICATION PROTOCOL (SICP V1.82)

RS232 User Guide. Planar Simplicity Series 4K Displays SL4364K SL5564K SL6564K SL7564K SL8664K. Simplicity Series 4K Displays User Guide A

ENERGY METER AND DATA MANAGEMENT

Interface MDB SLAVE to RS232 v Quick reference

Technical Information. Command overview of Vision Systems

CANopen. Network configuration. Operating instructions Software. Integration of Bürkert devices in CANopen networks

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

SMART CONNECTION TO SMART HOME VENTO

Flow Measurement SITRANS F US Inline

TKB Description of the Serial Interface 2WR6

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

AX-18F/ AX-18A. Part Photo. H/W Specification [AX-18F] [AX-18A]

CMa10,CMa11 Users Manual English ELVACO-CMa10 M-Bus Tempsensor; CMa11 M-Bus Temperatursensor

Optris CT/ CTlaser/ CTvideo communication interface

DTNFCSS UART YES Internal DTNFCUS USB YES Internal

SRS501 User s manual

ECA 73 M-Bus combi module for the ECL Comfort 300S controller. Installation and User Guide

Planar Simplicity Series

SITRANS F flowmeters SITRANS F US. SITRANS FUE950 energy calculator. 4/240 Siemens FI

1 SETTING UP GENERAL FUNCTION TYPE PROTOCOL MESSAGES COMMAND RETURN CODES... 6 TRANSACTION EXAMPLES...

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

Flow Measurement SITRANS F US Inline

SVM F4. Calculator. Manual

AB Axis Industries. Use

The MBus Driver. This document relates to MBus driver version 1.0 and 1.1

OPTRIS CT/CTL communication interface

Interface Card, Interface Box, Datalogger & Interface. Bedienungsanleitung. Kommunikationsprotokoll. Operating Instructions. Communications protocol

M-Bus Display / M-Bus Datalogger for 3 / 20 meters

1.1 Errors and Event list

Gateway configuration manual M-Bus master - KNX TP EK-BM1-TP-20 EK-BM1-TP-40 EK-BM1-TP-80 EK-BM1-TP-160

SwitchLinc 2-Wire Dimmer (RF Only) (2474DWH - Dev 0x01 / Sub 0x24)

Gateway configuration manual M-Bus master - KNX TP EK-BM1-TP-20 EK-BM1-TP-40 EK-BM1-TP-80 EK-BM1-TP-160

Developer Notes INSTEON Thermostat v012. Developer Notes. INSTEON Thermostat. Revision History

Conto D2 COMMUNICATION PROTOCOL CONTENTS 1.0 INTRODUCTION

SITRANS F US Inline. SITRANS FUE950 energy calculator 4/269

COMMUNICATION MODBUS PROTOCOL MF96001 / 021 NEMO 96HD

Dual-axis Electronic Digital Magnetic Compass Module User s Guide

Transcription:

OPERATING MANUAL OPERATING MANUAL M-BUS PROTOCOL for ML 311 Release number: 311_MBUS_EN_01.docx

INDEX INTRODUCTION... 3 HARDWARE CONNECTION... 3 SETTING ML 311 TO COMMUNICATE WITH M-BUS PROTOCOL... 4 ABBREVIATION DESCRIPTION... 4 THE ACK TELEGRAM... 4 ADDRESSING TYPE VIA M-BUS PROTOCOL... 5 M-BUS PARAMETERIZATION TELEGRAMS... 8 M-BUS READOUT TELEGRAMS - READING PROCESS DATA FROM ML 311... 10 M-BUS ALARM STATUS TELEGRAM... 15 ADDRESSES... 16 2

INTRODUCTION The M-Bus (Meter Bus) was developed to fill the need for a system for the networking and remote reading of utility meters, for example to measure the consumption of gas or water in the home. This bus fulfills the special requirements of remotely powered or battery driven systems, including consumer utility meters. When interrogated, the meters deliver the data they have collected to a common master, which can, for example, be a hand-held computer, connected at periodic intervals to read all utility meters of a building. An alternative method of collecting data centrally is to transmit meter readings via a modem. Other possible applications in home electronic systems for the M-Bus are alarm systems, flexible illumination installations and heating controlling. HARDWARE CONNECTION MBUS GND 16 15 14 13 12 11 10 9 3

SETTING ML 311 TO COMMUNICATE WITH M-BUS PROTOCOL 1) Select Menu 6-COMMUNICAT. -> Select Function Protocol -> Select MBUS protocol type 2) Select Menu 6-COMMUNICAT. -> Select Function Address -> Insert the M-BUS Primary address of the ML 311 Select Menu 6-COMMUNICAT. -> Select Function Speed -> Select the M-BUS communication speed 4) Select Menu 6-COMMUNICAT. -> Select Function Parity -> Set the EVEN parity for the M- BUS communication protocol ABBREVIATION DESCRIPTION Abbreviation Description REQ_UD2 Request for an RSP_UD telegram RSP_UD Data telegram from ML 311 to Master SND_UD Data telegram from Master to ML 311 (Send User Data to Slave) SND_NKE Initialization telegram in accordance with EN 13757 ACK Confirmation telegram in accordance with EN 13757 PADR Place-holder for the Primary address (1 byte) LEN Place-holder for the length byte (1 byte), calculated in accordance with EN 13757 IDENT Place-holder for the secondary address (4 bytes) MAN Place-holder for the manufacturer code (2 bytes) DEV Place-holder for the device version (1 byte) MED Place-holder for the medium (1 byte) ACC Place-holder for the access counter (1 byte) STAT Place-holder for the status (1 byte) CS Place-holder for the checksum (1 byte), calculated in accordance with EN 13757 THE ACK TELEGRAM The ACK telegram is send by the ML 311 to the Master for confirm the acquisition of the parameterization commands. The ACK telegram format: ACK 1 0xE5 4

ADDRESSING TYPE VIA M-BUS PROTOCOL Primary addressing Every ML 311 in an M-BUS network can be addressed via primary addressing. The Primary address range allowed is 0... 250. Each telegram contains the Primary address in the A field. The Primary address can be set with the function Address in the Menu 6-COMMUNICAT. or via M- BUS with the following telegram: L field 1 0x06 L field 1 0x06 C field 1 0x53/0x73 SND_UD (Send User Data to Slave) A field 1 PADR Old Primary address CI field 1 0x51 Parameterization telegram DIF 1 0x01 VIF 1 0x7A Value 1 New Primary address 0 250 Stop field 1 0x16 The ML 311 respond with an ACK telegram. Secondary addressing If an M-Bus network contains more than 250 meters, it is possible to use the Secondary addressing. Secondary addressing uses the A field (Primary address) with the value of 253 (0xFD) and the Slave is identified with the 8-byte header of the telegram. The 8-byte header of the telegram has the following composition: - Secondary address number - Manufacturer code - Device version - Medium Secondary addressing communication must be initialized with a Slave select telegram and at the end of the communication it is necessary to de-select the Slave. Slave select telegram: L field 1 0x0B 5

L field 1 0x0B C field 1 0x53/0x73 SND_UD (Send User Data to Slave) A field 1 0xFE Secondary addressing CI field 1 0x52 Slave select telegram Secondary address 4 IDENT Secondary address number Manufacturer code 2 MAN 0x266F = ISO (Isoil) Device version 1 DEV 0x00 MBUS version of ML 311 Medium 1 MED 0x04 = return 0x0C = flow Stop field 1 0x16 If all 8 bytes of the ML 311 of the M-BUS network match with the select telegram, it is selected and responds with an ACK telegram. If at least one of the 8 bytes does not match, the Slave is deselected and does not respond. The Slave can be de-select with the following telegram: Slave de-select telegram: Start field 0x10 C field 0x40 SND_NKE A field PADR Primary address Checksum CS Stop field 0x16 The ML 311 respond with an ACK telegram. Only the 4 bytes of the Secondary address number can be set via M-BUS. The other bytes are fixed for the ML 311. The Secondary address number is saved in EEPROM. It is possible to set the 4 bytes of the Secondary address number with the following telegram: L field 1 0x09 L field 1 0x09 C field 1 0x53/0x73 SND_UD (Send User Data to Slave) CI field 1 0x51 Parameterization telegram 6

DIF 1 0x07/0x0C Set Secondary address VIF 1 0x79 Value 8 New Secondary address Stop field 1 0x16 The ML 311 respond with an ACK telegram. Point to point addressing If the M-Bus network consists of a M-BUS Master and a single ML 311, point to point addressing can be used. In a point to point communication the A field (Primary address) in the Master telegram is set to 254 (0xFE). The Primary address of the ML 311 is irrelevant in a point to point communication. Broadcast addressing Broadcast addressing is used when is necessary to send a common message to all the devices of a M-BUS network at the same time, for example the date and time. The A field (Primary address) in the telegram of the Master is set to 255 (0xFF). The ML 311 does not respond to broadcast telegrams, but executes the commands. The Primary address of the ML 311 is irrelevant in a Broadcast addressing communication. 7

M-BUS PARAMETERIZATION TELEGRAMS Parameterize Date and Time L field 1 0x09 L field 1 0x09 C field 1 0x53/0x73 SND_UD (Send User Data to Slave) CI field 1 0x51 Parameterization telegram DIF 1 0x04 VIF 1 0x6D Value 4 New Date and Time Stop 1 0x16 The ML 311 respond with an ACK telegram. The Date and time do not support the summer/winter bit. Parameterize Process data response telegram The list of process data in the RSP_UD response telegram can be selected using the following telegram. The appropriate DIF and VIF must be used depending on the response telegram required. The factory setting for the ML 311 is the Standard telegram. L field 1 LEN L field 1 LEN C field 1 0x53/0x73 SND_UD (Send User Data to Slave) CI field 1 0x51 Parameterization telegram DIF 1 0x08/0x28 0x08 = readout Process data 0x28 = readout Cooling Energy counter VIF 1 VIF Stop field 1 0x16 The ML 311 respond with an ACK telegram. 8

The Global readout telegram The following telegram set the response telegram for return the Full process data list from the ML 311. L field 1 0x04 L field 1 0x04 C field 1 0x53/0x73 SND_UD (Send User Data to Slave) CI field 1 0x51 Parameterization telegram DIF 1 0x7F Global readout telegram Stop field 1 0x16 The ML 311 respond with an ACK telegram. The Application reset telegram The application reset telegram set the response telegram to the Standard response telegram. L field 1 0x03 L field 1 0x03 C field 1 0x53/0x73 SND_UD (Send User Data to Slave) CI field 1 0x50 Application reset Stop field 1 0x16 The ML 311 respond with an ACK telegram. 9

M-BUS READOUT TELEGRAMS - READING PROCESS DATA FROM ML 311 The reading of the process data from the ML 311 is always initiated by the Master by means of an REQ_UD2 telegram. The ML 311 responds with the RSP_UD telegram. The RSP_UD telegram is configurable with the SND_UD telegram (see previous sections). When the ML 311 is turned on it respond with the Standard telegram that contains the main process data. The REQ_UD2 telegram With the REQ_UD2 telegram the Master send the request of the process data to the ML 311. The ML 311 return the list of the process data depending on the list selected. The possible lists of process data can be the Standard list, the Full process data list or a combination of process data set with the SND_UD telegram (see previous sections). Start field 1 0x10 C field 1 0x5B/0x7B REQ_UD2 (Request for Class 2 Data) Stop 1 0x16 NOTE: The ML 311 does not distinguish between 0x5B and 0x7B in the C field. The RSP_UD Standard telegram L field 1 LEN L field 1 LEN C field 1 0x08 RSP_UD (response from Slave to Master) CI field 1 0x72 Readout telegram Secondary address 4 IDENT Secondary address Manufacturer 2 0x6F26 0x266F = ISO (Isoil) Device version 1 DEV M-BUS protocol version implemented Medium 1 MED 0x04 = return 0x0C = flow Readout Counter 1 ACC Incremented on each readout Status 1 STAT Status (see EN 13757) Signature 1 0x0000 Not used 10

VIF 1 (2) VIF/VIFE 0x03 = [Wh] 0x06 = [kwh] 0xFB01 = [MWh] 0x08 = [J] 0x0B = [kj] 0x0E = [MJ] 0xFB09 = [GJ] Value 4 Heating Energy counter VIF 1 0x16 [m3] Value 4 Volume counter vector fluid VIF 1 0x17 [m3] Value 4 Volume counter hot water VIF 1 0x18 [m3] Value 4 Volume counter cold water DIF 1 0x04 Instantaneous value - Long (32 bits) VIF 1 VIF/VIFE 11 0x20 = seconds 0x21 = minutes 0x22 = hours Value 4 work time of the board VIF 1 VIF/VIFE 0x2B = [W] 0x2E = [kw] Value 4 Power VIF 1 0x3E [m3/h] Value 4 Flow rate VIF 1 VIF/VIFE 0x5B = [ C] Value 4 Supply temperature VIF 1 VIF/VIFE 0x5F = [ C]

Value 4 Return temperature VIF 1 VIF/VIFE 0x63 = [K] Value 4 Delta T VIF 1 (2) VIF/VIFE 0x03 = [Wh] 0x06 = [kwh] 0xFB01 = [MWh] 0x08 = [J] 0x0B = [kj] 0x0E = [MJ] 0xFB09 = [GJ] Value 4 Cooling energy Stop 1 0x16 NOTE: The STAT byte can have the following values: STAT = 0x00 -> no error STAT = 0x02 -> Any application error and in this case it is possible to read the status byte of the alarms (see the last section). The RSP_UD Full process data list telegram L field 1 LEN L field 1 LEN C field 1 0x08 RSP_UD (response from Slave to Master) CI field 1 0x72 Readout telegram Secondary address 4 IDENT Secondary address Manufacturer 2 0x6F26 0x266F = ISO (Isoil) Device version 1 DEV M-BUS protocol version implemented Medium 1 MED 0x04 = return 0x0C = flow Readout Counter 1 ACC Incremented on each readout Status 1 STAT Status (see EN 13757) Signature 1 0x0000 Not used 12

VIF 1 (2) VIF/VIFE 0x03 = [Wh] 0x06 = [kwh] 0xFB01 = [MWh] 0x08 = [J] 0x0B = [kj] 0x0E = [MJ] 0xFB09 = [GJ] Value 4 Heating Energy counter VIF 1 0x16 [m3] Value 4 Volume counter DIF 1 0x04 Instantaneous value - Long (32 bits) VIF 1 VIF/VIFE 13 0x20 = seconds 0x21 = minutes 0x22 = hours Value 4 work time of the board VIF 1 VIF/VIFE 0x2B = [W] 0x2E = [kw] Value 4 Power VIF 1 0x3E [m3/h] Value 4 Flow rate VIF 1 VIF/VIFE 0x5B = [ C] Value 4 Supply temperature VIF 1 VIF/VIFE 0x5F = [ C] Value 4 Return temperature VIF 1 VIF/VIFE 0x63 = [K] Value 4 Delta T DIF 1 0x04 Instantaneous value 32 bits

Integer VIF 1 0x6D F - format Value 4 Current Date and Time of the ML 311 DIF 1 0x02 16 bits Integer VIF 1 0x78 VIF/VIFE Value 2 Board Serial number DIF 1 0x01 8 bits data VIF 1 0x7A VIF/VIFE Value 1 Primary address VIF 1 (2) VIF/VIFE 0x03 = [Wh] 0x06 = [kwh] 0xFB01 = [MWh] 0x08 = [J] 0x0B = [kj] 0x0E = [MJ] 0xFB09 = [GJ] Value 4 Cooling energy Stop 1 0x16 NOTE: The STAT byte can have the following values: STAT = 0x00 -> no error STAT = 0x02 -> Any application error and in this case it is possible to read the status byte of the alarms (see the last section). 14

M-BUS ALARM STATUS TELEGRAM The Master inform the ML 311 of the request for reading of the status of the alarms with the following telegram: Start field 1 0x10 C field 1 0x5A/0x7A REQ_UD1 (Request for Class1 Data) Stop field 1 0x16 The ML 311 send the following response telegram: L field 1 0x04 L field 1 0x04 C field 1 0x08 RSP_UD (response from Slave to Master) CI field 1 0x71 Alarm status telegram DIF 1 Alarm state Stop field 1 0x16 NOTE: Alarm state byte description: Bit0 = 1 -> max flow rate alarm Bit1 = 1 -> min flow rate alarm Bit2 = 1 -> measures overflow Bit3 = 1 -> pulse overflow Bit4 = 1 -> Ain Outrange ( Input 4-20 ma > 5% of range 4-20 ma) Bit5 = 1 -> Energy Outrange (Energy sign and remote input not match) Bit6 = 1 -> RTD temperature sensor error Bit7 = 1 -> power supply error 15

ADDRESSES Isoil Industria spa Head office 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.1 Fax +39-02-6123202 E-mail: sales@isoil.it Web: www.isoil.com Service Isoil Industria spa 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.1 Fax +39-02-6123202 E-mail: isomagservice@isoil.it