Modeling and Simulation in XENDEE

Similar documents
Modeling and Simulation in XENDEE

University of California, Santa Cruz Baskin Engineering School Electrical Engineering Department

A guide on PowerWorld Simulator ver. 12.0

This webinar brought to you by the Relion product family

LAB1 INTRODUCTION TO PSS/E EE461: POWER SYSTEMS COLORADO STATE UNIVERSITY

SIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB2 INTRODUCTION TO SLIDER BINARY (*.sld) FILES

SMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM

Tutorials. Tutorial: Creating a New Case Page 1 of 13

Small Generator Interconnection System Impact Study Report. Completed For Q0047

G. Larry Clark Principal Engineer Power Delivery Alabama Power Company, A Southern Company

Local Area Studies Update - PACW Kevin Putnam

1 Description of Methodology for Volt / Var Optimization

Simulating Active Distribution Systems. Roger C. Dugan Sr. Technical Executive EPRI, USA. OpenDSS

Smart Distribution Technology

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,

POWER WORLD LAB MANUAL

Requirements for Data for Power System Modeling and Analysis (MOD-032-1) Arizona Public Service Company

Power System Network Simulator (PSNsim)

Hosting Capacity for Distributed Energy Resources on Distribution Feeders A Case Study

ASPEN Software - Introduction

Karl Iliev, San Diego Gas & Electric Company

CHAPTER 4 FACTS CONTROLLERS FOR OPTIMIZATION OF POWER SYSTEM

ASPEN Software - Introduction

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):

ETAP PowerStation 4.0

Demonstration Test Bed for Advanced Control Systems

SMUD Model Data Requirements & Reporting Procedures MOD VERSION 1.2

ONLINE CLOSED-LOOP OPTIMIZATION OF DISTRIBUTION NETWORKS

BC Hydro s Voltage and VAR Optimization Program IEEE PES JTCM VVC TF - 13 Jan 2010

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Dynamic State Estimation Based Protection: Laboratory Validation

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds

Utility Interconnection. Highlights of the New Fast Track Process Proposed by FERC and Changes to IEEE 1547

COMPACT SUBSTATION WITH 34.5kV GIS (GAS-INSULATED SWITCHGEAR. Cleverson Shindi Takiguchi S&C Electric Europe LTd. Cape Town/WC South Africa

Semi-Structured Data Management (CSE 511)

Data Processing at Scale (CSE 511)

Final Report. Mini Project TET Group nr 7 - Project nr 4. Students: Hans Lavoll Halvorson, NTNU

Power System Enterprise Solution

345kV Transmission Line Thermal Uprating Using Connector Shunts

Power Flow Method for Loss Allocation in Radial Distribution Networks with DGs

Main Components of a Static Var Compensator (SVC)

System Studies for American Transmission Co. s Benson Lake SVC Project

SDG&E EPIC Program Overview

ELG4125: System Protection

Electrical Systems Technology

DSSim-XX communication library for MATLAB

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Simulation of FACTS Devices as Reactive Power Compensators and Voltage Controllers in the Smart Grid

SVC Light for rail traction The way to effective grid integration

Introduction to PowerWorld Simulator: Interface and Common Tools

Data Driving the Smart Grid

What s New in Version 5.00 Compared to Version 4.52

WinIGS. Windows Based Integrated Grounding System Design Program. Structural Dynamic Analysis Training Guide. Last Revision: February 2017

N-1-1 Reactive Upgrades

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

An expert solution is within your reach. EORSys. We take care of it.

Commission Testing Methods for Protection Systems

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Packaged Solutions. Grid Solutions. Value Added Solutions for Protection, Control and Automation Applications. Flexible and Expandable

INTERCONNECTION FACILITIES STUDY REPORT

National Load Despatch Centre Power System Operation Corporation

Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi

Using WECC Composite Load Model and PowerWorld Time Step Simulation Tool. Eleanor Ewry

Southern Company Smart Grid

HIGH LEVEL REQUIREMENTS OF FAST SIMULATION AND MODELLING SUITE OF TOOLS FOR FUTURE SELF-HEALING DISTRIBUTION POWER SYSTEM

Plats för bild på PST2291 med solpanel och en person

IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems

Simulation and Analysis of Static Var Compensator with Matlab

2. Control Pin Functions and Applications

2018 General Rate Case. Transmission & Distribution (T&D) Volume 3 R System Planning

Performance analysis of FACTS devices in steady state power flow

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Distribution Static Var Compensators and Static Synchronous Compensators for Suppressing Voltage Fluctuation

CONSCIENCE TECHNOLOGIES A Right Platform For All Engineers... CODE B.TECH EEE MAT LAB PROJECT TITLE

Version Changes

State Estimation at All India Level

This webinar brought to you by the Relion product family

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

Ground or Not to Ground Ethernet Protection (Part 2) Nisar Chaudhry P.E. Tii Network Technologies, Inc. Presented at Protection Engineers Group 2013

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

Load Flow Analysis. I Objectives

Bus Way vs. Cable: a CapEx comparison

Power systems 5: Protection

Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281

TSR A & B - FACILITIES STUDY REPORT

ETAP PowerStation 4.0

System Engineering, IT/OT Integration and the Smart Grid. Steve Apps Pr.Eng SAIEE Associate Director EON Consulting, South Africa

Pepco s Plans for Smart Grid. Rob Stewart Blueprint Technology Strategist

Wind Plant Systems Grid Integration Plant and Turbine Controls SCADA

Real Time Digital Simulator Testing of an On Line Integrated Stability Control System

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1

Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids

FAULT DETECTION ON RADIAL POWER DISTRIBUTION SYSTEMS USING FUZZY LOGIC.

Power Networks Demonstration Centre

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

Modular Multilevel Converter Solution in RT-LAB

Smart Grid Implementation Lessons Learned

Transcription:

Modeling and Simulation in XENDEE IEEE 34 Node Test Feeder Shammya Saha Graduate Research Assistant Electrical Engineering Ira A. Fulton School of Engineering Arizona State University shammya.saha@asu.edu Nathan Johnson Assistant Professor The Polytechnic School Ira A. Fulton School of Engineering Arizona State University nathanjohnson@asu.edu March 2, 2016 This document is one of several guides designed to support skills development in distribution network modeling. It can be used during standard university curricula, a short industry course, self-guided lessons, peer learning, or other training opportunities. Files resulting from the guide can also be modified at the discretion of the user to pursue advanced topics of analysis. The IEEE Test Feeders are used as examples given their wide recognition and use. Resulting power flow analysis and short circuit analysis are presented in separate documents for each test feeder. Each guide is developed through a partnership between Arizona State University researchers and XENDEE. These training guides have been successfully used to train people individually, in small and large classrooms, during interactive micro-grid boot camps, and during short sessions for industry integrators and operators. IN BRIEF: IEEE 34 Node Test Feeder is an existing feeder located in Arizona, with a nominal voltage of 24.9 kv. It is characterized by long and lightly loaded overhead transmission lines, two in-line regulators, one in-line transformer for a short 4.16 kv section, a total number of 24 unbalanced loads, and two shunt capacitors.

ONE-LINE DIAGRAM The below figure shows the one-line diagram of the IEEE 34 Node Test Feeder available in the IEEE 34 Node Test Feeder.doc file. 1 848 822 846 820 844 818 864 842 800 802 806 808 812 814 850 810 816 824 826 858 832 852 834 860 888 890 836 862 838 840 828 830 854 856 The below figure shows the one-line diagram of the IEEE 34 Node Test Feeder built in XENDEE.

2 1. OVERVIEW AND TECHNOLOGIES This document describes how to model the IEEE 34 Node Test Feeder in the XENDEE cloud computing platform. XENDEE simulation models and system infrastructure documentation are also included with this guide. OpenDSS, an open-source technology developed by the Electric Power Research Institute (EPRI), is a powerful analytics engine capable of simulating complex multi-phase electrical power distribution systems. XENDEE enhances EPRI OpenDSS with enterprise level features such as visualization, design, simulation, and reporting automation. XENDEE is a web-based analytical tool that runs in Mozilla Firefox using the Microsoft Silverlight add-on. 2. ATTACHMENT AND RELEVANT DOCUMENTS This package (IEEE34.zip) includes XENDEE model files (.xpf) that can be imported to create a personal XENDEE project library. Additional supporting files required for independent testing and verification are listed in Table 1. Table 1. List of XENDEE Files Along with Supporting Files for XENDEE Modeling. File Name IEEE_34_LVRauto.xpf IEEE_34_LVRtapsFixed.xpf Cap data.xls Transformer data.xls Distributed load data.xls Spot load data.xls Line Configurations.xls Line data.xls IEEE 34 Node Test Feeder.doc IEEE Test Feeder.pdf File Details XENDEE XML model with auto-adjusting regulators XENDEE XML model with fixed tap transformers Shunt capacitor data Transformer Parameters Distributed load data in kw, kvar, and power factor Spot load data in kw, kvar, and power factor Overhead wire model and pole configuration data Connectivity and configuration data for each segment IEEE Power Flow Results Details of wire parameters and pole construction IEEE_34_LVRauto.xpf A XENDEE model that implements line voltage regulators (LVRs) as suggested by EPRI. Specifically, OpenDSS simulates tap changes and then recalculates power flow. Many other software tools complete power flow studies using only estimates of tap changes.

IEEE_34_LVRtapsFixed.xpf A XENDEE model of the same network but with single-phase transformers with fixed tap settings defined to match IEEE data. 3 3. THE XENDEE NETWORK MODEL XENDEE automatically generates a one-line diagram and adjusts the layout to accommodate new nodes added to the system. Additional nodes are needed beyond the standard 34 nodes because of the mid-nodes that are created in-between nodes to simulate distributed loads. 3.1 POWER UTILITY (SLACK BUS) The utility has been modeled as a 69 kv three phase source (Figure 1). All other parameters for the utility were kept at their default value as shown in XENDEE. Figure 1. Slack Bus with model (left) and power flow solution (right). 3.2 TRANSMISSION LINE MODELING Modeling power flow along a transmission line requires data including (1) line length between two nodes, (2) line parameters and pole construction data at a specific bus. Line Data.xls Line length between two nodes with the configuration for that specific line. Line Configuration.xls Line parameters including the Geometric Mean Ratio (GMR) of the line and resistance per mile. Values pulled from the XENDEE overhead line catalogue.

4 XENDEE code words for a specific ACSR wire are present in this file (see Table 2). Pole construction data is also included for the each type of configuration. IEEE Test Feeder.pdf All details summarized for the IEEE Test Feeder. Table 2. IEEE Conductor Models in XENDEE. IEEE Conductor Model ACSR 1/0 ACSR #2 6/1 ACSR #4 6/1 Corresponding code word from XENDEE Catalogue IEEE8 IEEE11 IEEE12 3.3 TRANSFORMER MODELING Transformers are modeled in XENDEE according to the winding connection provided in the Excel file. Figure 2. Transmission Line with model (left) and power flow solution (right).

Transformer Data.xls Transformer model data. XENDEE requires ZZ% and XX % ratio for RR modeling a transformer as given in Table 3. Table 3. Transformer Parameters for IEEE 34 Node Test Feeder RR% XX% ZZ% = RR 22 + XX 22 (XX/RR)% Substation Transformer 1.00 8.00 8.062 8.000 Ignored in the IEEE results XFM-1 1.9 4.08 4.500 2.147 5 Substation transformer impedances are provided but they are not used by IEEE for power flow analysis. IEEE reports results that assume voltage begins at the substation bus at the designated voltage. To address this issue, a substation transformer in XENDEE has RR% of 0.001% and XX % RR of 1.001%. 3.4 LINE VOLTAGE REGULATOR MODELING Figure 3. Transformer with model (left) and power flow solution (right). A line voltage regulator is connected between two nodes or two buses. This regulator modifies the line voltage in case of sudden addition or loss of load connected to the distribution network. Regulator Data.xls Contains line voltage regulator information. IEEE_34_LVRauto.xpf uses LVR with automatic tap control. This is used for modern distribution system analysis rather than estimated tap control. Additional information required to model the LVR in XENDEE is provided in the following table.

6 Table 4. LVR Parameters for IEEE 34 Node Test Feeder. Parameter Value Rating 2MVA Impedance 0.001% XX/RR% ratio 1.001 Delay 30s Tapping Secondary The LVR is modeled by a single phase transformer with a fixed tap setting. Similarly, a three phase LVR is modeled by three single phase transformers each associated with an individual phase and a fixed tap position. IEEE_34_LVRtapsFixed.xls uses single phase transformers with fixed tapping instead of LVR. The fixed tap values are present in IEEE 34 Node Test Feeder.doc in the power flow results section. Each LVR fixed tap setting is calculated using the following equation: tttttt% iiii XXXXXXXXXXXX = 100 + 0.625 AAAAAAAAAAAA TTTTTT iiii LLLLLL For example, if the transformer tap in the power flow solution is kept at position 12, the corresponding percentage tap in XENDEE is: 100 + 0.625 12 = 107.5% 3.5 MODELING LOADS There are two types of loads in the IEEE test system: Spot loads Loads connected to a specific node Distributed loads- Loads distributed between two connected nodes

7 Figure 4. LVR with model (top) and power flow solution (bottom). 3.5.1 SPOT LOADS All spot loads have their respective load model (constant power, constant impedance, constant current) type defined and are considered balanced across all three phases. These loads are modeled as three phase with appropriate load model. Spot_Load_Data.xls includes spot load data. Figure 5. Spot loads with model (left) and power flow solution (right).

The power factor for the load is calculated in the Excel file. XENDEE requires the power factor be given as a percentage of the load. See column heading Power Factor (%). 8 3.5.2 DISTRIBUTED LOADS Unbalanced load data for distributed loads are included in a separate file. Distributed_Load_data.xls includes distributed load data. Modeling a distributed load requires creating an additional node between the two nodes across which the distributed load is applied. For example, the IEEE test case provides information for distributed loads that can be connected between two nodes as shown in Figure 6a. Figure 6a. Distributed load schematic for IEEE test case. XENDEE / EPRI OpenDSS approach this scenario by inserting a middle node and modeling two overhead wires of the same configuration but each having one-half the length of the original line. Figure 6b shows this approach for the original line shown in Figure 6a. Figure 6b. Distributed load schematic using one-half line length.

9 In looking at an example from the actual IEEE 34 Node Test Feeder system, Figure 7 shows an extra node created at the midpoint between nodes 802 and 806. That distributed load is connected to that middle node. Figure 7. Distributed loads with model (left) and power flow solution (right). 3.6 MODELING SHUNT CAPACITOR The shunt capacitor parameters are available in the Shunt Capacitor Excel file. They are modeled using the capacitor bus in XENDEE according to their phase information. Figure 8. Shunt capacitors with model (left) and power flow solution (right).

4. MODEL AND SIMULATION VALIDATION: IEEE_34_LVRTAPSFIXED.XPF 4.1 RADIAL FLOW SUMMARY Real power, reactive power, and system with losses are given in Table 5 with comparisons between XENDEE simulation results and those reported in IEEE 34 Node Test Feeder.doc. 10 Table 5. Comparison of Power and Losses between IEEE Results & XENDEE Simulation. Output Result IEEE XENDEE Difference (%) Total System input MW 2.0429 2.0432 0.0001 Total System input MVAR 0.2903 0.2909 0.0020 Total System kw Loss 273.0490 267.8790 0.0190 Total System kvar Loss 34.9990 34.8820 0.0030 4.2 VOLTAGE PROFILE VALIDATION The voltage profile of selected nodes is provided in Table 6 for comparison. Table 6. Comparison of Phase Voltage Magnitude & Angle between IEEE Results & XENDEE Simulation. Node IEEE A-N XENDEE A-N IEEE B-N XENDEE B-N IEEE C-N XENDEE C-N IEEE Angles XENDE Angles 800 1.0500 1.0500 1.0500 1.0500 1.0500 1.0500 0.0/-120.0/120.0 0.0/-120.0/120.0 802 1.0475 1.4750 1.0484 1.0485 1.0484 1.0485-0.5/-120.1/119.9-0.1/-120.1/119.9 806 1.0457 1.0458 1.0474 1.0475 1.0474 1.0475-0.1/-120.1/119.9-0.1/-120.1/119.9 808 1.0136 1.0141 1.0296 1.0300 1.0289 1.0293-0.8/.120.9/119.3-0.8/-121.0/119.3 The voltage profile at each node can be viewed within the annotation view in XENDEE. Moreover, the professional report view in XENDEE can be used to check voltages at any node. 4.3 CURRENT FLOW VALIDATION The magnitude of current through selected lines is provided in Table 7. Table 7. Comparison of Phase Current Magnitude between IEEE Results & XENDEE Simulation. Line From Node To Node IEEE Phase A XENDEE Phase A IEEE Phase B XENDEE Phase B IEEE Phase C XENDEE Phase C L14a 828 830 35.87 35.90 36.93 36.90 37.77 37.80 L17a 834 860 11.16 11.20 9.090 9.100 10.60 10.60 L22a 844 846 9.830 9.900 9.400 9.400 9.400 9.400 L24 850 816 48.47 48.50 40.04 40.00 38.17 38.20 The annotation view in XENDEE can also be used to view current values through individual lines for each phase.

11 5 ADDITIONAL NOTES We hope you have benefited from this step-by-step guide to creating an IEEE Test Feeder in XENDEE. The full XENDEE results report can be generated by importing and simulating the models referenced in this guide. The partnership with XENDEE has allowed our education and research programs at Arizona State University to grow rapidly through the easy-to-use and versatile user interface. You can find out more about our research, computational lab, micro-grid test bed, and capacity building programs at http://faculty.engineering.asu.edu/nathanjohnson/ Visit XENDEE at www.xendee.com to access the online simulation tool Data for the IEEE 34 Node Test Feeder can be downloaded from the Web at http://ewh.ieee.org/soc/pes/dsacom/testfeeders/index.html To learn OpenDSS visit http://smartgrid.epri.com/simulationtool.aspx