Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center

Similar documents
INSIDE: Enterprise Migrations to Collocation Sites See page 12.

Rack-Level I/O Consolidation with Cisco Nexus 5000 Series Switches

Deploying 10 Gigabit Ethernet with Cisco Nexus 5000 Series Switches

How You Can Optimize Passive Optical LAN Through Structured Cabling

InfiniBand SDR, DDR, and QDR Technology Guide

Fibre Channel over Ethernet and 10GBASE-T: Do More with Less

Mellanox Virtual Modular Switch

Anticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards

IBM Europe Announcement ZG , dated February 13, 2007

Passive optical LAN explained

for Power Energy and

Trends in Data Centre

Migrate from Cisco Catalyst 6500 Series Switches to Cisco Nexus 9000 Series Switches

Technical Document. What You Need to Know About Ethernet Audio

OmniSwitch 6850E Stackable LAN Switch

High Speed Migration: Choosing the right multimode multi-fiber push on (MPO) system for your data center

Conflicts in Data Center Fiber Structured Cabling Standards

Category 8 paves the way for IEEE 40GBASE-T. David Hughes RCDD/DCDC/NTS Senior Technical Manager MEA CommScope

Increasing Bandwidth while Reducing Costs with the AOI Remote PHY Solution

Arista 7160 series: Q&A

Cabling Best Practices Using Fast Channel TM Switch Connect. Marc Dunham, Methode - Data Solutions

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Saving Critical Space. Cable Management Solutions

Cisco HyperFlex HX220c M4 Node

Pass-Through Technology

The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures. Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress

Deploying Gigabit Ethernet to the Desktop: Drivers and Applications

APPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS

Arista 400G Transceivers and Cables: Q&A

IBM To Resell Cisco Systems MDS 9000 Multilayer Switch and Director Family of Intelligent Storage Networking Products

Chapter 10: Planning and Cabling Networks

THE OPEN DATA CENTER FABRIC FOR THE CLOUD

SAN Design Best Practices for the Dell PowerEdge M1000e Blade Enclosure and EqualLogic PS Series Storage (1GbE) A Dell Technical Whitepaper

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett

Enterprise-class desktop virtualization with NComputing. Clear the hurdles that block you from getting ahead. Whitepaper

Optimizing PON architectures maximizes electronics efficiencies. White paper

Virtualization and consolidation

Networking Terminology Cheat Sheet

Introduction. Figure 1 - AFS Applicability in CORD Use Cases

V-Built Custom Preconfigured Solutions

Managing Density Managing Density in the Data Center: A Long-term Approach for the Future

83951c01.qxd:Layout 1 1/24/07 10:14 PM Page 1 PART. Technology Evolution COPYRIGHTED MATERIAL

SINGLEstream Link Aggregation Tap (SS-100)

BROCADE ICX 6610 SWITCHES FREQUENTLY ASKED QUESTIONS

HUBER+SUHNER DCCT Training

Cisco HyperFlex HX220c M4 and HX220c M4 All Flash Nodes

Cisco Nexus 4000 Series Switches for IBM BladeCenter

Network Service Description

V.I.B.E. Virtual. Integrated. Blade. Environment. Harveenpal Singh. System-x PLM

San Francisco Chapter. What an auditor needs to know

Cabling Solutions for Nexus 9000 Switches With Dual-Rate 40/100G BiDi Transceiver and Panduit Connectivity

IBM Ethernet Switch J08E and IBM Ethernet Switch J16E

New Product: Cisco Catalyst 2950 Series Fast Ethernet Desktop Switches

SUN BLADE 6000 VIRTUALIZED 40 GbE NETWORK EXPRESS MODULE

Hitachi Adaptable Modular Storage and Hitachi Workgroup Modular Storage

THE INVISIBLE UPGRADE: MOVING TO 1Gbps

Simplify Fiber Optic Cabling Migrations with a Multi-Path System

The Arista Universal transceiver is the first of its kind 40G transceiver that aims at addressing several challenges faced by today s data centers.

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric

2 visit

SAAS: THE RDP ADVANTAGE FOR ISVS AND USERS

BUILD A BUSINESS CASE

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016

HP Converged Network Switches and Adapters. HP StorageWorks 2408 Converged Network Switch

A PRINCIPLED TECHNOLOGIES TEST REPORT DELL ACTIVE SYSTEM 800 WITH DELL OPENMANAGE POWER CENTER

Siemon Interconnect Solutions

802.11ac FREQUENTLY ASKED QUESTIONS. May 2012

GPON Gigabit Passive Optical Network

Hitachi Adaptable Modular Storage and Workgroup Modular Storage

Arista 7060X, 7060X2, 7260X and 7260X3 series: Q&A

Cisco HyperFlex HX220c M4 and HX220c M4 All Flash Nodes

Using the Network to Optimize a Virtualized Data Center

BWDM CWDM DWDM WDM TECHNOLOGY

Siemon PON Fiber Cabling Solutions

QLogic 10GbE High-Performance Adapters for Dell PowerEdge Servers

CORNING S EDGE SOLUTIONS FOR DATA CENTERS

As enterprise organizations face the major

Passive Optical LAN Executive Summary. Overview

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy

Broadcom Adapters for Dell PowerEdge 12G Servers

Cisco Introduces the Cisco Nexus 2232TM-E 10GE Fabric Extender

3331 Quantifying the value proposition of blade systems

Juniper Virtual Chassis Technology: A Short Tutorial

24-Fiber MPO System 10/40/100 GbE Migration Solution HIGH DENSITY EQUIPMENT PANEL (HDEP) ORDERING GUIDE

1 of 5 12/31/2008 8:41 AM

Architecting the High Performance Storage Network

The Software Defined Hybrid Packet Optical Datacenter Network BIG DATA AT LIGHT SPEED TM CALIENT Technologies

The Smart Route To Visibility. GigaVUE H Series. High-density, High-scale Traffic Visibility Fabric Nodes

The Economic Benefits of a Cooperative Control Wireless LAN Architecture

Role of Copper Cabling in Datacentres

w w w. s i g n a m a x. c o m Power over Ethernet PoE A P P L I C A T I O N S G U I D E

Cisco UCS Mini Software-Defined Storage with StorMagic SvSAN for Remote Offices

Cisco Meraki MS400 Series Cloud-Managed Aggregation Switches

NC Education Cloud Feasibility Report

Distributed Core Architecture Using Dell Networking Z9000 and S4810 Switches

Cisco Nexus 9508 Switch Power and Performance

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

SEL-2730M. Reliably Control and Monitor Your Substation and Plant Networks. Managed 24-Port Ethernet Switch

FOUR WAYS TO LOWER THE COST OF REPLICATION

Microsoft IT Leverages its Compute Service to Virtualize SharePoint 2010

Transcription:

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center Executive Summary There is no single end-all cabling configuration for every data center, and CIOs, data center professionals and IT managers need to examine the pros and cons of each solution based on their specific needs. This paper focuses on the many factors to consider when evaluating top of rack (ToR) and structured cabling configurations. The discussion includes the impact of those configurations on total management; scalability and upgrades; interoperability; equipment, maintenance and cabling costs; port utilization; power consumption and cooling requirements. Bandwidth demand and scalability, server virtualization, high-performance switching capabilities and higher densities necessitate taking a careful look at the various configurations available for cabling a data center. Today s data center cabling configuration choices are also impacted by the need to lower power consumption and ensure efficient cooling of critical equipment, as well as by budget constraints and management structure. Introduction As data centers become more complex, cabling system design and topology become critical. When the first data centers were built, end user terminals were connected via point-to-point connections. This was a viable option for small computer rooms with no foreseeable need for growth or reconfiguration. As computing needs increased and new equipment was added, these point-to-point connections resulted in cabling chaos with associated complexity and higher cost. In response, data center standards like TIA-942-A and ISO 24764 recommended a hierarchical structured cabling infrastructure for connecting equipment. Instead of point-to-point connections, structured cabling uses distribution areas that provide flexible, standards-based connections between equipment, such as connections from switches to servers, servers to storage devices and switches to switches (see Figure 1).

Figure 1: TIA-942-A Data Center Topology (similar to ISO 24764) With today s high-performance servers and virtualization, more applications can be delivered from a single rack of servers than ever before. In response, several switch manufacturers recommend a Top of Rack (ToR) configuration where smaller (1RU to 2RU) edge switches are placed in the top of each server rack (or cabinet) and connect directly to the servers in the rack via short preterminated small form-factor pluggable (e.g., SFP+ and QSFP) twinaxial cable assemblies, active optical cable assemblies or RJ-45 modular patch cords. ToR significantly increases the number of switches and reduces the initial amount of structured cabling. It is often recommended for its rack-at-a-time deployment, ability to limit the use of copper cabling to within racks, support for east-west (i.e., server-to-sever) traffic and rack-level management capabilities. Both TIA 942-compliant structured cabling and ToR have advantages and disadvantages. When selecting the cabling configuration to best meet the needs of the data center, it is important to examine the impact that structured cabling and ToR have on overall total cost of operations, as well as other trade-offs. Manageability Considerations Before choosing a cabling infrastructure, data center professionals should consider operational structure and policies. With structured cabling, patch panels that mirror switch ports and server ports connect to corresponding panels in one or more central patching areas or zones via permanent (or fixed) links. Also referred to as distribution areas, these patching areas may be located at the end or in the middle of a row of cabinets. Moves, adds and changes (MACs) are accomplished by repositioning patch cord or fiber jumper connections at the central patching area. The fixed portion of the channel remains unchanged and switches and equipment are left untouched and secure. This creates an any-to-all configuration where any switch port can be connected to any equipment port. Furthermore, structured cabling can be field terminated to any length to maintain a clean, slack-free appearance.

In a ToR configuration, switches at the top of each rack connect directly to the servers in the same rack, requiring all changes to be made within each individual rack (or cabinet). This eliminates the use of central patching and reduces the amount of structured cabling in the data center (see Figure 2). MACs in a ToR configuration can be more complicated and time consuming especially in large data centers with hundreds of cabinets. Changes must be made in individual racks or cabinets, rather than at one convenient central patching area. Identifying the specific rack or cabinet requiring the change can be a complicated process. ToR can be a solution for data centers where individual racks of servers and their corresponding switches need to be managed as their own entity or segregated by application. ToR does not allow network administrators to keep switches separate from server administrators, which can be problematic when these groups manage switches and servers separately and when switches must remain protected for security purposes. Figure 2: Structured Cabling vs. ToR Topology. ToR eliminates central patching in the distribution area. Note: Designs based on a three-tier switch architecture. Scalability and Upgrade Considerations Cabling system design can limit or enhance squeezing the most from racks, servers and ports. A widespread switch upgrade with ToR impacts many more switches than with structured cabling and requires equipment at the network core to have the port densities and bandwidth capacity to support the increased number of switches. An individual switch upgrade with structured cabling can increase connection speeds to multiple servers across several racks in the data center. An upgrade to an individual ToR switch improves connection speed to only the servers in that rack. ToR switches using short-distance small form-factor pluggable twinaxial cable assemblies cannot support autonegotiation. Because the twisted-pair cabling used with structured cabling is backwards compatible, it supports autonegotiation where individual ports can switch between a 10 and 1 gigabit operation depending on the connected equipment. Autonegotiation enables partial switch or server upgrades on an as-needed basis, enabling a cost-effective migration over time. Without autonegotiation, a switch upgrade requires all equipment connected to that switch to be upgraded simultaneously, incurring full upgrade costs all at once.

Because ToR small form-factor pluggable twinaxial cable assemblies are typically more expensive than copper patch cords in a structured cabling system, costs can escalate even further during upgrades as some equipment vendors require use of their cable assemblies and force cable upgrades with equipment upgrades. The core physical layer infrastructure or the fixed portion of the cabling channel is typically installed once, as long as the minimum standards recommended fiber and copper cabling are used. In a ToR configuration using small form-factor pluggable twinaxial cable assemblies, distance between the switches and the servers is limited to a length of 7 meters in passive mode. While this is not a problem if each rack will always be managed as an individual unit, these short lengths can restrict the location of equipment if needs change. Structured cabling lengths can be up to 100 meters, allowing flexible equipment placement. Interoperability Concerns Open systems enable more choices and a competitive market place. Interoperability and the open systems concept is the bedrock of cabling industry standards. Data center managers expect and value interoperability to fully leverage their existing cabling investment by ensuring performance and a competitive market regardless of which vendors equipment and cable designs are selected. Unfortunately, some switch vendors now require their proprietary cable assemblies for connecting ToR switches to servers when using small form-factor pluggable twinaxial cable assemblies. Some ToR switches are designed to check vendor security IDs on cables and either display errors or prevent ports from functioning when connected to an unsupported vendor ID. While this helps ensure that vendor-approved cable assemblies are used with corresponding electronics, it can limit data center design options by locking data center managers into a proprietary solution. This is a substantial change from the industry standards-based fiber connectivity and copper connectivity successfully deployed in data centers for decades. Third-party independent testing by University of New Hampshire's Interoperability Lab (UNH IOL) proves that passive small form-factor pluggable twinaxial cable assemblies from cabling vendors pass interoperability testing with several vendors ToR switches that are designed to display errors. These tests demonstrate that proprietary cables are not necessarily required. This may not be the case for switches designed to actually prevent ports from functioning altogether when connected to an unsupported vendor ID. Maintenance, Equipment and Cabling Cost The choice of cabling system has a major impact on cost. With a ToR switch in every cabinet (or two for dual primary and secondary networks), the total number of switch ports depends on the total number of cabinets in the data center, rather than on the actual number of switch ports needed to support the equipment. This can nearly double the amount of switches and power supplies required, compared to structured cabling. Unlike passive structured cabling, ToR switches require power and ongoing maintenance. For example, based on an actual 39-cabinet data center using separate dual networks, the cost for equipment and maintenance for ToR is more than twice that of structured cabling (see Figure 3). The use of distribution areas with structured cabling also impacts cabling costs. ToR saves on structured cabling costs, but the added cost of cabling assemblies can negate that savings, especially when switch vendors require their proprietary cable assemblies. As shown in Figure 3, the cost of the ToR cable assemblies for each used port is more than twice the cost of structured cabling. Even if the cost of ToR cable assemblies is not a consideration, structured cabling costs represents only about five percent of the total equipment and maintenance savings realized with structured cabling. Structured cabling also typically carries a 15 to 25 year warranty (depending on manufacturer) as opposed to the average 90-day warranty on cabling assemblies offered by most electronics vendors.

Equipment and Unit Price ToR Structured Cabling Units Price Units Price Total Savings 32-port 10G ToR Switches ($15,000) 78 $1,170,000 35 $525,000 $645,000 Redundant Power Supplies ($500) 78 $39,000 35 $17,500 $21,500 SFP+ Uplink ($1500) 312 $468,000 140 $210,000 $258,000 32-Port Aggregation Switches ($25,000) 10 $250,000 5 $125,000 $125,000 SFP+ Modules ($5000) 80 $400,000 40 $200,000 $200,000 Redundant Power Supplies ($500) 10 $5,000 5 $2,500 $2,500 Core Switches ($80,000) 2 $160,000 2 $160,000 0 Redundant Power Supplies at ($7,500) 2 $15,000 2 $15,000 0 Fiber Cards for Uplinks at ($70,000) 4 $280,000 2 $140,000 $140,000 Cabling Total $240,000 $110,000 $130,000 Equipment Total (not including software) $2,787,000 $1,395,000 $1,392,000 3 Years Maintenance $1,200,000 $570,000 $630,000 TOTAL $4,227,000 $2,075,000 $2,152,000 Figure 3: ToR vs. Structured Cabling Cost Comparison (based on MSRP at time of print) for an actual 39-cabinet data center (assumes average 5 to 6kW per cabinet, dual network, redundant power supplies, 14 servers per cabinet, four uplinks per switch, 2.5-meter SFP+ direct attach cable assemblies for each used ToR port, and category 6A UTP for structured cabling). Furthermore, a ToR design can add to server costs. Servers with twisted-pair network interface cards (NICs) are typically less expensive than those with SFP+ or QSFP NICs. Many server platforms also ship with twisted-pair copper NICs native to the motherboard. With ToR deployments supported by small form-factor pluggable twinaxial cable assemblies, SFP+ or QSFP NICs would need to be purchased for those connections, which can range from about $400 to $800 per NIC. Switch Port Utilization Structured cabling maximizes port accessibility and utilization. Studies by DataCenter Dynamics and the Gartner Group show that the average power supplied to a server cabinet ranges between 5 and 6kW. Using this assumption, the number of servers in a cabinet is approximately 14. Server switch port demand is therefore typically lower than the switch ports available on a ToR switch. For example, with only 14 ports of a 32-port switch used, 18 ports will remain unused. Other assumptions using a higher number of servers and higher power supplied to the server cabinet would improve the switch port utilization on a ToR switch. The relative economics would need to be determined based on the actual design and type of servers that are deployed. When using separate dual networks with 14 servers per cabinet where each server connects to two 32-port switches, 28 of the 64 ports are used for the 14 servers, leaving 36 unused. When applied across the actual 39- cabinet example used in Figure 3, this scenario results in 1,404 unused ports, which equates to nearly 44 unnecessary switch purchases (see Figure 4). With structured cabling, virtually all active ports can be fully utilized because they are not confined to single cabinets. Instead, the 32 switch ports that would be dedicated to a single cabinet in the ToR configuration can now be divided up, on demand, to any of several cabinets via the distribution area. Even if edge switches are used to accommodate east-west (i.e., server-to-server) traffic, structured cabling allows the switches to be centrally located in distribution areas, which decreases the number of unused ports and reduces the amount of north-south traffic to and from aggregate and core switches.

Equipment Units Total ToR Used Unused Units Structured Cabling Total Used 32-port 10G ToR Switches 78 2496 1092 1404 35 1120 1092 28 32-Port Aggregation Switches 10 320 312 8 5 160 140 20 Fiber Cards for Core Uplinks 4 128 40 88 2 64 20 44 Unused TOTAL PORT USAGE 2944 1444 1500 1344 1252 92 Figure 4: Switch port utilization for ToR vs. Structured Cabling for an actual 39-cabinet data center (assumes average 5 to 6kW per cabinet, dual network, redundant power supplies, 14 servers per cabinet and four uplinks per switch ). While the number of unused ports will be less in high-density server environments where the power supplied to server cabinets is now reaching upwards of 20kW to support a full complement of servers, they can still add up. For example, in a 200-cabinet high-density server farm with 40 servers and a 48-port switch per cabinet, the number of unused ports reaches 1600 (i.e., 8 unused ports per cabinet) at a cost of about $735,000. Using structured cabling can save nearly 85% even in these high-density environments. Being able to effectively manage unused switch ports is therefore a key consideration when selecting a ToR configuration. It is worth noting that some data centers use a switch fabric architecture, which may have a different outcome on the number of unused ports and amount of equipment and cabling compared to a three-tier switch architecture. However, the benefits of a structured cabling system remain. Increased Power Consumption Port utilization and equipment have a major impact on power consumption. Power consumption is one of the top concerns among today s data center managers as energy costs continue to rise, power becomes more costly and green initiatives take center stage. As shown in Figure 5 below, the ability to use all switch ports with structured cabling lowers the number of switches and power supplies required by more than half. This helps cut equipment and energy costs while contributing to green initiatives such as LEED, BREEAM or STEP. With structured cabling requiring fewer power supplies, future upgrades to more efficient power supplies are easier and more cost effective. Equipment ToR Structured Cabling 32-port 10G ToR Switches 78 35 Redundant Power Supplies 78 35 SFP+ Uplink 312 140 32-Port Aggregation Switches 10 5 SFP+ Modules 80 40 Redundant Power Supplies 10 5 Core Switches) 2 2 Redundant Power Supplies 2 2 Fiber Cards for Uplinks at 4 2 TOTAL SWITCHES 90 42 TOTAL POWER SUPPLIES 90 42 Figure 5: With structured cabling, the number of switches and power supplies required is less than half that of ToR, thereby reducing power consumption When switches reach full utilization in a ToR configuration, adding a new server to the cabinet requires an additional switch in the cabinet as well as additional power supplies. This can take away from potential power that

can be allocated for servers. There may not even be enough power provisioned to the cabinet to support the additional load. Even with virtualization reducing the number of servers and related power and cooling, the increased number of power supplies required with ToR can potentially negate some virtualization savings. It is important to remember that even in an idle state, unused switch ports can consume power. Furthermore, edge switches like those used in ToR process more instructions in their central processing units. This can cause potential unanticipated power spikes. Regardless of the configuration and technologies deployed, power consumption varies by switch model and manufacturer and actual port consumption or power draw should be examined across the entire data center. Cooling and Failure Rate Considerations Improper placement of equipment can wreak havoc on the best data center cooling and uptime plan. While a ToR switch can technically be placed in the middle or bottom of a cabinet, they are most often placed at the top for easier accessibility and manageability. According to the Uptime Institute, the failure rate for equipment placed in the top third of the rack is three times greater than that of equipment located in the lower two thirds. In a structured cabling configuration, the passive components (i.e., patch panels) are generally placed in the upper position, leaving the cooler space for the equipment. ToR designs can also land-lock equipment placement due to the short cabling lengths available and data center policies that do not allow patching from cabinet to cabinet. This can prevent placing equipment where it makes the most sense for power and cooling. For example, if the networking budget does not allow for outfitting another cabinet with a ToR switch, placement of a new blade server may be limited to where network ports are available. This can lead to hot spots, which can adversely impact neighboring equipment within the same cooling zone. Structured Cabling systems avoid these problems. Conclusion Many factors impact the choice of which cabling configuration to deploy, and there is no single end-all solution. ToR configurations can make a lot of sense for small server rooms, when self-contained cabinets are required or where a higher number of unused ports can be managed. However, data center managers should carefully consider the pros and cons as outlined in Figure 6. ToR Pros Reduced amount of structured cabling Lower cabling infrastructure costs Rack-based cable management and changes Rack-based access for application segregation Rack-based switch upgrades Figure 6: ToR Pros and Cons ToR Cons Significantly higher equipment, maintenance and cabling costs Poor port utilization Increased power consumption Scalability and upgrade limitations may not support interoperability and autonegotiation Time consuming MACs in large data centers Limited equipment placement and potential hot spots When selecting a cabling configuration for the data center, an overall study that includes total management; scalability and upgrades; interoperability; equipment, maintenance and cabling costs; port utilization; and power and cooling requirements should be undertaken by facilities and all networking departments to ultimately make the best educated decision. ToR is often positioned as a replacement for structured cabling, but in many instances, structured cabling must coexist with ToR to support central switching for KVM or other in-band or out-of-band management and data center monitoring.