A0-10 ANALOG OUTPUT. Instruction Manual April 2001 NALOG OUTPUT

Similar documents
Operating Instructions July milltronics ZSS

DOLPHIN PLUS. Instrument configuration software OLPHIN PLUS

Instruction Manual August milltronics ZSS

Instrument Configuration Software March dolphin PLUS

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS

COMPU-M INTEGRATOR. Instruction Manual PL-516 April Rev. 2.2

SMARTLINX INTERFACE MODULE

Ultrasonic Transmitters SITRANS LU150. Operating Instructions 03/2015 SITRANS

Instruction Manual February smartlinx interface module MODBUS RTU

Instruction Manual April 2001 CCUMASS SF500

Instruction Manual March airanger XPL PLUS

Ultrasonic Transmitters

Remote Data Manager. SITRANS RD500 Module 8 Inputs, 6 Relay Outputs. Operating Instructions 01/2010 SITRANS

SMARTLINX INTERFACE MODULE

Instruction Manual April milltronics SF500

Instruction Manual January milltronics MLC BELT SCALE

Instruction Manual July sitrans RD SOFTWARE

NTP-5521/5531/5561 SWITCHING MODE POWER SUPPLY

Ultrasonic Transmitters SITRANS LU150. Operating Instructions

SMARTLINX INTERFACE MODULE

Instruction Manual February smartlinx interface module PROFIBUS-DP

SITRANS L Level instruments

PanelView Plus/VersaView CE Terminals and Display Modules

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

Instruction Manual March smartlinx interface module REMOTE I/O

MARTLINX INTERFACE MODULE

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Installation & Operation Guide

Multi-Point Gas Detection and Control System

Model DMX8DIM Installation and Operations Manual

SITRANS LU 02. Instruction Manual January 2002

ENVIRORANGER ERS 500 NVIRORANGER ERS 500 USER GUIDE. Instruction Manual PL-600 January Rev. 1.2

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

Tempco Instruction Manual

PowerLogic High Density Metering System 1-Meter Enclosure

Carbon Monoxide (CO) Gas Detection and Control System

5B Series 16 Channel Backplane 5B01 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Analog Monitor Installation Manual

ICS Entrance Management Sign Installation Guide. Version 1.0

Analog Input Installation Manual

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

Specifications, Installation, and Operating Instructions

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

ACCUMASS BW500. Instruction Manual May 2002 ACCUMASS BW500

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

MOTION FAILURE ALARM MFA-4P OTION FAILURE ALARM. Instruction Manual PL-298 February Rev. 3.1

EPS Power Supply

Level-Lance Model 5400A

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

Siemens AG Continuous level measurement - Radar transmitters. Configuration. Mounting on a nozzle. Installation min.

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

ACCESS 9340/9360 Meter Input/Output Module

Product and functional description

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 120 Volt

Level Measurement Continuous level measurement Ultrasonic controllers

H704-42(H)(E), H704-42/1(H)(E)

HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control

Quick Start Guide TS A

PM Series Power Meter

ACCUMASS BW500. Instruction Manual PL-565 April Rev 1.0

Power Supply. Users Guide PRODUCT MANUAL. WESTELL.COM Westell Technologies MNL rd

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

Continuous level measurement Radar transmitters

ORB TM 4-20 ma Input Box Installation & Operation Manual

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016

ENVIRORANGER ERS 500 NVIRORANGER ERS 500 COMMUNICATIONS REFERENCE. Instruction Manual August 2001

MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER

Instruction Manual: IM E

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Model 7705 Control Module

Expansion Module HZS 541-1S

INSTALLATION INSTRUCTIONS

Level Measurement Continuous level measurement - Ultrasonic controllers

COMPU - M INTEGRATOR. Instruction Manual PL-453. July PRR 1.0

PowerFlex 400 AC Drive Guide Specification

Rack Input Module Installation Instructions

is then retained absolutely without interruption.

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Quick Start Installation Guide

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

Occupancy and Vacancy Sensors ROOM CONTROLLER* DAYLIGHT SENSOR WPP-INT INSTALLATION GUIDE

Service Instructions. Conductor 420

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 230 Volt

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

VBT-75 S2 VACUUM BOTTLE TESTER

Level instruments. Communications and Displays SITRANS RD200. 5/306 Siemens FI Technical specifications. Overview

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Laboratory Switch Mode Power Supply Series. Instruction Manual

Transcription:

A0-10 ANALOG OUTPUT Instruction Manual April 2001 NALOG OUTPUT

Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed. Qualified Personnel This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards. Warning: This product can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and maintained. Note: Always use product in accordance with specifications. Copyright Siemens Milltronics Process Instruments Inc. 2000. All Rights Reserved This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions. Disclaimer of Liability While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement. Technical data subject to change. MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments Inc. Contact SMPI Technical Publications at the following address: Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs@milltronics.com For the library of SMPI instruction manuals, visit our Web site: www.milltronics.com Siemens Milltronics Process Instruments Inc. 2001

AO 10: Introduction Note: The AO 10 is to be used only in the manner outlined in this instruction manual. The AO 10 Analog Output Module is used to provide analog output for the scan points of the associated application device. The operation of the AO 10 is programmed via the application device. The only AO 10 on-board settings are for bank selection and output testing. The AO 10 can be programmed to provide up to 10 analog outputs, each sharing a common negative buss which is electrically isolated from ground. If desired, the common negative buss and / or cable shield may be connected to ground at only one location; either at the AO 10 or at the load (e.g. customer's computer). Specifications Power 100/115/200/230 V ac ±15%, 50/60 Hz, 15 VA Environmental Input location: indoor / outdoor altitude: 2000 m max. ambient temperature: 20 to 50 C ( 5 to 122 F ) relative humidity: suitable for outdoor (Type 4X / NEMA 4X / IP65 enclosure) installation category: II pollution degree: 4 communication from application device 1 ± 20 ma bipolar current loop 4800 baud rate non-polarized Output 10 analog current outputs, programmable from application device 1 isolated 0 or 4 to 20 ma into 750 Ω max. 0.1% resolution Accuracy: 0.25% of span 1. Application Device: AiRanger XPL & XPL Plus process material level monitors 7ML19981CE01 AO 10 INSTRUCTION MANUAL Page 1

Display 1 power / communication status LED Memory 10 minutes minimum data retention Enclosure Type 4X / NEMA 4X / IP65 209 mm W x 285 mm H x 92 mm D (8.2" W x 11.2"H x 3.6"D) polycarbonate Approvals Weight CE 2, FM, CSA NRTL/C 2 kg (4.4 lb) Cable (optional): Belden 8760, shielded / twisted pair, 18 ga. or equivalent 2. EMC performance available upon request. Page 2 AO 10 INSTRUCTION MANUAL 7ML19981CE01

Installation Note: Installation shall only be performed by qualified personnel and in accordance with local governing regulations. Mount the AO 10 in an area that is within the unit's ambient temperature range and suitable for the specified enclosure. The front cover should be easy to view, and should have room to swing open for access to wiring and switch-settings. Caution: Do not mount the AO 10 in direct sunlight without the use of a sun shield. This product is susceptible to electrostatic shock: follow proper grounding procedures. The AO 10 may be installed remotely from the associated application device to a maximum loop length of 3,000 m (10,000 ft) when using 18 ga. wire. Outline and Mounting 16 mm (0.6") 209 mm (8.2 ) 172 mm (6.8 ) Lid screws (6 places) 91 mm (3.6 ) 285 mm (11.2 ) 267 mm (10.5 ) 4.3 mm (0.17 ) dia. 4 places Mounting holes (accessed under lid) Suitable location for conduit entrances Milltronics recommends using a punch for making holes in enclosure. Lid Enclosure Customer mounting screw Caution: Non-metallic enclosure does not provide grounding between connections. Use grounding type bushings and jumpers. 7ML19981CE01 AO 10 INSTRUCTION MANUAL Page 3

Layout Board A All field wiring must have insulation suitable for at least 250 V. Page 4 AO 10 INSTRUCTION MANUAL 7ML19981CE01

Switch Settings Ensure that the BANK dip switch is set as shown below. toggle 1 2 3 4 bank (output) 1 0 0 0 1 (1 10) (toggles) Interconnection System Diagram Milltronics AO 10 Milltronics AiRanger XPL or AiRanger XPL Plus Typical system design. Refer to associated application device instruction manual. 7ML19981CE01 AO 10 INSTRUCTION MANUAL Page 5

AiRanger XPL Communication AO 10 AiRanger XPL AiRanger XPL Plus Communication AO 10 AiRanger XPL 1. AO 10 receiver input is non-polarized. 2. Refer to associated application device instruction manual for wiring detail. Check that the communication parameter (AiRanger XPL \ P-54 or AiRanger XPL Plus \ P740, is `ON'. 3. AO 10 interconnecting cable shield should be grounded at AiRanger XPL or AiRanger XPL Plus only. Insulate shields at junctions to prevent inadvertent grounding. Use Belden 8760, 1 pair shielded twisted, 18 ga. or equivalent. Maximum individual loop length is 3000 m (10,000 ft). Page 6 AO 10 INSTRUCTION MANUAL 7ML19981CE01

Current Output isolated 0 or 4 to 20 ma out, 750 Ω load max. (typical of 10) ma outputs: Belden 8760, shielded / twisted pair, 18 AWG (0.75mm 2 ) or equivalent. Maximum separation 1,500 m (5,000 ft). ma output to customer instrumentation: ground shield at one end only All field wiring must have insulation suitable for at least 250 V Power Note: The AO-10 ma output cable must be shielded over its entire length and grounded at one point only, for maximum noise immunity. Ensure the application device is properly grounded. Connect the cable shield to the application device shield terminal. To avoid developing a ground loop, leave the cable shield open at the AO-10 termination and insulate any cable shield junctions from ground. Switch is shown in OFF position. Select appropriate voltage. 100 / 115 / 200 /230 V 50 / 60 Hz select voltage via switch Caution: The equipment must be protected by a 15 A fuse or circuit breaker in the building installation. A circuit breaker or switch in the building installation, marked as the disconnect switch, shall be in close proximity to the equipment and within easy reach of the operator. 7ML19981CE01 AO 10 INSTRUCTION MANUAL Page 7

Operation Analog output span (empty to full scale) and range ( 0-20 or 4-20 ma, proportional or inverse ) are established when programming the associated application device. Trimming and limiting of the individual analog outputs is done via the application device, where applicable. Associated Parameters. Function Parameter AiRanger XPL AiRanger XPL Plus span P-04 P007 range P-06 P006 trim P-17 & 18 P212 & P213 limit P-19 & 20 P214 & P215 Refer to the associated application device manual. When power is applied to the AO 10, LED 1 illuminates, and all analog outputs default to 0 ma until they are updated by the associated application device. DATA RECEIVED LED 1 also flashes whenever a valid message is received from the application device. If LED 1 does not flash and the corresponding AO 10 is functioning properly, check for faulty communication wiring. The received data from the application device is then processed to extract only the data dedicated to the AO 10 bank selected. The buffers associated with the individual outputs hold the extracted data until it is updated, controlling the analog output level accordingly. These buffers are updated subject to the scan sequence of the application device, but the analog outputs are independent of the application device LCD display. If there is a power interruption, all outputs drop to 0 ma, but the stored output values are retained in memory for ten minutes. Once power is restored, all outputs revert to their previous ma values, if the memory is intact, and normal operation resumes. The AO 10 can be programmed to activate an alarm if communication is lost. When the toggles are set as shown below, the AO 10 forces all outputs to 0mA if communication is lost for more than the set time. When communication is resumed, the outputs revert to their normal function. 5 minutes 3 minutes 1 minute Page 8 AO 10 INSTRUCTION MANUAL 7ML19981CE01

The AO 10 may be tested in two ways: 1. Via the associated application device: Refer to the associated instruction manual. 2. Via the TEST switch located at the top of the AO 10 board. Set the toggle down at 1 for the test output desired. Set all toggles down at 0 for normal operation. Test output of 4 ma is selected. This test overrides the normal operation and all 10 outputs on the AO 10 assume the test value selected until the toggle is reset (0) for normal operation. During test, the AO 10 buffer updates if communication has continued. Upon resumption of normal operation, the outputs assume the value found in the buffer. Maintenance The AO 10 requires no maintenance, but a program of periodic checks is recommended. This should include regular inspection, general cleaning and good housekeeping practices. Always disconnect power at the main breaker before cleaning the enclosure. Use a vacuum and a clean, dry paint brush to clean the enclosure and circuit boards. Check all electrical terminals for corrosion and arcing. 7ML19981CE01 AO 10 INSTRUCTION MANUAL Page 9

Notes

Notes

*7ml19981ce01* Rev. 1.0