Manual No: Revision: F. Relay Output Modules. Installation Guide

Similar documents
Vapor Monitor Interface Module

IFSF Interface Module

Manual No: Revision: D. Mag Retrofit Probe. Installation Guide

Pressurized Line Leak Controller Module. For Veeder-Root TLS-350/350R Systems

TLS-3XX Series Consoles

Manual No: Revision: E. Mag Plus Probe. Assembly Guide

Manual No: Revision: A. TLS-4XX Consoles. Upgrade Installation Instructions

Manual No: Revision: G. Mag Probe. Assembly Manual

Pressurized Line Leak Interface Module. For TLS-350 and TLS-350R Systems

Manual No: Revision: D. Tokheim DIMs. Installation Guide

TLS-450 To TLS-450PLUS Console

INSTALLATION and QUICK HELP FOR TLS CONSOLE INTERFACE TO THE VEEDER-ROOT EMR4 DATALINK USING AN XTEND 900 MHZ WIRELESS MODEM Rev.

TLS-350 Series Consoles

Manual No: Revision: D. TLS-XB Expansion Box. Site Prep and Installation Manual

Always make sure ALL power to the equipment you are working with is turned OFF before starting any maintenance.

XTEND 900 MHZ WIRELESS MODEM For use with VEEDER-ROOT EMR4 DATALINK INSTALLATION INSTRUCTIONS Manual , Rev. A

TLS4/8601 Series Consoles

OilCop Component Wiring Installation Manual

TLS4/8601 Series Consoles

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 7705 Control Module

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

Installation Instructions. For TMS MPC Systems Connecting to Gilbarco Electronic Pumps/Dispensers

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

OPERATING MANUAL LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES

LINE VOLTAGE TESTER CT101 USER S MANUAL. Please read this manual carefully and thoroughly before using this product.

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

UniStream CPU-for-Panel

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

V E2B Snap-in I/O Module

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Upgrading and Servicing Guide

PS/IO Circuit Board Retrofit

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

Manual No: Revision: I. TLS-350 Series. Board and Software Replacement

I/O Expansion Box Installation & Operator s Instruction Manual

EX-RC1 Remote I/O Adapter

Multi Unit Enclosed Meter

iconverter 2-Module Power Chassis

Upgrading and Servicing Guide

Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch

Model 2380 Rack-Mount Kit

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

CA-A480-A Elevator Controller. Reference & Installation Manual

C-POWER AC AUTOMATIC CONTROL

CMSA-100 Manual. Cinema Media Server Automation

Differential Liquid/Gas Pressure Transmitter

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Model 2380 Rack-Mount Kit

TLS-4XX Setup and Operation

MTP INSTRUCTION MANUAL

5504 Thermocouple Analog Input Module

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

TC100 Precision Thermocouple Calibrator

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

Install Motor Controller User Manual

High Speed Remote I/O Module

MDE-4815B INSTALLATION MANUAL. This document is based on Orpak s WGT outdoor unit installation manual P/N

2-Way Wireless I/O Expander Installation Guide

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Series 8000 RF Signal Switch Solution

User Guide. Control Box. RoscoLED TM.

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

TRC-190 User s Manual

Installation Notes TII Model 341 Protector

3M Wrist Strap and Ground Monitor 773. User s Guide

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

6222 Two Door Module Technical Operations Manual

User's Guide. MiniTec TM Series Model MN25 MultiMeter

SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION. NI CompactDAQ Four-Slot Controller with Quad-Core Processor

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Vision OPLC V TR6/V350-J-TR6

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

Installation and Operation

Tornado F-5. Motor Backspin Detect Relay And Probe For F-5 Motor Controller

Model 2657A-LIM-3 LO Interconnect Module

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

Transcription:

Manual No: 576013-614 Revision: F Relay Output Modules Installation Guide

Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication. Veeder-Root reserves the right to change system options or features, or the information contained in this publication. This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root. DAMAGE CLAIMS 1. Thoroughly examine all components and units as soon as they are received. If damaged, write a complete and detailed description of the damage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description. 2. Immediately notify the delivering carrier of damage or loss. This notification may be given either in person or by telephone. Written confirmation must be mailed within 48 hours. Railroads and motor carriers are reluctant to make adjustments for damaged merchandise unless inspected and reported promptly. 3. Risk of loss, or damage to merchandise remains with the buyer. It is the buyer's responsibility to file a claim with the carrier involved. RETURN SHIPPING For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy" and "Parts Return" pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root 2005. All rights reserved.

Table of Contents Table of Contents Introduction General...1 Related Manuals...1 Contractor Certification Requirements...1 Safety Precautions...1 Warnings and Important Notes...2 Installation Module/Connector Positions...3 Module Position...3 Connector Position...3 Module Installation...4 Relay Module Output Wiring Connections...4 Relay Module Relay Ratings...4 Four Relay Output Module Wiring...6 Input/Output Combination Module Wiring...7 Dispenser Controller Module Wiring...7 Figures Figure 1. Power Bay in TLS Console...3 Figure 2. CPU/ECPU board battery backup switch locations...5 Figure 3. Four Relay Output Module Wiring Diagram...6 Figure 4. Input/Output Combination Module Wiring Diagram...7 Figure 5. Dispenser Controller Module Wiring Diagram...8 i

ii Table of Contents

Introduction General This manual contains procedures for the installation or replacement of the following: Veeder-Root Four Relay Output Module (P/N 329359-00X) Veeder-Root Input/Output Combination Module (P/N 329360-00X) Veeder-Root Dispenser Controller Module (P/N 331408-00X) The above parts are for the TLS System designed and manufactured by Veeder-Root. This manual assumes all preliminary site preparation is completed, and that field wiring from the monitor to the sensor junction box is in place. If site preparation is necessary, refer to the TLS-3XX Site Preparation and Installation manual, or contact your Veeder-Root representative for assistance. Related Manuals 576013-879 TLS-3XX Site Prep and Installation Manual 576013-623 TLS-3XX System Setup Manual Contractor Certification Requirements Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual: Level 1 Contractors holding valid Level 1 Certification are approved to perform wiring and conduit routing, equipment mounting, probe and sensor installation, tank and line preparation, and line leak detector installation. Level 2/3 Contractors holding valid Level 2 or 3 Certifications are approved to perform installation checkout, startup, programming and operations training, troubleshooting and servicing for all Veeder-Root Tank Monitoring Systems, including Line Leak Detection and associated accessories. Warranty Registrations may only be submitted by selected distributors. Safety Precautions The following safety symbols are used throughout this manual to alert you to important safety hazards and precautions. EXPLOSIVE Fuels and their vapors are extremely explosive if ignited. FLAMMABLE Fuels and their vapors are extremely flammable. 1

Relay Module Installation Guide Warnings and Important Notes ELECTRICITY High voltage exists in, and is supplied to, the device. A potential shock hazard exists. OFF TURN POWER OFF Live power to a device creates a potential shock hazard. Turn Off power to the device and associated accessories when servicing the unit. WARNING Heed the adjacent instructions to avoid equipment damage or personal injury. READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important. Read and understand all manuals thoroughly. If you do not understand a procedure, ask someone who does. Warnings and Important Notes OFF WARNING You are working with a device in which potentially lethal voltages may be present. This product is to be installed in systems operating near locations where highly combustible fuels or vapors may be present. Fire or explosion resulting in serious injury or death could result if the equipment is improperly installed or modified. Serious contamination of the environment may also occur. 1. Read and follow all instructions in this manual, including all safety warnings. 2. Turn POWER OFF before installing theses modules. 3. Comply with all applicable codes including: the National Electrical Code; federal, state, and local codes; and other applicable safety codes. 4. Do not alter or modify any component or substitute components in this kit. 5. Do not use this component for other systems aside from the TLS Console. Install only as described in this manual or you will void all warranties connected with this product. 2

Installation Module/Connector Positions Figure 1 shows the Power Bay slots of the TLS Console in which Relay Modules are installed. Comm Bay Slot Numbers 1 2 3 4 Comm T1: PREMIUM UNLEADED Cage* VOLUME = 4208 GALS ULLAGE = 5792 GALS 90% ULLAGE = 4792 GALS TC VOLUME = 4194 GALS HEIGHT = 41.02 INCHES WATER VOL = 0 GALS WATER = 0.00 INCHES TEMP = 65.0 DEG F T1: REGULAR GASOLINE VOLUME = 9038 GALS ULLAGE = 962 GALS 90% ULLAGE = 0 GALS TC VOLUME = 8950 GALS HEIGHT = 81.37 INCHES WATER VOL = 28 GALS WATER = 1.37 INCHES TEMP = 74.9 DEG F 16 15 14 13 12 11 10 9 Power Bay Slot Numbers Power Bay Install Relay Modules in this bay! 8 7 6 5 4 3 2 1 Intrinsically Safe Bay Do not install Relay Modules in this bay! console\pwrbay.eps Figure 1. Power Bay in TLS Console MODULE POSITION Record on the circuit directory (on the inside front panel of the console) the type of module you are installing in this slot. Once a particular type of module has been installed in that slot, the system will always look for that type of module in that slot. CONNECTOR POSITION Identify all connectors according to their slot location using the self-adhesive numbering labels supplied with each module. Once a device has been wired to certain terminals on the connector and the system has been programmed, terminal position may not be changed without reprogramming the system. 3

Relay Module Installation Guide Module Installation Module Installation For additional information regarding the below steps, refer to the Veeder-Root TLS-3XX Site Preparation and Installation manual. Read and follow all instructions carefully. 1. Open the right-hand door of the TLS Console by unscrewing the right-top and right-bottom locking bolts. 2. To retain current programming, be sure that the CPU (for TLS-350) or ECPU (for TLS-350R) board battery switch is set to ON (see Figure 2). To avoid electrical shock or damage to components, if accessing the battery switch, avoid touching any circuit components with your hand or any conductive tool or jewelry. 3. Turn console POWER OFF before installing the module. 4. While working in the Power Bay of the console, avoid shorting high voltage across any component or module in the adjacent intrinsically safe bay of the console. This could result in an explosion near the sensor. 5. Remove a blank cover plate from any unused slot in the Power Bay compartment. 6. Slide the new Relay module into the empty slot until its rear board connector engages the connector in the console. Gently push in on the module until the connector is completely seated. Do not apply excessive force when installing the module. Push the two snap fasteners on the front panel of the module until they snap in. 7. Be sure all of remaining unused slots in the Power Bay have blank plates installed. If you are installing these modules in a system that has already been programmed, you CANNOT CHANGE the position of existing modules and/or connectors without reprogramming the entire system. If any connectors are removed during installation, BE SURE they are reconnected to their original modules. Relay Module Output Wiring Connections RELAY MODULE RELAY RATINGS Relay Module relay ratings are based on resistive loads: 4-Relay Output Module - four Form-C relays - 2 A maximum - 120/240 Vac or 24 Vdc Input/Output Combination Module - two Form-C relays - 2 A maximum - 120/240 Vac or 24 Vdc Dispenser Controller Module - four Form-A relays - 10 A maximum - 120/240 Vac 4

Relay Module Installation Guide Relay Module Output Wiring Connections CPU Board Battery Backup Switch (S1) Shown in ON position (up) S1 1 2 3 4 S2 BATT OPEN OPEN DIP switches (S2) ECPU Board DIP switches (S2) 1 2 3 4 Battery Backup Switch (S1) Shown in On position (up) OPEN SW2 SW1 consoles\ecpubbsw.eps Figure 2. CPU/ECPU board battery backup switch locations 5

Relay Module Installation Guide Relay Module Output Wiring Connections WARNING You are working with a device in which potentially lethal voltages may be present. If high voltage is shorted across any barrier terminal, explosion and fire could result. OFF Be sure AC POWER to the TLS Console is OFF before opening the front panel and installing or wiring any module. Be sure to record on the circuit directory the type of module and the name or location of each device wired to the connector. Once external devices have been connected and the system has been programmed, module, connector and wiring positions cannot be changed without re-programming the system. Improper system operation will result if any one of these positions are changed without re-programming. Refer to the appropriate module wiring diagram below and connect the wires (#14 AWG) from each external device to the appropriate terminals on the module connector. Module wiring is connected to devices located in the non-hazardous area and it must be in accordance with the National Electrical Code (NFPA 70) and the Automotive and Marine Service Station Code (NFPA 30A). FOUR RELAY OUTPUT MODULE WIRING RELAY 1 1 2 2 3 3 4 4 NC NO C NC NO C NC NO C NC NO C 4-RELAY OUTPUT MODULE RELAY RATINGS FORM C CONTACTS 120 VAC 2A MAX 24 VDC 2A MAX FUSE RATINGS 2A 250VAC TYPE T (SLO-BLO) Rigid Conduit (enters Console through a Power Bay knockout) Up to 4 external devices Console NC NO C NC NO C External Device External Device consoles\4r0mw.eps Figure 3. Four Relay Output Module Wiring Diagram 6

Relay Module Installation Guide Relay Module Output Wiring Connections INPUT/OUTPUT COMBINATION MODULE WIRING The TLS-350 and TLS-350R can accept a dry-contact switch closure input from an external device such as a line leak detector or well monitoring system. Each Input/Output Module accepts two external inputs. 1. For each external input, connect a shielded cable consisting of two 18 AWG conductors to the appropriate terminals on the I/O Module (see Figure 4). 2. Ground the cable shield to the ground terminal closest to the conduit entry. DO NOT ground both ends of the shield on the cable run. Not Used INPUT Attach Cable Shield to Ground Lug Closest to Conduit Entry 1 2 3 3 4 4 NC NO C NC NO C + + I/O COMBINATION MODULE RELAY RELAY RATINGS FORM C CONTACTS 120 VAC 2A MAX 24 VDC 2A MAX FUSE RATINGS 2A 250VAC TYPE T (SLO-BLO) Rigid Conduit (enters Console through a Power Bay knockout) Console Shielded Cables + + NC NO C NC NO C Input Input External Device External Device External Input Wiring #18 AWG Relay Output Wiring #14 AWG consoles\iocmw.eps DISPENSER CONTROLLER MODULE WIRING Figure 4. Input/Output Combination Module Wiring Diagram The TLS-350R Console may be used to interrupt the power supplied to individual dispensers. Each Dispenser Controller Module consists of four pairs of relay outputs (see Figure 5). To use the Dispenser Controller Module, each dispenser must draw less than 10 amperes of current. Connect only one dispenser circuit to a single pair of relay outputs: NO - Normally Open Contact C - Common side The relay contacts are not polarized. Each pair of output terminals is isolated from the other pairs and from ground. 7

Relay Module Installation Guide Relay Module Output Wiring Connections 1 Dispenser Circuit 1 Dispenser Circuit NO C NO C Rigid Conduit (enters Console through a Power Area knockout) Up to 4 dispenser circuits Console NOTE: only one dispenser circuit per pair of output terminals. Strip insulation 3/16" (4.7 mm) maximum. Ensure bare wire is completely in terminal to avoid shock. RELAY 1 2 3 4 NO C NO C NO C NO C DISPENSER CONTROLLER RELAY RATINGS NORM OPEN 10 AMP MAX 120 / 240 VAC FUSE RATINGS 10A 250VAC (SLO-BLO) consoles\dspcrmw.eps Figure 5. Dispenser Controller Module Wiring Diagram 8

Headquarters 125 Powder Forest Drive Simsbury, CT 06070-7684 Tel: (860) 651-2700 Fax: (860) 651-2719 Email: marketing@veeder.com www.veeder.com