Overview Signal converters Your process requires the utmost attention Our new signal conditioners support you in achieving this Many process parameters in your system are handled by your control system, which shows you the current status of your process. Even so, do you have a full overview of critical system states? And this at all times, at every location, and with the recent system history? D With the, you receive accurate information on the status of the sensors, signal processing and cabling. Data can be called up and will depending on your individual communications infrastructure. This comprehensive overview allows you to accurately analyse errors and faults, and initiate targeted actions taken by system operators and maintenance personnel. By doing so, this technology contributes to ensuring reliable system operation. D.4 1460730000 2014/2015
Overview signal conditioner with Ethernet interface Comprehensive process transparency is provided by the transfer of diagnostics information, signals and data Signal converters You would like more process transparency for your systems. We support you with signal conditioners that supply you with precise information via our Ethernet interace. Let s connect. To be able to control systems and processes optimally, you require a constant flow of information on the current states of individual applications, devices and functions. Our signal conditioner not only monitors the signal conversion, but also communicates precise information on device status, signals and data directly to connected computer and control systems. D Our Ethernet interface enables an event-controlled transfer of diagnostics information, which in turn supports the elimination of faults in, for example, plant operation. Universal signal conversion Can be used in a multitude of applications thanks to customer and application specific defined conversion methods with just one single module. Simple operation and configuration Software supported configuration allows a fast application of settings and simple operation. Simple remote access Continuous monitoring of device and system functions, simple and affordable integration of existing Ethernet networks. ETH I, U I, U PS 1460730000 2014/2015 D.5
Overview Signal converters Detailed analysis and presentation of core process parameters The supplies key parameters and historical data, independent of the location D Thanks to the, Weidmüller is now the first to offer a solution which supplies you with extensive diagnostic and status information without the need to deal with the complexity of field bus systems. The isolating converters are based on the proven, robust technology of transferring analogue signals to the DCS system. Various signal sources and field devices can be connected to the input side of the isolating converters. As a result of this, the can be configured for the user-defined processing of current, voltage and transmitter signals. Access is accomplished via a service interface on the front panel or via the Ethernet, and performance is ensured through the manufacturer-independent FDT/DTM software platform. To work with this platform, Weidmüller provides the WI-Manager universal FDT frame application. Data collected in the is made available over the Ethernet via Modbus TCP. Depending on the communications infrastructure, you can make this data available to your SCADA system within your network, and you can also access it via the Internet from any location using an industrial Ethernet router. D.6 1460730000 2014/2015
- Network-compatible signal converter Network-ready signal converter for DC voltage and current signals Network-compatible signal converter with Ethernet Scalable current or voltage input Current or voltage output Limit-value monitoring with parameterisation options Diagnostics on device status, signals and line faults via Modbus PC configuration with FDT/DTM software, download link at Weidmueller. -AI-AO-MTCP-S Signal converters Technical data Input Input current Input voltage Sensor supply Output Output current Output voltage Load impedance current Load impedance voltage Signal processing Transfer functions Limit-value monitoring Condition Monitoring Diagnostics General data Supply voltage Power consumption Accuracy Temperature coefficient Ambient temperature (operational) Storage temperature Humidity Protection degree Insulation coordination Galvanic isolation Rated voltage test voltage: inpututput to output/input supply Ethernet interface Rated voltage test voltage: Ethernet interface to supply functional earth to supply Ethernet interface Rated voltage test voltage: functional earth to input output U I I U I RJ45 11 51 ETH + 12 52 + V + I, U I, U + ma 13 53 Tx + 14 PS 54 63 64 + 24 V DC 0...20 ma, 4...20 ma 0(2) 10 V > 17 V DC at 20 ma 0...20 ma, 4...20 ma 0...10 V 500 Ω 10 kω Linear, Inverse Process alarms with adjustable delay and hysteresis Process value: sensor value, output value Device status, Short-circuit (input/output), Cable break (input/output), Overload (sensor/output) 24 V DC ± 25 % 3.5 W < 0.15% end value (+ 0.05% > 55 C), Current: 1 ua / 30 ua (+ 10 ua > 55 C), Voltage: 1 mv / 15 mv (+ 5 mv > 55 C) 0.01 % / C -20 C...+70 C -20 C...+85 C 0...95 % (no condensation) IP 20 4-way isolator;, between input / output / power supply / Ethernet 300 V rms / 1.7 kv rms on secondary electric circuits, reinforced insulation 31.2 VDC / 0.9 kv rms on secondary electric circuits, basic insulation 300 V rms / 1.1 kv rms on secondary electric circuits, basic insulation D Pollution degree Communication RJ45 ports Interface Addressing Protocol Configuration Approvals Standards Recommendations 2 10/100BaseT(X), auto negotiation RJ45: female-female, Cat.5 to 100 MHz, Jack plug for CBX200 DHCP or manual adjustment FDT/DTM, Modbus/TCP FDT/DTM (Ethernet or service interface) DIN EN 61010-1, EN 61326-1:2006 Namur NE43, Namur NE44, Namur NE107 Ordering data Type Qty. Order No. -AI-AO-MTCP 1 1334490000 Dimensions Clamping range (nominal / min. / max.) Depth x width x height / Weight Note mm² mm 2.5 / 0.5 / 2.5 113.6 / 22.5 / / 180 1460730000 2014/2015 D.7
-GTW-100-MTCP-S [!-] General ordering data Type -GTW-100-MTCP-S Order No. 1510370000 Version Gateway for station GTIN (EAN) 4050118319606 Qty. 1 pc(s).
-GTW-100-MTCP-S Technical data Dimensions and weights Width 22.5 mm Height 119.2 mm Depth 113.7 mm Net weight 150 g Temperatures Humidity 5...95 %, no condensation Operating temperature Ambient temperature -20 C...+60 C Storage temperature -40 C...85 C Probability of failure MTTF 160 Years communication Addressing Interface DHCP or manual adjustment Ethernet 10/100 Base T, Jack plug for CBX200, Communication via CH20M rail bus with all current measuring transducers (- CMT-x) Configuration RJ45 ports With FDT/DTM software 10/100BaseT(X), auto negotiation Input Type receives data via the CH20M rail bus from multiple -CMT communicative current measuring transducers Input Type receives data via the CH20M rail bus from multiple -CMT communicative current measuring transducers General data Configuration With FDT/DTM software Mounting rail TS 35 Power consumption, max. 2.2 W Supply voltage 16,8 V 31,2 V Insulation coordination Impulse withstand voltage 0,5 kv (1.2/50 μs) Pollution severity 2 Rated voltage test voltage: Ethernet Surge voltage category interface to supply functional earth to supply Ethernet interface 30 V AC RMS II Test voltage 1.1 kv
-GTW-100-MTCP-S Technical data Connection data Tightening torque, max. Wire connection cross section, finely stranded, max. 0.5 Nm 2.5 mm² Wire connection cross-section, finely stranded, min. 0.5 mm² Classifications ETIM 5.0 EC002048 ETIM 6.0 EC002048 eclass 6.2 27-21-09-02 eclass 7.1 27-21-09-02 eclass 8.1 27-21-09-02 eclass 9.0 27-21-09-02 Approvals ROHS Conform Downloads Manual Package insert Declaration of Conformity Manual Station- hardware + software german / english instruction sheet Declaration of Conformity.pdf
-GTW-100-MTCP-S Drawings dimensions releasable terminals with coding station with gateway and current converters
-GTW-100-MTCP-S Drawings connection plan
-CMT-10-AO-RC-S [!-] General ordering data Type -CMT-10-AO-RC-S Order No. 1510240000 Version Current-measuring transducer, communicative GTIN (EAN) 4050118319460 Qty. 1 pc(s).
-CMT-10-AO-RC-S Technical data Dimensions and weights Length 119.2 mm Width 22.5 mm Depth 113.6 mm Weight 180 g Net weight 154 g Temperatures Humidity 5...95 %, no condensation Operating temperature -25 C...60 C Storage temperature -40 C...85 C Probability of failure MTTF 130 Years communication Configuration With FDT/DTM software, via gateway (- GTW-100-MTCP-S), Addressing via DIP switches Interface Communication via CH20M rail bus with gateway (- GTW-100-MTCP-S) Input Input frequency AC: 15 700 Hz Input Input signal Input frequency Current-carrying cable in feed-through hole, Diameter 10.5 mm AC: 15 700 Hz Input measurement range 0 5/10 A AC (RMS) or DC General data Accuracy Configuration With FDT/DTM software, via gateway (- GTW-100-MTCP-S), Addressing via DIP < 0.5 % of end value switches Galvanic isolation 4-way isolator;, between input output supply Mounting rail relay TS 35 Power consumption, max. 2.2 W Step response time < 300 ms Supply voltage 16,8 V 31,2 V, via the Temperature coefficient system bus 200 ppm/k Insulation coordination EMC standards Galvanic isolation 4-way isolator;, between input output supply IEC 61326-1:2012 relay Impulse withstand voltage 6.4 kv (1.2/50 µs) Pollution severity 2 Rated voltage 300 V AC rms Surge voltage category III Test voltage 4 kv
-CMT-10-AO-RC-S Technical data Output (analogue) Load resistance current [output analogue] Output current [output analogue] Type (analogue output) Output (digital) 600 Ω adjustable, 0...20 ma, 4...20 ma, -20 +20 ma Voltage and current output (configurable) Load resistance voltage [output analogue] 10 kω Output voltage [output analogue] adjustable, 0(1)...5 V, 0(2)...10 V, -5 +5 V, -10... +10 V Type Rated switching current Relay, 1 CO contact, 2 obere und 2 untere Grenzwerte einstellbar, Open or closed-circuit principle, with alarm delay time (configurable) 0 s 2 s 5 s 10 s 6 A Max. switching voltage, AC 250 V Connection data Wire cross-section, solid, min. 0.5 mm² Wire cross-section, solid, max. 2.5 mm² Classifications ETIM 5.0 EC002048 ETIM 6.0 EC002048 eclass 6.2 27-21-09-02 eclass 7.1 27-21-09-02 eclass 8.1 27-21-09-02 eclass 9.0 27-21-09-02 Approvals ROHS Conform Downloads Manual Package insert Declaration of Conformity Manual Station- hardware + software german / english instruction sheet Declaration of Conformity.pdf
-CMT-10-AO-RC-S Drawings dimensions releasable terminals with coding DIP switch setting screenshot of parameter setting via FDT2
-CMT-10-AO-RC-S Drawings
-CMT-60-AO-RC-S [!-] General ordering data Type -CMT-60-AO-RC-S Order No. 1510420000 Version Current-measuring transducer, communicative GTIN (EAN) 4050118319613 Qty. 1 pc(s).
-CMT-60-AO-RC-S Technical data Dimensions and weights Length 119.2 mm Width 22.5 mm Depth 113.6 mm Weight 180 g Net weight 154 g Temperatures Humidity 5...95 %, no condensation Operating temperature -25 C...60 C Storage temperature -40 C...85 C Probability of failure MTTF 130 Years communication Configuration With FDT/DTM software, via gateway (- GTW-100-MTCP-S), Addressing via DIP switches Interface Communication via CH20M rail bus with gateway (- GTW-100-MTCP-S) Input Input frequency AC: 15 700 Hz Input Input signal Input frequency Current-carrying cable in feed-through hole, Diameter 10.5 mm AC: 15 700 Hz Input measurement range 0 40/50/60 A AC (RMS) or DC General data Accuracy Configuration With FDT/DTM software, via gateway (- GTW-100-MTCP-S), Addressing via DIP < 0.5 % of end value switches Galvanic isolation 4-way isolator;, between input output supply Mounting rail relay TS 35 Power consumption, max. 2.2 W Step response time < 300 ms Supply voltage 16,8 V 31,2 V, via the Temperature coefficient system bus 200 ppm/k Insulation coordination EMC standards Galvanic isolation 4-way isolator;, between input output supply IEC 61326-1:2012 relay Impulse withstand voltage 6.4 kv (1.2/50 µs) Pollution severity 2 Rated voltage 300 V AC rms Surge voltage category III Test voltage 4 kv
-CMT-60-AO-RC-S Technical data Output (analogue) Load resistance current [output analogue] Output current [output analogue] Type (analogue output) Output (digital) 600 Ω adjustable, 0...20 ma, 4...20 ma, -20 +20 ma Voltage and current output (configurable) Load resistance voltage [output analogue] 10 kω Output voltage [output analogue] adjustable, 0(1)...5 V, 0(2)...10 V, -5 +5 V, -10... +10 V Type Rated switching current Relay, 1 CO contact, 2 obere und 2 untere Grenzwerte einstellbar, Open or closed-circuit principle, with alarm delay time (configurable) 0 s 2 s 5 s 10 s 6 A Max. switching voltage, AC 250 V Connection data Wire cross-section, solid, min. 0.5 mm² Wire cross-section, solid, max. 2.5 mm² Classifications ETIM 5.0 EC002048 ETIM 6.0 EC002048 eclass 6.2 27-21-09-02 eclass 7.1 27-21-09-02 eclass 8.1 27-21-09-02 eclass 9.0 27-21-09-02 Approvals ROHS Conform Downloads Manual Package insert Declaration of Conformity Manual Station- hardware + software german / english instruction sheet Declaration of Conformity.pdf
-CMT-60-AO-RC-S Drawings dimensions releasable terminals with coding DIP switch setting screenshot of parameter setting via FDT2
-CMT-60-AO-RC-S Drawings
-LBT-10 [!-] General ordering data Type -LBT-10 Order No. 1510340000 Version Bus termination terminal GTIN (EAN) 4050118319491 Qty. 1 pc(s).
-LBT-10 Technical data Dimensions and weights Width 20.6 mm Height 56 mm Depth 63 mm Net weight 53.842 g Temperatures Humidity 5...95 %, no condensation Operating temperature Ambient temperature -25 C...+60 C Storage temperature -40 C...85 C Probability of failure MTTF 120 Years communication Configuration none General data Configuration none Mounting rail TS 35 Connection data Tightening torque, min. 1.2 Nm Tightening torque, max. 2.4 Nm Classifications ETIM 5.0 EC002048 ETIM 6.0 EC002048 eclass 6.2 27-21-09-02 eclass 7.1 27-21-09-02 eclass 8.1 27-21-09-02 eclass 9.0 27-21-09-02 Approvals ROHS Conform Downloads Manual Package insert Declaration of Conformity Manual Station- hardware + software german / english instruction sheet Declaration of Conformity.pdf