Global Plasma Solutions. 10 Mall Terrace, Bldg C Savannah, GA (912) ph (877) fax

Similar documents
1. Mount the echo and tremolo control switches under the keyboard shelf, in a position convenient for the organist.

Basketball Shot Clock Set LX2180 Manual

ETM-2040 Service Manual

ETM-2050/ETM-2051 Service Manual

AI-102. IR Illuminator. Installation Guide. Rev IP Surveillance

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

INSTRUCTIONS Operation/Maintenance

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide

TOXALERT MODEL AIR 2000

E1135C PDU and Pod Upgrade Procedure

Active UTP Transceiver Hub with Integral Camera Power Installation Guide

NO: PH-185 PRODUCT: E3JK Photoelectric Sensors DATE: May 2014 TYPE: Discontinuation Notice

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Active UTP Transceiver Hub with Integral Isolated Camera Power

CONSOLE CONNECTOR KIT 9501 INSTALLATION INSTRUCTIONS

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

T7560A1036 Digital Wall Module

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

MAXIMA + Series ROTARY LEVEL CONTROL

ADVANCED TECHNICAL MANUAL AAC1 SMALL SYSTEM CONTROL CONSOLE. Redefine your comfort zone.

Preparing for a Docking Drawer Slim Installation To prepare for a successful Docking Drawer Slim installation please ensure that the cable management

HydroGuard 4 to 20 ma Output Module. For use with HydroGuard Water Quality Monitor and Controller

Transceiver Hub with Integral Camera Power

Mini Photoelectric Sensor

USBCNC USB Disk Key reader for CNC Controls Machine Mount instructions

ZC-OH5 TAMPER-RESISTANT INDOOR/OUTDOOR HOUSING INSTRUCTION MANUAL FOR USE WITH GANZ ZC-D5000 SERIES MINIDOME CAMERAS

INSTALLATION INSTRUCTIONS Model 930 EntryCheck

ADDENDUM FOR 20, 27, & 28 OPTIONS

MAXIMA+ Series Rotary Level Indicator

Active UTP Transceiver Hub with Integral Camera Power Installation Guide

INSTALLATION, OPERATION & MAINTENANCE CRFF Series Wall Control Console. ECM Motors. ACC1-25 (Part # ) Revision:

Zone Pressure Touch Sensor - Standard Range

PN PSTK-120 PowerSwitch Tail 120vac Kit PN PSTK-240 PowerSwitch Tail 240vac Kit

MAXIMA + Series ROTARY LEVEL CONTROL

PhoneSaver USER MANUAL. Never lose a call! Never miss a message!

Treadmill Embedded Touch Screen Won t Power Up

Progressive Industries, Inc. EMS Electrical Management System

Active UTP Transceiver Hub with Integral Isolated Camera Power Installation Guide

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

A-dec 586 Ceiling Monitor Mount

MS-5000: MiniStar Reader

!There are two kit models. The ZCTK-120 is designed to operate with.!the pulse output is isolated from the mains line voltage. A pull-up resistor

AirTest Model CN9000 Series Sensor Controller

NPN output PNP output Cord connection Cord length: 2 m Through-beam 7 m Light-ON. 2 m. (selectable by wiring) Diffuse reflective 0.

MS-7000: SuperStar Reader

Principal LED Street Stik Fluorescent Bulb Replacements

USER GUIDE PARASYNC for ipod touch (5 th and 6 th generation) 30-unit Charging and Synchronization Dock

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

BL-FLOWSTN-P FlowStation Module Installation Guide

- ELV OVERVIEW. InstallationGuide SUPPLIED PARTS RELATED PARTS. Brackets Fixtures. Other. 1 of 9 IG-STR9-ELV

Quick Start Guide TS A

Power Supply (48Vdc, 2.5A)

PEREGRINE SERIES RETROFIT INSTALLATION GUIDE

CDD4 Duct Carbon Dioxide Transmitter

PowerPal Selectable Voltage 3-Amp Breadboard Power Supply (#32133)

Screw. Nut Guide. Features

ELECTRO-MECH SCOREBOARD CO.

Operating Instructions & Service Manual FOULS

ENCELIUM EXTEND Manager Wiring and installation manual Light is OSRAM

Connecting a Cisco Output Module

CAUTION READ CAREFULLY

CAUTION READ CAREFULLY

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

TRC-190 User s Manual

Inductive Proximity Sensor

ELECTRO-MECH SCOREBOARD CO.

How to hardwire the Olympus D-370 and D-380 Digital Cameras

Copy Machine Reader. Installation and Setup Guide

Cylindrical Proximity Sensor

7" Touch Screen Display

C5 Series Stainless Steel Photoelectric

Passive UTP Transceiver Hub with Integral Isolated Camera Power Installation Guide

Full HD Speed Dome IP Camera

Zero Volt Monitor Installation, Operation and Maintenance

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

CMSA-100 Manual. Cinema Media Server Automation

Manual Control Unit GFC 32

OPERATING INSTRUCTIONS AND SERVICE MANUAL BASKETBALL SHOTCLOCK MODEL MP-5299

TPE 1464 Series Pressure Transducer

INSTALLATION MANUAL. ST-BTWD650IR2812 B or W Weatherproof Day/Night Infrared Color Camera

Operation and Maintenance Manual

Thermometer / Barometer System

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Installation & Operation Guide

Zone Pressure Touch (ZPT) Sensor - Standard Range

INSTALLATION INSTRUCTIONS

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

Trouble Shooting Leveling Control Box Electric Jacks. Touch Pad LED Probable Cause Solution

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC.

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

PRO REMOTE 25 LV CAPACITANCE PROBE

User Manual VIDEO DOOR PHONE

XW3B. Connector Terminal Boxes. Ratings and Specifications. Compatible Connectors. Materials and Finish

B&W RearView Camera Installation & Operation

Connecting a Cisco Input Module

Encoder Firmware V User s Manual. Outdoor PTZ Camera Hardware Manual KCM /05/09.

TRC-190 User s Manual

SAVE THESE INSTRUCTIONS

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions

T7560A,B,C Digital Wall Module

Transcription:

10 Mall Terrace, Bldg C Savannah, GA 31406 (912) 356-0115 ph (877) 270-5353 fax GPS-RN IOM MANUAL

10 Mall Terrace, Bldg C Savannah, GA 31406 (912) 356-0115 ph (912) 356-0114 fax GPS-RN RTU/AHU INSTALLATION AND WIRING DIRECTIONS OA A B C GPS-RN units may be mounted on their side or with the needles facing up or down; whichever is more convenient for the mounting location selected. RA ROOFTOP INSTALLATION DIRECTIONS 1. Provide a bracket to hold the GPS-RN unit such that air flows across the needles simultaneously. See the example of two units below. 2. The preferred mounting location is "B". The second preferred location is "C" and the third preferred location is "A". Please note mounting in "A" the filter will stop the ions. 2 Unit Example 3' DC cable with 2.5mm plugs (Provided by GPS) Air Flow Bracket "By Others" 24-240VAC PLAN OR ELEVATION VIEW UNIT WIRING INSTRUCTIONS 1. Mount the GPS-RN unit to a bracket, provided by others. 2. The GPS-UP12-RN power supply can accecpt 24VAC to 240VAC input. 3. Secure the power supply in the RTU/AHU control panel or junction box, provided by others. 4. Plenum rated DC power cables will be provided by Global Plasma Solutions with each system. 5. The power supply will be provided with a 3' long cable. The wires colors are: Green/Yellow = Ground BROWN = AC INPUT BLUE = AC INPUT 6. Connect the 2.5mm DC power plug into the first GPS-RN unit as shown. 7. If the system contains more than one GPS-RN unit, 3' DC power cables will be provided with 2.5mm plugs on both ends. Simply plug the cable into the jacks as shown in the above samples. 8. All DC power jacks on the GPS-RN units are wired in parallel internally so there are no in/out requirements. UNIT DIMENSIONS IN INCHES

GPS-RN RTU/AHU INSTALLATION AND WIRING DIRECTIONS Air Flow Bracket "By Others" 4 Unit Example 24VAC to 240VAC Input 3' DC cable with 2.5mm plugs (Provided by GPS) PLAN OR ELEVATION VIEW GPS-RN units may be mounted on their side or with the needles facing up or down; whichever is more convenient for the mounting location selected. IMPORTANT NOTES: The GPS-UP12-RN power supply can power up to two GPS-RN units. GPS-UP12-RN Power Supply Specifications: Voltage: 24VAC to 240VAC Power: 12VA Output: 12VDC at 1A Power Input Connection: 3' Plenum Rated Cable with ground and AC input Power Output Connection: 2.5mm DC Power Jack = center Pin +12V Size: 3.5"L x 3.5"W x 1.25"H Indication: Integral Green LED Power Indicator Wire Colors: Green/Yellow = Ground, Blue = AC Input, Brown=AC Input

GPS-RN DUCT INSTALLATION AND WIRING DIRECTIONS 1. Locate position on duct such that air flows across the ion needles simultaneously. Refer to examples shown for proper unit orientation. 2. Drill (2) TWO 1/2" holes 1.6" apart, center to center. 3. Push wire through extensions and hand tighten to threaded nipple. 4. Insert ion needles through holes and secure the GPS-RN unit to the duct using the two stainless steel tabs and sheet metal screws. 5. Mount the power supply near the GPS-RN. 6. Insert the 2.5mm DC plug into one of the power jacks on the GPS-RN unit. If two GPS-RN units are required per duct, a double end cable with 2.5mm plugs on both ends will be provided by GPS. See the power drawing below as an example. Note: Mounting the GPS-RN unit before the filter will prevent the ions from traveling further down the duct. It is recommended to mount the product after the filter. Model: GPS-UP12-RN Ion Output "On" Indicator Lamp 24VAC to 240VAC Input Wire Nuts Required 90VAC to 266VAC Input (Wall Plug) 3' DC power cord with (2) 2.5mm plugs Up to 2 total per GPS-UPW12 Power cord provided by GPS power supply* NOTE: Only one power supply will be provided per AHU/duct. Options are shown for illustration purposes. * Power supplies shown can only power up to two GPS-RN units.

GPS-RN BAS INTERFACE Wiring By Others TO BAS Wiring By Others TO BAS Local Ion Output "On" Indication Lamp 1. When the ion output lamp is "ON", the dry contact is closed allowing the building automation system (BAS) to know that there are no alarms. 2. Each GPS-RN can be wired for individual BAS control or wired in series as shown in the above example so if one unit fails, an alarm is initiated. NOTE: Dry contact rated for low voltage AC and DC only! Maximum of 1 AMP. Illuminated ON/OFF switch

OPERATION / TROUBLESHOOTING BAS Dry Contacts Ion Output LED 12VDC Power Jack 12VDC Power Jack Illuminated On/Off Switch Standard Operation 1. Provide 12VDC power to either power jack. The center pin requires the 12V+ and the outer pin requires the negative connection. 2. Up to two units may be powered in series using 2.5mm DC power cables provided by GPS. 3. The BAS Dry Contacts may be wired in series with no limit to the number of units that can be used. 4. Once 12VDC power is applied, turn the On/Off switch to the "On" position. The On/Off switch will now illuminate. 5. Once the On/Off switch is turned to the "On" position, upon no faults, the ion output LED will illuminate. 6. When the ion output LED is illuminated, the BAS dry contact will closed. Troubleshooting 1. Confirm 12VDC is being supplied to the power jack. The center pin requires the 12V+ and the outer pin requires the negative connection. 2. Confirm only up to two units are being powered in series using 2.5mm DC power cables provided by GPS. 3. Confirm the On/Off Switch is in the "On" position and illuminated. 4. If On/Off switch is "On" and illuminated, 12VDC jack has power and polarity is correct, but the ion LED light is off, the unit must be returned to the factory and a replacement provided. 5. If the ion output LED is on, the BAS dry contacts will be closed. If the ion output LED is off, the BAS dry contacts will be open. 6. Please note that the ion output LED and BAS dry contacts are linked directly to the output side of the ion circuit. If the ion output LED is on and/or the BAS dry contact is closed, there will be voltage output to the ion needles. 7. If all components are functioning properly, but the ion count at the supply diffuser is less than 1,000 ions/cm, use a cotton ball with rubbing alcohol and wipe off the ion needles. Needle oxidation may have occurred, resulting in ion output reduction. CAUTION 1. NEVER TOUCH ION NEEDLES WHILE OPERATING. SHOCK MAY OCCUR. 2. GPS-RN SHOULD NEVER BE CONNECTED WITH AN EXTENSION CORD. 3. DO NOT CONNECT POWER BEFORE INSTALLATION IS COMPLETE. ALWAYS DISCONNECT POWER TO THE UNIT BEFORE HANLDING ANY OF THE UNIT COMPONENTS OR SERVICING. 4. THIS PRODUCT SHALL NOT BE INSTALLED BEHIND A SUSPENDED FLOOR/CEILING, OR A STRUCTURAL WALL, CEILING OR FLOOR. 5. THIS PRODUCT IS SUITABLE FOR MOUNTING INTO A DUCT OF METALLIC CONSTRUCTION ONLY. 6. PRODUCT SHOULD BE MOUNTED SUCH THAT THE POWER SUPPLIES CAN BE POWERED WITHOUT THE USE OF AN EXTENSION CORD. FOLLOW ALL LOCAL AND NATIONAL ELECTRIC CODES WHEN WIRING.