Installing the Tracer MP503 Input/Output Module Ordering number: ,

Similar documents
Temperature. Power requirements. Weight. Dimensions

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

Installation and Operation Tracer. MP503 Input/Output Module CNT-SVX09A-E4

Tracer Controllers. Tracer MP503 Input/Output Module BAS-PRC009-EN. January 2005

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

Tracer Controllers. Tracer MP503 Input/Output Module BAS-PRC009-EN. September 2001

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

PanelView Plus/VersaView CE Terminals and Display Modules

Installation Instructions

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

MAXIMA+ Series Rotary Level Indicator

TM3TI8T module TM3-8 inputs temperature

PowerLogic High Density Metering System 1-Meter Enclosure

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

MAXIMA + Series ROTARY LEVEL CONTROL

TM3AI4 module TM3-4 analog inputs

TM7BDM16A expansion block - TM7 - IP67-16 DI/DO - 24V DC A - M12 connector

TM7BDI16B. Main. Enclosure material. Input/output number 16 Input/output number of splitter box

TM3TM3 module TM3-2 temperature inputs and 1 analog output

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

FP-PS-4. Features. Installation

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

TM3TI4 module TM3-4 inputs temperature

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

PanelView 600 Terminals

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

MicroTech II TM Remote I/O Panel Installation Manual

CompactBlock Guard I/O EtherNet/IP Safety Modules

ArmorPoint I/O Field Potential Distributor, Series A

TM7BDM8B. Main. Enclosure material. Input/output number 8 Input/output number of splitter box

Enclosed Power Supplies

NI 6521 Specifications

LN Series Remote Input/Output (I/O) Modules

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100hp)

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

TM3DI16 module TM3-16 inputs

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

FX Input/Output (I/O) Modules XM07 and XM14

ACCESS 9340/9360 Meter Input/Output Module

TRC-190 User s Manual

Installation Instructions for UL Rev A

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

em4 Accessories Digital expansions

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

FLEX Ex Spring Clamp Terminal Base

TM3TI4 module TM3-4 inputs temperature

BCM2 Series Branch Circuit Monitors Quick Setup Guide

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

TAC Xenta 301. Controller, Freely Programmable

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

CMSA-100 Manual. Cinema Media Server Automation

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS

SCADAPack E 5405 Digital Input Hardware Manual

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

High Performance Output Filter Instruction Manual

Avanti HP Series Centrifuges Preinstallation

TruPortal Dual Door Interface Module Quick Reference

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

LTEC Heat Pump DDC Controller

VersaView Industrial Non-display Computers

MicroTech II Remote I/O Panel Installation Manual

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

S66 Series Electronic Fan Speed Control

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Line Impedance Stabilization Network (LISN)

RM35TF V AC

LX Series Remote Input/Output (I/O) Controller

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

ORB TM 4-20 ma Input Box Installation & Operation Manual

Operating instructions. Switching amplifier DN0210 DN / / 2015

Satellite INSTALLATION GUIDE

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

NI PXI-1042 Series Power Supply Shuttle

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

SCC-RLY01 Relay Module

Transcription:

Installing the Tracer MP503 Input/Output Module Ordering number: 4950 0490, 4950 0590 Product overview The Tracer MP503 input/output (I/O) module is a field-installed device used to monitor inputs and control binary outputs. The I/O module has four universal inputs that can be configured as binary, thermistor, 0 20 ma, or 0 10 Vdc. It also has four binary outputs. The Tracer MP503 is available in two different versions: frame-mount (4950 0490) and metal enclosure (4950 0590) (see Figure 1 and Figure 2 on page 2). The frame-mount package contains: A Tracer MP503 circuit board fastened to a metal back plate A removable molded resin cover The metal-enclosure package contains: A Tracer MP503 circuit board fastened to the back plate of the metal enclosure A removable metal cover Shipment Visually inspect all parts for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred in shipping should be filed with the carrier. Storage environment The storage environment must meet the following requirements: Temperature: -40 F to 185 F (-40 C to 85 C) Relative humidity: 5 95%, noncondensing Operating environment Make sure that the operating environment conforms to the specifications listed in Table 1. Dimensions and clearances are illustrated in Figure 1 and Figure 2 on page 2. Table 1. Operating environment specifications Temperature Humidity Power Mounting weight (framemount) Mounting weight (metal enclosure) Altitude Installation Category 3 Pollution Degree 2 Location From -40 F to 158 F (-40 C to 70 C) 5 95%, noncondensing 20 30 Vac (24 Vac nominal), 50 60 Hz 10 VA per I/O module plus a maximum of 12 VA per binary output used Mounting surface must be able to support 4 lb (2 kg) Mounting surface must be able to support 16 lb (7.5 kg) 6,500 ft (2,000 m) maximum Trane recommends locating the Tracer MP503 I/O module: In an indoor environment for protection from the elements Where public access is restricted to minimize the possibility of tampering or vandalism Near the controlled equipment to reduce wiring costs Where it is easily accessible for service personnel Trane A Business of American Standard Companies www.trane.com 2004 American Standard Inc. All rights reserved. 3270 3332 C

Figure 1. Dimensions and clearances for the frame-mount I/O module 6.313 in. (160 mm) 2 in. (51 mm) 4 in. (102 mm) 4 in. (102 mm) 1 2 3 4 AC POWER BINARY OUTPUTS STATUS 4 in. (102 mm) 5.375 in. (137 mm) 6.875 in. (175 mm) DC OUT UNIVERSAL INPUTS PIN SERVICE 1 2 3 4 A B A B 5.625 in. (143 mm) Clearances Dimensions Figure 2. Dimensions and clearances for the metal-enclosure version I/O module 1.875 in. (48 mm) 6.5 in. (165 mm) 2 in. (51mm) 9 in. (229 mm) 2 in. (51 mm) 7 in. (178 mm) 9 in. (229 mm) 24 in. (610 mm) 10.37 in. (263 mm) width with cover 2.25 in. (58 mm) 10.25 in. (260 mm) width without cover Clearances Dimensions 3270 3332 C 2

Mounting the frame-mount I/O module IMPORTANT Mount the Tracer MP503 with the cover on to avoid damaging the circuit board during installation. To mount the frame-mount I/O module: 1. Using the module as a template, mark the location of the two mounting holes on the mounting surface (Figure 3). 2. Set the module aside and drill holes for the screws at the marked locations. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 3. Insert wall anchors if needed. 4. Secure the module to the mounting surface with #10 (5 mm) screws (not included). Attach the frame-mount module securely so that it can withstand the vibrations of associated heating, ventilating, and air-conditioning (HVAC) equipment. Mounting the metal-enclosure I/O module To mount the metal-enclosure I/O module: 1. Remove the two cover screws and then the cover. 2. Using the enclosure as a template, mark the location of the four mounting holes on the mounting surface (Figure 4). 3. Set the enclosure aside and drill holes for the screws at the marked locations. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 4. Insert wall anchors if needed. 5. Secure the enclosure to the mounting surface with #10 (5 mm) screws (not included). Figure 4. Mounting the metal-enclosure Tracer MP503 Figure 3. Mounting the Tracer MP503 Agency listings/compliance CE marked UL and C-UL listed: Energy Management Equipment PAZX (UL 916) UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Subpart B, Class B 3 3270 3332 C

AC-power wiring See Figure 5 or Figure 6 for the location of the ACpower connections. IMPORTANT Make sure that the 24 Vac power supplies are consistently grounded. Do not share 24 Vac between I/O modules. The recommended wire for AC-power is 16 AWG copper wire. All wiring must comply with National Electrical Code and local codes. Use a UL-listed Class 2 power transformer supplying a nominal 24 Vac (20 30 Vac). The transformer must be sized to provide adequate power to the Tracer MP503 (10 VA) and outputs (a maximum of 12 VA per binary output). WARNING Hazardous voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. CAUTION Personal injury and equipment damage! After installation, make sure that the 24 Vac transformer is grounded through the board. Failure to do so may result in personal injury and/or damage to equipment. CAUTION Equipment damage! Complete input/output wiring before applying power to the controller. Failure to do so may cause damage to the controller or power transformer due to inadvertent connections to power circuits. CAUTION Equipment damage! Do not share 24 Vac between controllers. Sharing 24 Vac power may cause controller damage. Wiring AC-power to the frame-mount I/O module Please read the preceding warning and cautions. To connect AC-power to the frame-mount I/O module: 1. Connect one secondary wire from the 24 Vac transformer to the terminal shown in Figure 5. 2. Connect the other secondary wire to the terminal. Figure 5. AC-power wiring for frame-mount 24 Vac transformer AC POWER 1 Wiring AC-power to the metal-enclosure I/O module Please read the preceding warnings and cautions. To connect AC-power wiring to the enclosure: 1. Remove the cover of the enclosure. 2. Remove the knockout for the 0.5 in. (13 mm) conduit from the enclosure and attach the conduit. 3. Feed the power wire into the enclosure. 4. When mounting on dry wall or other nonconductive surface, connect an earth ground to the earth-ground stud on the enclosure (Figure 6). 5. Connect one secondary wire from the 24 Vac transformer to the terminal. 6. Connect the other secondary wire to the terminal. 7. Replace the cover of the enclosure. BIN 3270 3332 C 4

4 Figure 6. AC-power wiring for metal enclosure Communication-link wiring The Tracer MP503 communicates with the building automation system (BAS) and with other controllers by means of a LonTalk (formerly called Comm5) communication link. For instructions on LonTalk communication wiring and addressing, follow the Tracer Summit Hardware and Software Installation guide (BMTW-SVN01E), the Tracker Building Automation System Hardware Installation guide (BMTK-SVN01D), or another BAS installation manual. Input/output terminal wiring All input/output terminal wiring for the Tracer MP503 must meet the following requirements: All wiring must be in accordance with the National Electrical Code and local codes. Use only 18 22 AWG, stranded, tinned-copper, shielded, twisted-pair wire. Binary output wiring must not exceed 1000 ft (300 m). Binary input and 4 20 ma input wiring must not exceed 1000 ft (300 m). Thermistor input and 0 10 Vdc input wiring must not exceed 300 ft (100 m). Do not run input/output wires in the same wire bundle with any AC-power wires. The Tracer MP503 has four binary outputs and four universal inputs. Earth-ground stud 24 Vdc outputs The Tracer MP503 provides power for ma and Vdc sensors. The DC OUT outputs are currentlimited to 80mA (see Figure 7 on page 6). If sensors draw more than 80mA, the output of the circuit drops from to 0V. Periodically, the circuit is turned On to test the current draw and if the draw is less than 80mA, the DC OUT output returns to dc. Binary outputs The binary outputs are form A (SPST) relay outputs. These relays are not dry contacts; they switch 24 Vac. A pilot relay is required for any application requiring dry contacts. Relays connected to the binary outputs on the I/O module (see Figure 7 on page 6) cannot exceed 12 VA or 0.5 A current draw at 24 Vac. Universal inputs Each of the four universal inputs may be configured as: Binary Thermistor 0 20 ma 0 10 Vdc You can configure each input using the device plugin and a service tool, such as the Rover service tool. The inputs are software configurable only; there are no jumpers to set on the circuit board. The inputs are factory-configured to be thermistors. Figure 7 on page 6 shows some common sensor types wired to the Tracer MP503. 5 3270 3332 C

Figure 7. Input/output terminal wiring diagram for the Tracer MP503 1 2 3 4 AC POWER BINARY OUTPUTS STATUS PIN SERVICE DC OUT 1 UNIVERSAL INPUTS 2 3 4 A B A B Typical 2-wire 4 20 ma sensor + Not used Typical thermistor sensor Typical binary switching device In Out LonTalk communication link + Typical 3-wire 0 10 Vdc sensor The following are trademarks or registered trademarks of American Standard Inc.: Rover, Tracer, Tracer Summit, Tracker. The following are trademarks or registered trademarks of their respective companies or organizations: LonTalk from Echelon; National Electrical Code from National Fire Protection Association. 3270 3332 C 6

Declaration of Conformity Manufacturer s Name: Trane Manufacturer s Address: 4833 White Bear Parkway St. Paul MN 55110 USA The manufacturer hereby declares that the product Product Name: Tracer MP503 Model Number: MP503 (4950 0490 and 4950 0590) Conforms to the following standards or other normative documents: Electromagnetic Emission: (by Council Directive 89/336/EEC) EN50081-1:1992, EN50090-2-2:1996, and EN61326-1:1997 Radiated EN55022:1994 Class A limit: 4950 0590 Class B limit: 4950 0490 Conducted EN55022:1994 Class B limit Electromagnetic Immunity: (by Council Directive 89/336/EEC) EN50082-2:1995, EN50090-2-2:1996, and EN61326-1:1997 IEC 1000-4-2:1995 ±4.0 kv by Contact EN61000-4-2 IEC 1000-4-3:1995 EN61000-4-3:1996 Amendment A1:1998 IEC 1000-4-4:1995 EN61000-4-4 10.0 V/m 80 to 1000 MHz ±2.0 kv Signal Lines ±2.0 kv AC Power Lines IEC 1000-4-5:1995 EN61000-4-5 IEC 1000-4-6:1996 EN61000-4-6 IEC 1000-4-8:1993 EN61000-4-8 10 V 0.15 to 80 MHz 30 A/m IEC 1000-4-11:1994 EN61000-4-11 When and Where Issued Electromagnetic Emission 05/09/2001 Electromagnetic Immunity 07/06/2001 Craig Kasl Design/Compliance Engineer Mark of Compliance European Contact Societe Trane (Epinal, France) 1, rue des Ameriques, B.P. 6 F-88191 Golbey Cedex, France Phone: (33) 329.31.73.00 Fax: (33) 329.81.24.98 This document validates CE conformity of the Tracer MP503 controller. 7 3270 3332 C