BACnet Protocol Implementation Conformance Statement Date: December 1 st, 2015 Vendor Name: Danfoss A/S Product Name: VLT HVAC Drive FC-102 Product Model Number: FC-102 Applications Software Version: 1.6 Firmware Revision: 1.6 BACnet Protocol Revision: 14 Product Description: The VLT HVAC Drive unleashes the full potential of HVAC. Built on Danfoss modular plugand-play platform and dedicated to HVAC applications, the VLT HVAC Drive makes HVAC setup and operation very easy. Danfoss unequalled experience in advanced drive technologies for HVAC application provides optimized features in the VLT HVAC Drive and makes it the perfect match for pumps, fans and water chillers (compressors) in buildings fitted with sophisticated HVAC solutions. BACnet Standardized Device Profile (Annex L): BACnet Operator Workstation (B-OWS) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA) List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B DS-WP-B DM-DDB-B DM-DOB-B DM-DCC-B DM-TS-B DM-RD-B Segmentation Capability: Segmented requests supported Segmented responses supported Window Size Window Size Standard Types Supported: Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Device Multi-state Output instantiation is static. Refer to tables at end of this document for object details.
Data Link Layer Options: BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) MS/TP master (Clause 9), baud rate(s): 9600; 19200; 38400; 76800 MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: Other: Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No Networking Options: Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ISO 10646 IBM /Microsoft DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226 If this product is a communication gateway, describe the types of non-bacnet equipment/networks(s) that the gateway supports:
Device Binary Input Binary Output Binary Value Analog Input Analog Output Analog Value Multistage Value Identifier x x Type x x System Status Vendor Name Vendor Identifier Model Name Firmware Revision App Software Revision Location Description Protocol Version Protocol Revision Services Supported List Max APDU Length Segmentation Support Local Time Local Date APDU Timeout Number APDU Retries Max Masters Max Info Frames Device Address Binding Database Revision Present Value Status Flags Event State Reliability Out-of-Service Number of States State text Units Priority Array * * * Relinquish Default * * * Polarity Active Text Inactive Text *For commandable values only
Analog Inputs AI:0 Analog Input 53 AI:1 Analog Input 54 AI:2 Analog In 30/11 AI:3 Analog In 30/12 / If MCB101 installed If MCB101 installed Analog Outputs AO:0 Terminal 42 Output Bus Control AO:1 Pulse out #27 Bus Control / Commandable Commandable AO:2 Pulse out #29 Bus Control AO:3 Terminal 30/8 Output Bus Control Commandable If MCB101 installed Analog Values / AV:1 Input Reference 1 Commandable AV:2 Input Reference 2 Commandable AV:3 Output Speed AV:4 P Feedback AV:5 Motor Current AV:6 Power AV:15 Motor Thermal AV:21 Operating Hours AV:22 Running Hours AV:23 kwh Counter AV:24 Motor Voltage AV:25 Frequency AV:26 Torque AV:27 DC Link Voltage AV:28 Heatsink Temp. AV:29 Inverter Thermal AV:30 Setpoint 1 AV:31 Bus Feedback 1 AV:35 Setpoint 2 AV:36 Bus Feedback 2 AV:40 Setpoint 3 AV:41 Bus Feedback 3 AV:50 Last Alarm AV:51 Fault Code AV:52 P Start Speed BACnet embedded object list for Danfoss FC102 Drive Page 4 of 6
AV:53 On Reference Bandwidth AV:54 P Proportional Gain AV:55 P Integral Time AV:56 P Differentiation Time AV:57 P Diff. Gain Limit AV:58 Sensorless out AV:61 Alarm Word AV:62 Alarm Word 2 AV:65 External Reference AV:66 Warning Word AV:67 Warning Word 2 / Binary Inputs Id BI:0 Digital input Term 33 BI:1 Digital input Term 32 BI:2 Digital input Term 29 BI:3 Digital input Term 27 BI:4 Digital input Term 19 BI:5 Digital input Term 18 BI:6 Digital input Term 37 BI:7 Digital input GPIO Term 30/2 BI:8 Digital input GPIO Term 30/3 BI:9 Digital input GPIO Term 30/4 / If MCB101 installed If MCB101 installed If MCB101 installed Binary Outputs Id / BO:0 Digital Output Term 27 Commandable BO:1 Digital Output Term 29 Commandable BO:2 GPIO Output Term 30/6 If MCB101 installed BO:3 GPIO Output Term 30/7 If MCB101 installed BO:4 Relay 1 Commandable BO:5 Relay 2 Commandable BACnet embedded object list for Danfoss FC102 Drive Page 5 of 6
Binary Values BV:1 RUN/STOP Command BV:2 REF 1/REF 2 Select BV:3 Fault Reset Command BV:4 RUN / STOP Monitor BV:5 OK / FAULT Monitor BV:6 HAND / AUTO Reference BV:21 Warning BV:22 Trip BV:23 Triplock BV:24 Coasting BV:25 CW/CCW BV:26 Jog BV:27 Reset BV:28 Reset kwh Counter BV:29 Reset Running Hours Counter BV:30 RevStatus BV:31 Speed = reference BV:32 Bus Control BV:33 Running BV:34 Ramp 1/Ramp 2 / Commandable Commandable Commandable Commandable Commandable Commandable Commandable Multistate Value Id MSV:0 Smart Logic Controller State MSV:1 Active Setup / W BACnet embedded object list for Danfoss FC102 Drive Page 6 of 6