Installation and commissioning guide SmartLink Host Communication Module (HCM-GPU)

Similar documents
Installation and commissioning guide SmartLink PSD Power Supply Module (DC)

SmartLink Configuration Manual

Engauge Quick Start Guide

Instruction manual XPU-2 option RS-232C / RS-485

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

FLEX Ex Spring Clamp Terminal Base

Channel Switch CS. General Operating, Maintenance and Installation Manual

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

R507 I.S. Interface Module User Manual

EasySync Ltd. ES-R-2x01-M RS232 to RS422 / RS485 Converter. User Guide. Document Reference No.: ES_ Version draft Issue Date:

Hardware Manual RM CANview

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Modbus TCP/RTU Gateway

Serial PROFIBUS Interface

CPCI-PS24 24V-Power Supply

Extension module for BACnet over Ethernet / IP and graphic Web functions

Manual Industry Interfaces

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

Instruction manual CIU Prime type 880 (CIU858 emulation)

HEC. General Operating, Maintenance and Installation Manual

ICF-1150 Series Quick Installation Guide

ABB Drives. User s Manual. Digital I/O Extension Module RDIO-01

ICF-1150 Series Quick Installation Guide

Manual Fiber Optic Interfaces

Serial/Ethernet Converter

MGate MB3170/MB3270 Quick Installation Guide

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration

GT- IRDM-9603 Product description Rev. 2 17/06/2014

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

Operating instructions. Speed monitor D / / 2014

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

MT8050iE series. Installation Instruction (1) (2)

EX-RC1 Remote I/O Adapter

Bluetooth to RS-232&RS422/485. EX-9132B/BI Bluetooth Adapter Operation Manual

Installation guide Ensite Pro Configuration Tool

SPECIFICATIONS AND FEATURES GUIDE NI Serial Legacy Hardware

SoundwebTM. Installation Guide

General Operating, Maintenance and Installation Manual

Note: For BANDIT II, BANDIT III, or VSR-1200 specifications, see the BANDIT II, BANDIT III, and VSR-1200 Document Set. Function

CAN Repeater CAN-CR200, CAN-CR220, CAN-CR210/FO

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter

PHOENIX CONTACT - 12/2007

solartron digital readout model no. DR600 DR700 installation manual

Installation- and Operating instructions for CU Ethernet Controller with USB Input. Version: 1.4 Date:

ABB Drives. User s Manual Modbus Adapter Module FMBA-01

PI-EX-ME-2NAM/COC-24VDC

Extension module for lighting control

Zener Barriers Bulletin 937Z

MGate 4101-MB-PBS Series

RS-232 Industrial Media Converter

Operating instructions. Switching amplifier DN0210 DN / / 2015

OPERATOR MANUAL OSD136 SYNCHRONOUS FIBER OPTIC RS232 MODEM

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

Language of the manual

RS-232 to RS-422/485 Converter with 3KV Isolation Protection

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9871E

Operating instructions. Standstill monitor A / / 2011

Priva Blue ID Communication module RS232 SC22

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

IDS-141A/181A. Industrial 4-port/8-port slim type serial to Ethernet device server. Features. Introduction. DS-Tool

Extension module for graphic Web functions for one automation station

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

GT- HE910-EUD. Product description Rev. 8 21/02/ Overview

RTU560 Connections and Settings DIN Rail RTU 560CIG10

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

Product description The SWH is a board Cellular Terminal solution for GSM GPS/GLONASS

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Moxa TCC-100 Series Hardware Installation Guide

PI-EX-ME-2NAM/COC-120VAC

CAN Repeater CAN-CR200, CAN-CR220, CAN-CR210/FO USER MANUAL ENGLISH

FX-485PC-IF RS485 Interface Unit Hardware Manual

CMU 100 RS485 to Ethernet Converter User Manual CMU 100 / CMU 100 / 1.M.9 CMU 100 / 1.L.9 CMU 100 / CMU 100 / 7.M.9 CMU 100 / 7.L.

Extension module for Web functions generic

F1000 User's Manual. (Version: V1.01)

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

ADA User manual ADA RS-485 / RS-422 to RS-232 Converter. 1 io_ada-4010_v3.22_en. Copyright CEL-MAR sp.j.

MGate 5111 Quick Installation Guide

Enclosure TS-530 User Manual

DT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions

Data Sheet SRM-6A. Short-Range Asynchronous Modem. The Access Company

RS-485 Fiber-Optic Link RS-485 to Multi-Mode Fiber-Optic converter ST Fiber Connectors DIN Rail Mount

ExBin-D Transducers for ExPro-B... sensors (probes) ExPro-B... Thermostats / humidistats ( C, % rh)

AC Power Meter GPM-8212 USER MANUAL

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

DIN Rail Mounted Dial-up Modem Users Manual


CMU 100 RS232 to Singlemode Fiber Optic Converter User Manual

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Intelligent 4 Port RS-422/485 to 2 Port Ethernet Serial Device Server with PoE

Siemens Spares. Preface 1. Scope of Delivery 2 SIPLUS CMS4000. Product Characteristics 3 ION PROFIBUS DP SPY T001 Installation and Maintenance 4

Power Supply HARTING pcon

Installation Instructions for UL Rev A

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Expansion Module HZS 541-1S

Transcription:

Installation and commissioning guide SmartLink Host Communication Module (HCM-GPU) Rev. 2 September 2012 Part No. 4417552 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywell.com Website : http://www.honeywell.com SmartLink HCM-GPU Page 1

Copyright 2012 Enraf BV All rights reserved. Reproduction in any form without the prior consent of Enraf BV is not allowed. This manual is for information only. The contents, descriptions and specifications are subject to change without notice. Enraf BV accepts no responsibility for any errors that may appear in this manual. The warranty terms and conditions applicable in the country of purchase in respect to Enraf BV products are available from your supplier. Please retain them with your proof of purchase. Page 2 SmartLink HCM-GPU

1 Preface This manual describes the installation and commissioning procedure of the SmartLink Host Communication Module (HCM-GPU). It contains all the necessary information for installation, commissioning and maintenance of this product. Refer to the Instruction manual SmartLink configuration, Part No. 4417554 for a comprehensive description of all settings and details. Safety and prevention of damage Always adhere to the instructions in this manual. In case of doubt, or problems, always consult your Enraf representative. Refer to the front cover for contact information. Additional information Please do not hesitate to contact Enraf or its representative if you require additional information. Declaration of conformity This device fulfills the requirements of the following directives EMC directive 89/336EEC Legal aspects The information in this manual is copyright property of Enraf BV, Netherlands. Enraf BV disclaims any responsibility for personal injury or damage to equipment caused by: Deviation from any of the prescribed procedures; Execution of activities that are not clearly documented. SmartLink HCM-GPU Page 3

Table of contents 1 Preface... 3 2 Introduction... 5 2.1 The SmartLink modular concept 5 2.2 Preparation before installation 5 2.3 Identification.. 5 2.4 Functional description. 6 3 Safety... 7 3.1 EMC 7 3.2 Special conditions for use... 8 4 Mechanical specifications... 9 4.1Dimensions. 9 4.2 Weight 9 4.3 Climatic Conditions.. 9 5 Mechanical installation... 10 5.1 Installation of the DIN-rail.. 10 5.1.1 Using the DIN-rail connectors 10 5.1.2 Clicking the connector onto the rail.. 10 5.1.3 Compiling a SmartLink system.. 10 5.2 Mounting the SmartLink module.. 12 5.3 Dismounting the SmartLink module 13 6 Electrical specifications... 14 6.1 Electrical characteristics. 14 6.1.1 Isolated RS232 cable specifications. 14 6.1.2 RS485 cable specifications 15 6.1.3 RS232 non-isolated. 15 6.1.4 RS422 non-isolated. 15 6.1.5 Electrical installation 15 6.2 Connecting the HCM-GPU module.. 16 7 Disposal... 19 8 Maintenance... 19 Page 4 SmartLink HCM-GPU

2 Introduction 2.1 The SmartLink modular concept The 780 SmartLink provides a gateway to terminal automation related field instrumentation. With the modular design of the SmartLink this bridge concept is scalable from small to medium tank terminal installations. The SmartLink modular concepts consist of separate modules on a DIN-rail. Available modules include: PSA (Power Supply AC), PSD (Power Supply DC), HCM (Host Communication Module) for communication with the PC, and FCM (Field Communication module) for communication with the field instruments. 2.2 Preparation before installation Visually check the product for damage. Contact your Enraf representative in case of damage. Check the delivery for completeness. The HCM-GPU is packed in an ESD safe bag. The package should contain: - the SmartLink Host Communication Module - 2 DIN-rail connectors Immediately contact your Enraf representative if the delivery is incomplete. 2.3 Identification The SmartLink module is equipped with a label on the right side (front of the unit toward viewer) of the casing. The label is shown below. The following label is attached to the HCM-GPU SmartLink module: SmartLink HCM-GPU Page 5

Figure 1 SmartLink HCM-GPU label The following label is attached to the connector: Figure 2 HCM-GPU connector layout 2.4 Functional description The SmartLink HCM-GPU is a plug-and-play communication module for communication beween the PC and the field instruments that are connected to the Field Communication Modules (FCM s). The power supply is realized through a SmartLink PSA (AC) or PSD (DC) power supply unit. The interface with the PC is realized via RS232 (isolated or non-isolated), nonisolated RS422 or isolated RS485. The HCM-GPU communicates with the FCM(s) via the bus-system. As a result a host system like e.g. Entis XS, can communicate with level gauges via this HCM-GPU module and the FCM(s). Default the interface is set to RS232. The default baudrate is 38400 bits/sec. Please consult the separate software configuration manual if another setting is required. Page 6 SmartLink HCM-GPU

3 Safety Applied (safety, approval) standards This module must only be installed by sufficiently trained and experienced personnel, taking into account the relevant company, local and national regulations. 3.1 EMC The HCM-GPU module complies with the EMC specifications according to the following standards: Type Item Standard Specific level/criteria Emission General emission EN-IEC61000-6-4: Immunity General immunity EN-IEC61000-6-2 Ensure that the module is installed by sufficiently trained personnel, aware of the EMC aspects. SmartLink HCM-GPU Page 7

3.2 Special conditions for use When using the HCM-GPU in a SmartLink system, the following integration requirements must be met: The HCM-GPU enables the galvanic isolation between the RS232 or an RS485 line and the bus side, however the isolation is not certified in the context of ATEX. Integration in a system requiring prolongation of Ex barriers requires special attention. The shield of each field cable is connected to the system enclosure. The circuit GND or GND-ISO is a cable wire, not the cable shield. Special shielding requirements may be valid depending on the system (e.g. junction boxes with C s for connecting shield to earth). The HCM-GPU may be placed in hazardous zone 1 only within a Ex [d] certified enclosure, operating temperature as specified by section 4.3. The system in which the HCM-GPU module is integrated must maintain the isolation between the bus and the isolated RS232 and RS485 side of the module. The clearance to other isolated circuitry must be according to EN61010-1: 3[mm] (Double insulation, measurement category II, mains voltage >150 300V). The circuit GND of CN1 must be externally connected to earth. To activate the protective earth (CN3) for isolated RS232 and RS485, the resistor R47 (0E) should not be placed. Page 8 SmartLink HCM-GPU

4 Mechanical specifications 4.1 Dimensions Figure 3 Dimensions SmartLink module A = 114 mm (4.49 ) B = 117 mm (4.61 ) The width is 45 mm (1.77 ) Note: Take into account that an additional space of appr. 35 mm is required above a SmartLink module for mounting / dismounting purposes. (Refer to section 5.3). 4.2 Weight The HCM-GPU module weighs 194 grams. 4.3 Climatic Conditions The SmartLink HCM-GPU complies with the environmental conditions as defined in the table below. Operating temperature -20 o C to +60 o C (-4 o F to +140 o F) Storage temperature -40 o C to +85 o C (-40 o F to +185 o F) Protection class (SmartLink) IP 20 (EN 60529:2000, NEMA) Relative humidity 20-95%, non condensing SmartLink HCM-GPU Page 9

5 Mechanical installation 5.1 Installation of the DIN-rail 5.1.1 Using the DIN-rail connectors The SmartLink HCM-GPU module can only be installed onto the connector supplied with the delivery. Do not use any other connectors. 5.1.2 Clicking the connector onto the rail Click the connector onto the rail. Take into account that any additional modules should be added to the right hand side of this module, so click the connector onto the DIN-rail as far left as possible and convenient. Also click the connectors of any additional SmartLink modules that are also to be installed onto the DIN-rail and make sure they are properly linked together. Figure 4 Connectors on DIN-rail 5.1.3 Compiling a SmartLink system As mentioned in section 2.1, the SmartLink system consists of a power supply module (PSA or PSD), a HCM and 1-3 FCM s. The modules are added from left to right in the sequence as indicated in the figure below. Page 10 SmartLink HCM-GPU

Always place a termination clip at the far right hand side, i.e. to the right hand side of the rightmost FCM. Without this termination the SmartLink system will not work properly. Also refer to the relevant manuals. Figure 5 SmartLink modules on DIN-rail From left to right: 1 The power supply unit 2 The host module (HCM) 3 Field communication module(s) (FCM) 4 Termination clip (also shown in picture below) SmartLink HCM-GPU Page 11

Figure 6 Termination NOTE! Always adhere to this sequence. Ensure the Termination clip is in place, otherwise the system will not operate. 5.2 Mounting the SmartLink module The HCM is always positioned immediately right of the power supply module. To the right of the HCM one or more FCM s are installed. Hold the module upright, place the base on the connector that is fitted onto the DIN-rail. Ensure that the notch marked 1 is engaged first and click the module onto the DIN-rail with the tilting movement as indicated by arrow 2 (refer to figures 7 and 8). Page 12 SmartLink HCM-GPU

Figure 7 Side view of module Figure 8 Clicking the module onto the connector on the DIN-rail 5.3 Dismounting the SmartLink module Figure 9 Removing the module from the DIN-rail A module that is mounted on the DIN-rail can be removed by placing a blade screwdriver under the notch (refer to the figure) and making a slight upward leveraging movement, lifting the module of the rail at the same time. Do NOT use excessive force. SmartLink HCM-GPU Page 13

6 Electrical specifications 6.1 Electrical characteristics Item Conditions Min Typ. Max Unit Power Consumption - 1.8 - W +5V ISO I Viso Galvanic separation ESD protection isolated RS232 ESD protection isolated RS485 ESD protection Nonisolated RS232 and RS485 Isolated 5V supply output on CN2 Isolated 5V supply max current Between RS232/RS485 isolated and other circuitry 4.9 5.00 5.1 V - - 15 ma - 2500 - V MAX3221E - - ±15 kv SN65HVD3082 - - ±15 kv LTC1334 - - ±10 kv 6.1.1 Isolated RS232 cable specifications Item Type Length (max) Number of instruments (max) Shielded 15 m (50 ft) 2; point to point Page 14 SmartLink HCM-GPU

6.1.2 RS485 cable specifications Item Type Twisted pair + signal ground C max 119 pf/m L max 1.45 mh R max 0.12 Ω per line Length (max) 1000 m (3280 ft) Number of instruments (max) 10 6.1.3 RS232 non-isolated Item Type Length (max) Number of instruments (max) Shielded 15 m (50 ft) 2; point to point 6.1.4 RS422 non-isolated Item Type C max L max R max Length (max) Twisted pair + signal ground 119 pf/m 1.45 mh 0.12 Ω per line 1000 m (3280 ft) 6.1.5 Electrical installation Warning Do not connect anything else to the DIN-rail connectors but the SmartLink modules. Ensure the power supply is switched off or disconnected, and secured against switching on again, before commencing the installation. SmartLink HCM-GPU Page 15

Ensure that the local power supply voltage matches the voltage stated on the module. In order to ensure a safe operation of the module, it should only be connected to a mains supply that is fused with a maximum value of 16A. Safety depends on the correct earthing of the instrument. Therefore check the resistance of the earth connection immediately after installation; the maximum resistance should correspond with the local earth resistance requirements. The module is equipped with an internal fuse, which may only be replaced by the manufacturer. 6.2 Connecting the HCM-GPU module First ensure that the module has been properly mounted onto the rail as defined in section 5.2. The HCM-GPU module is supplied with 15 Vdc power via the bus. Default the communication between the HCM-GPU and the PC, for configuration, and for retrieving and sending data to the connected field instruments when FCM modules are connected, takes place via the RS232 cable which is connected to the SUB-D connector on the front of the HCM module. Figure 10 HCM with RS232 connector on front Page 16 SmartLink HCM-GPU

Table 1 Pinning CN2 (Isolated RS232) Pin No. Signal 1 232RxD 2 232TxD 3 +5V_CN2 4 GND_ISO Table 2 Pinning CN3 (Isolated RS485) Pin No. Signal 5 485A 6 485B 7 Shield 8 GND_ISO Table 3 Pinning CN5 (Non-isolated RS232 with flow control or RS422) Pin No. RS232 signals RS422 signals 1 DCD 2 RxD RxD 3 TxD TxD 4 DTR 5 GND GND 6 DSR 7 RTS TX+ 8 CTS RX+ 9 n.c. Chassis Shield Shield The pinning chosen is for DTE equipment (data terminal equipment), so that a 1 to 1 cable can be used for a modem connection (DCE). Connection to a PC takes place via a cross cable. SmartLink HCM-GPU Page 17

6.3 Removing the connection Use the reverse of the above described procedure in order to disconnect the module. 6.4 Configuration The HCM-GPU should be configured by Engauge service tool running on a PC. Only a SmartLink delivered before September 2007 should be configured by the SmartLink configuration tool running on a PC. Refer to the separate Instruction Manual SmartLink configuration, Part No. 4417554. 6.5 Default settings Default the HCM-GPU is set to communicate via the RS-232 port with a baudrate of 38400 bits/sec. Changing these and other settings is only possible by Engauge (or Smartlink configuration tool) running on a PC. 6.6 LED Besides the standard led, the module has following optical indicators and corresponding functionality: (Note for pcb silkscreen the LE1 text is repeated from [1].) Table 4 LED s LED text Color ID Function RdY Blue LE1 Alive / error indication TxD Amber LE2 Follows Tx on active RS line RxD Amber LE3 Follows Rx on active RS line Page 18 SmartLink HCM-GPU

7 Disposal The SmartLink module contains electronic components and should therefore, when defect or no longer used, be disposed of as electronic equipment according to the local regulations for this type of waste. 8 Maintenance The SmartLink module does not require any specific maintenance. Simply keep the module clean and remove dust when it accumulates. SmartLink HCM-GPU Page 19

Delftechpark 39 2628 XJ Delft Tel. :+31 15 2701 100 E-mail : enraf-nl@honeywell.com Website: http://www.honeywellenraf.com PO Box 812 2600 AV Delft The Netherlands We at Honeywell Enraf are committed to excellence. Information in this publication is subject to change without notice Enraf is a registered trade mark. Enraf B.V. Netherlands Page 20 SmartLink HCM-GPU