Andover ContinuumTM Infinet II

Similar documents
Andover ContinuumTM. b3850 Series Terminal Controllers

Andover ContinuumTM Infinet II

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM Infinet II

BACnet. b3810 Series Local Controllers

BACnet. b3867 Terminal Controllers

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM Infinet II

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

Andover Continuum. Power Supplies with or without UPS

Andover ContinuumTM. Family of Controllers. BACnetTM

ACX Series. Access Controller for Ethernet

lighting control. Each controller switches up to 48 high voltage, 20-amp lighting circuits, using

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed

Specification Sheet For electronically commutated motors

Andover ContinuumTM. Family of Security Products

TAC I/NETTM 1284, 1280, Security Control Unit

Andover Continuum. Family of Security Products

Installation Instructions for UL Rev A

clarity 3 Programmable Controller

FX06 Field Controller

LX Series Free Programmable Controllers

FX Input/Output (I/O) Modules XM07 and XM14

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

TALON Network Manager- 2 & 6 Express

SE7600E Series Application Guide

AIR HANDLING UNIT CONTROLS

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

Siemens BACnet Programmable TEC Unit Conditioner Controller

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

clarity 3 VAV Programmable Controller

Quick Start Installation Guide

TAC Xenta 121-FC Programmable Fan Coil Application

XT-9100 Technical Bulletin

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

Room Controllers. SC3000 Relay Pack

SEZ7000 Series. Wireless Commercial Zoning System

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

Smart Equipment Controls (SEC)

ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers

TAC Xenta 121-HP Programmable Heat Pump Application

Datasheet. ECB-600 and ECx-400 Series. ECB-600 & ECx-400. Overview. Applications. Features & Benefits.

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

PXC Modular Series. Features. Description. Technical Specification Sheet Document No Rev. 1.1, May 2007

mxcontrol Multifunction Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

TC-9102 Terminal Controller

FCU-MULTI Modbus Fan Coil Unit Controller

TAC Xenta 301. Controller, Freely Programmable

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

DS Type: MAXIM III Controller

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Unit Vent Controller

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

Medium User Interface (MUI) Version 3

DX-9100 Digital Controller, Version 2

Measure & Control Temperature & CO2 levels with analog & digital I/O

FCU-4 FAN COIL CONTROLLER

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Web server. Simplified.

DS October MAXIM 1010 Controller

Neon pr. ph/ ORP measurement. Applications. Description

HLS34 Modbus FCU/VAV Controllers installation instructions

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

RTD-W Installation Instructions

PXC Modular Series. Features. Description. Technical Specification Sheet Document No July 24, 2012

GreenEye Monitor Specifications

ECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Fast Route to Reliable Energy Savings ZIP Economizer

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

Satchwell MicroNet. Building Management System MicroNet 50 Series

Input/Output Module (IOM) Series Catalog Page

Power Panel Integrated control, operation and visualization

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

SmartStruxure SmartStruxure Lite ZENO InnPoint. ZENOcontrols.com. compatible with

THERMOSTATS & CONTROLLERS

SE7600E Series Application Guide

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

APS SCALE SERIES DIMENSIONS

Digital Indicator Solutions

Level instruments. Continuous level measurement - Ultrasonic controllers SITRANS LUC500. 5/146 Siemens FI

TC Modular Series for BACnet Networks

ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

VZ7000 Series. BACnet Commercial Zoning System

Field selectable application type and room module series, via dip-switches on controller

Non-communicating room controllers

Transcription:

Andover ContinuumTM Infinet II i2850 Series The i2850, i2851, and i2853 controllers provide cost-effective DDC control of individual terminal units (e.g. VAV boxes, fan-powered induction units, unit ventilators, heat pumps).

02 Features The i2850 Series is a perfect fit for your VAV applications where external damper actuators are used. And because all i2850 Series controllers feature a built-in expansion port for additional I/O, these controllers are perfect for your more demanding control applications. Choose the i2850 Series controller with the input confi guration that matches your application: PRODUCT AT A GLANCE Compact Provide VAV Control for a Broad Range of Applications Compatible with Both Andover Continuum and Infinity Systems Expandable I/O Meets Additional Point Count Needs Universal Inputs with Form A and Form K Outputs for Flexible Control Options Non-Volatile Flash Memory Provides Utmost Reliability Stores Both Application Program and Operating System Flash Memory Allows Easy On-Line Software Updates On-Board Airflow Sensor Optional Display/Keypad Provides Easy Operator Interface (Mounted Separately) View and Modify Information with Optional Andover Continuum Smart Sensor Display Local On-Board Service Port The i2850 has four full range universal inputs plus a fi fth input for an on-board air fl ow sensor for VAV airfl ow measurement. The i2851 contains four universal inputs as well, but does not have the on-board air fl ow sensor and is perfect for applications not requiring airfl ow measurement, such as heat pumps and fan coils. The i2853 is for dual-duct VAV applications. It contains two onboard airfl ow sensors and four universal inputs. All three models feature an additional room sensor input, which supports Andover Continuum Smart Sensor, or any standard room temperature sensor; plus three Form A relays and one Form K Tri-state relay output. Similar to all i2 controllers, the i2850 Series features Flash memory, increased user memory, and a fast (32-bit) processor for faster scan times, with plenty of additional memory available for data logging of your critical data. The i2850 Series communicates with the entire Andover Continuum Infi net RS-485 fi eld bus (i.e. both Andover Continuum Infi net and Andover Continuum Infi net II controllers) and is compatible with both the Andover Continuum CyberStation and Infi nity SX 8000 front-ends. Up to 254 Andover Continuum Infi net devices can be networked to any Andover Continuum network controller.

03 Features (continued) Increased Reliability with Flash Memory The i2850 s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application will be restored when power is returned. In addition, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out proms. The i2850 controllers include an on-board battery to safeguard your runtime data protecting all point data and log data from being lost if power is removed. Inputs The input configuration on the i2850 Series consists of four full range universal inputs that accept voltage (0-5VDC), digital (on/off), counter signals (up to 4Hz), or temperature signals. The i2850 features one on-board air flow sensor; the i2853 provides two. All models offer an additional input to support the Andover Continuum Smart Sensor, or any standard room temperature sensor. Outputs The i2850 Series contains three Form A relay outputs and one Form K Tri-state output. Each relay is rated for 24 VAC/VDC, 3 amp. These outputs can be used separately for on/off or pulsed control of lighting, heat, and fan units. The preconfigured Form K Tri-state output can be used for bi-directional control of dampers and valves. Dimensional Drawings 1 2 4 3 (Note: Any two consecutive Form A outputs can be configured to form an additional Form K output.) I/O Expansion The i2850 Series contains an I/O expansion port for the addition of up to two xp expansion modules directly on the bottom of the controller. The i2 family of modules includes the xpdi8, xpui4, xpdo2, xpdo4, xpao2, and xpao4. In addition, the I/O bus supports the xp Display Module, which allows the user to view and change point values.

04 Features (continued) Software Capabilities The dynamic memory of the i2850 Series can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Continuum Plain English TM programming language. Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the i2850 Series using the Andover Continuum CyberStation, Infinity SX 8000 Workstation, or local user terminal. Programs are then stored in, and executed by, the i2850 Series controllers. Programming multiple i2850 Series controllers is inherently easy with Plain English. A complete copy of one i2850 controller s programs can be loaded directly into other i2850 controllers without changing any point names or programs. Dimensional Drawings 1 Power Drawing 2 Communication Drawing Smart Sensor Interface The i2850 Series provides a built-in connection for Andover Continuum Smart Sensor. The Smart Sensor provides a 2-character LED display and a 6-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a 4-digit custom LCD that provides the following icons: PM, %,, Setpoint, Cool, Heat, CFM, Fan, OA, and SP. Local Display The local display with keypad (xp-display) allows for the addition of a fully programmable local display module that can be mounted within 10 feet (3 meters) of the controller. Connected via a ribbon cable, the xp-display easily allows the Operator Interface to be mounted on the door of an enclosure or on a wall below or next to the controller. 3 Smart Sensor and 4 Inputs Drawing Outputs Drawing Optional Wireless Andover Continuum Infinet The i2850 Series Andover Continuum Infinet controllers can also communicate using a wireless mesh network. Simply plug Andover Continuum Wireless Adapters into the service ports of these controllers with wireless compatible firmware to create a wireless mesh network that sends and receives Andover Continuum Infinet messages.

05 Specifications 05 i2850 Series Electrical Power 24 VAC, +10% -15%, 50/60 Hz Power Consumption 20 VA Overload Protection Fused with 2 amp fuse. MOV protected. Software Real-Time Clock Synchronized through Andover Continuum Infinet by network controller Mechanical Operating Environment 32 120 F (0 49 C), 10 95% RH (non-condensing) Size 5.47 H x 8.16 W x 2.44 D (139H x 207W x 62) mm Weight 1.08 lbs. (.50 kg) Enclosure Type UL Open class, IP 10. Flammability rating of UL94-5V Mounting Panel mount Battery Battery Backup Replaceable, non-rechargeable, lithium battery. Provides 5 years typical accumulated power failure backup of RAM memory Communications Communications Interface Through Andover Continuum Infinet RS-485 field bus to network controller Communications Speed 1200 to 19.2K baud Bus Length 4,000 ft. (1,220m) standard for Andover Continuum Infinet, i2 Infilink module allows extension to longer distances and is required after every group of 32 units on the network. Bus Media Andover Continuum Infinet: twisted, shielded pair, low capacitance cable RS-485 port for implementing Wireless Infinet II connection, including: Standard service port, four-position shrouded connector Comm. Error Checking International Standard CRC 16 Compatibility Andover Continuum Cyberstation and Infinity SX 8000 systems Inputs 4 Universal inputs: Voltage (0-5.115 VDC); Temperature -30 F to 230 F (-34 C to 110 C), Digital (on/off), Counter (up to 4Hz at 50% duty cycle, 125 ms min. pulse width). Supervised Alarm (single or double resistor). Current input (0-20 ma) using external 250 ohm resistor 1 Smart Sensor Temperature Input (32 F to 105 F) (0 C to 41 C) Airflow sensor (0 to 2 W.C.) (i2850- qty 1; i2853-qty 2) Input Voltage Range 0-5.115 volts DC Input Impedance 10K ohm to 5.120V or 5M ohm with pull-up resistor disabled Input Protection 24 VAC or 24 VDC temporarily on any single channel, ±1000V transients (Tested according to EN61000-4-4) Input Resolution 5.0 mv Input Accuracy ±15mV (±0.56 C from -23 C to +66 C or ±1 F from -10 F to +150 F) Airflow Input Range: 0 to 2 W.C. (0-500 Pa) Resolution: 0.005 W.C. (1.25 Pa) @ 23 C (73 F) Accuracy: ±0.05 W.C. (6.25 Pa) @23 C (73 F)

06 Specifications (continued) i2850 Series Outputs 3 single pole single throw (SPST) Form A relays 1 Form K Tri-state relay output (Any two consecutive Form A outputs can be configured as one Form K Tri-state) Output Rating Maximum 3A, 24VAC/VDC, ±1500V transients (Tested according to EN61000-4-4) Output Accuracy 0.1 sec. for pulse width modulation Expansion Bus Interfaces to optional xp I/O Expansion Modules Connections Power 3-position fixed screw terminal connector Inputs 6-position fixed screw terminal connector Outputs 9-position fixed screw terminal connector Smart Sensor 3-position fixed screw terminal connector Communications 3-position removable screw terminal connector Expansion Port 6-position shrouded connector Service Port 4-position shrouded connector User LEDs/Switches Status Indicator LEDs: CPU CPU Active TD Transmit Data RD Receive Data Output Output Status (per output) (Digital only) EXPANSION PORT PWR Power Status Switches RESET Input Pull-up Resistor Switch (per input) General Memory 128K SRAM, 1MB FLASH Processor Motorola 32-bit Coldfire Agency Listings UL/CUL 916, FCC CFR 47 Part 15, ICES-003, EN55022, AS/NZS 3548, Class A, CE Options UL864, Smoke Control System Equipment, UUKL (i2850-s, i2851-s, i2853-s) Models i2850 Infinet II i2850 Terminal Controller i2850-s Infinet II i2850 Terminal Controller with Smoke-Control option i2850-wl Wireless Infinet II i2850 Terminal Controller i2851 Infinet II i2851 Terminal Controller i2851-s Infinet II i2851 Terminal Controller with Smoke-Control option i2851-wl Wireless Infinet II i2851 Terminal Controller i2853 Infinet II i2853 Terminal Controller i2853-s Infinet II i2853 Terminal Controller with Smoke-Control option i2853-wl Wireless Infinet II i2853 Terminal Controller All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. 2007-2009 Schneider Electric. All rights reserved. November 2007 pdw