Elastimold Molded Vacuum Recloser - MVR

Similar documents
SERIES SD3800 / SD3810 SPECIFICATION

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

Vacuum-Break Switches

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

Solid Dielectric Switchgear

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

OSM PRODUCT GUIDE. OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models

Products Portfolio. Pole mounted Vacuum Recloser

Single Phase Vacuum Capacitor Switch. UltraVacLT 15kV 95kV or 125kV BIL

SmartClose 3-phase, Synchronous Close Vacuum Capacitor Switch

Diamondback. Solid Dielectric Load Break Switch Catalog. Distributed By;

Medium Voltage Metal-Enclosed Power Capacitor Banks

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN

NU-LEC. Loop Automation. Reclosers & Sectionalizers

Performance. Reliability. Simplicity. A smarter grid requires an intelligent recloser.

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv)

Underground Distribution Switchgear

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions.

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Descriptive bulletin. OVR outdoor vacuum reclosers kv Innovative designs ensure system reliability

Solid Dielectric Switchgear Catalog S-trid13

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

2.1 The NOVA-TS Triple-Single Recloser and Form 6-TS control shall be designed in accordance with the following standards as applicable:

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

Lightweight and flexible recloser control for single-phase applications

WiAutoLink Frequently Asked Questions

Specif ications. S&C Remote Supervisory Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions

Instrument Current Transformers

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

Annexure-1 (CC no )

E-Series General Specifications

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

SECTION SWITCHBOARDS

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Series 100. Mechanical Switches Contents. Series 100 Multiple Position Switches

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

S Sectionalizers

ASCO 920 Remote Control (RC) Switches

SECTION DISCONNECT SWITCHES

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

LineScope. Smart Power Monitor. Bulletin DB50C18. US Patent Nos , , and B2

920 Remote Control (RC) Switches

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

Instruction manual. Type SDR 15.5 kv to 27 kv single-phase distribution recloser. Answers for infrastructure.

SECTION PANELBOARDS

FT Flexitest Family. Switches, Covers and Test Plugs

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches

GridShield outdoor vacuum reclosers kv Making distribution networks more reliable

POLE MOUNTED Load Break Switch

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

Elastimold Switchgear Configurator Instruction Manual

I-Line Panelboards. Innovative design, smart bus technology, and simple installation

Magnetic and Hydraulic-Magnetic Circuit Breaker

VisoVac padmount fault interrupter

1. Coordination of series-rated devices is permitted where indicated on Drawings.

Introduction Circuit Protection

SPECIAL SPECIFICATION 6274 Microwave Vehicle Detection System

CITY OF BOISE SPECIFICATIONS FOR LIGHT EMITTING DIODE (LED) STREET LIGHTING Effective 1 Feb, 2018

600-Amp Elbow Connectors 600 Series Deadbreak Components

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

CERTIFIED TEST REPORT

COOPER POWER. UltraSIL polymer-housed VariSTAR IEEE surge arresters; normal-duty (5 ka), heavyduty, and riser pole (10 ka) for MV systems to 36 kv

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

Reclosers. Functional Specification Guide PS280026EN. Form 6 Rack/Yard-Mount Recloser Control

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks

Autodaptive Capacitor Control M 2501B

Power Control Systems

MATERIAIS PARA REDES APARELHAGEM AT E MT

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W)

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Effective May 2018 Supersedes October 2017

SECTION MEDIUM-VOLTAGE CIRCUIT BREAKER SWITCHGEAR (GAS-INSULATED, VACUUM)

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

PDI Modular Compact Remote Power Panel

Specifications. S&C Line-Rupters. For Line and Cable Switching. Outdoor Transmission (115 kv through 230 kv) Conditions of Sale

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

VariSTAR AZE Station Surge Arresters

Type SDR 15.5 kv to 38.0 kv distribution vacuum three-phase recloser instruction manual

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

Square D Meter Centers. A Comprehensive. Selection. Time-Saving, Reliable. Solutions

File Ref: CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT. Cooper Power Systems. 28 kv Class 600 Amp 16.2 / 28.

Transcription:

Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical requirements for Three and single phase molded vacuum reclosers and controls for use on standard distribution class of voltages. 2.0 STANDARDS Elastimold Molded Vacuum Reclosers (MVR) comply with the applicable provisions of the latest NEMA, IEEE, ANSI/IEEE, and IEC standards relating to Reclosers. The applicable standards include, but are not limited to, the following: 2.1 ANSI/IEEE C37.60-2003 American National Standards Requirements for Overhead, pad-mounted, dry vault, and submersible automatic circuit reclosers and fault interrupters for alternating current systems up to 38 kv 2.2 IEC 62217 - Salt Spray Test 2.3 Thomas & Betts /Elastimold manufacturing facilities are ISO 9001:2008 certified. 3.0 FUNCTIONAL FEATURES The Elastimold Molded Vacuum Reclosers (MVR) are designed to automatically interrupt and reclose either all three phase or a single phase of an alternating-current circuit. The Elastimold MVR has a programmable electronic control that allows the operating characteristics to be changed without de-energizing the recloser. The Elastimold MVR is utilized to improve system coordination, reduce momentary outages, improve reliability and simultaneously isolate permanent faults. 4.0 PRODUCT FEATURES AND ACCESSORIES 4.1 Construction & Operation

File: MVR-RS-0412 Page: 2 of 6 The Elastimold MVR three-phase units are electrically ganged which allows the recloser to perform, through a control selection option, either simultaneous three phase trip or single phase trip operations and selection of three phase or single phase lockout.. The manual trip handle is mechanically linked to trip and lockout all three phases simultaneously. The provided manual-tripping lever does not require external power for operation. The manual tripping lever is suitable for operation with a hot line stick in accordance with IEEE C37.60. The tripping lever is yellow in color. Lever status can be displayed on the control LED panel and also provided remotely via SCADA when used with SEL651R and 351RS Kestrel controls. 4.2 Mechanism 4.2.1 The mechanism uses three magnetic actuators (one for single phase units) capable of fast opening and closing operations with no recharging delay. 4.2.2 The recloser utilizes a modular design concept that has identical interrupter housings integrated into a common housing for three phase units. 4.2.3 The highly visible position indicator utilizes a viewing window that can be seen from any position 360 around the recloser. 4.2.4 Elastimold MVR does not require any special tools or measurement for routine inspection and maintenance. 4.2.5 The mechanism housing is sealed and manufactured from durable cast aluminum 4.3 Solid Dielectric Module 4.3.1 The Elastimold MVR solid polymer module is highly resistant to ozone, tracking, and ultraviolet rays. The insulating material is constructed of a highly damage resistant EPDM rubber. The bushings sheds are made of silicone rubber and are high resistant to impact, ozone tracking, and damage from UV light.

File: MVR-RS-0412 Page: 3 of 6 4.4 Vacuum Interrupters 4.4.1 Current interruption occurs in vacuum interrupters, providing minimum and even contact wear, long life and maximum reliability. Elastimold MVR utilizes vacuum interrupters with the following ratings: 4.5 Current & Voltage Sensing Voltage Class BIL Rating 15 kv 150 kv 27 kv 150 kv 38 kv 170 kv 4.5.1 Three current sensors are provided for protection, instrumentation, metering and are capable of accurately monitoring full fault duty and providing accurate oscillographic data up to the full interrupting rating of the unit. Three load-side voltage sensors are provided for accurate voltage measurements and loss of voltage indication. The current and load-side voltage sensors are embedded in the recloser. Integral Source-side voltage sensors can be provided as an option to provide full loop scheme automation. 4.6 Mounting Frame 4.6.1 The Elastimold MVR is provided with a corrosion resistant galvanized mounting frame for pole mounting. 4.6.2 Each mounting frame can be supplied with an optional voltage transformer for power to the control and six (6) surge arresters mounting provisions for the three-phase units (two for single-phase units). 4.6.3 Lifting lugs are provided in accordance with IEEE C37.60. 4.7 Control Cable 4.7.1 The Elastimold MVR is supplied with a standard 35 feet length UV protected cable and weatherproof connectors for assembly. Larger cable lengths are available and optional.

File: MVR-RS-0412 Page: 4 of 6 4.8 Electronics Control 5.0 RATINGS 4.8.1 The single phase Elastimold MVR is controlled and operated by the SEL 351RS-Kestrel control via a 10 pin interconnecting cable. The three phase Elastimold MVR can either by controlled directly with the SEL 651R control via a 32 pin interconnecting cable or by a SEL 351R or 351R Falcon control via a 14 pin cable connected to an MVR Power Module which then connects to the recloser. 4.8.2 The relays are SCADA ready with 9-pin serial cable connection. The controls communicate serially using DNP protocol level 2 or higher. 4.8.3 Recloser control will be provided with SEL ACSELERATOR QuickSet SEL- 5030 Software Database for ease and comprehensive logic manipulation and industry standard operating curves. 5.1 The recloser shall meet or exceed the following electrical and physical ratings: NOMINAL SYSTEM VOLTAGE RATING 15 kv 27 kv 38 kv Rated Max. Design Voltage (kv rms) 14.4 25 35 Max. Symmetrical Interrupting Capability at Max. Design Voltage 17.1 29.3 38 Nominal Frequency (Hz) 50 or 60 50 or 60 50 or 60 Phase Spacing on 3 phase units (inches) 15.5 15.5 15.5 BIL (kv) 150 150 170 Power Frequency Withstand - Dry (kv) 50 60 70 Power Frequency Withstand - Wet (kv) 45 50 60 Continuous Current (A RMS) 800 800 800 Eight (8) hour Overload Current (A RMS) 960 960 960 CT Ratio 1000 to 1 1000 to 1 1000 to 1 Interrupting Current (ka RMS Symmetrical) 12.5 12.5 12.5 Making Current (ka Asymmetrical Peak) 32.5 32.5 32.5 Creepage Distances - inches (line to ground) 41.5 41.5 51 Arc Extinction Medium Vacuum Vacuum Vacuum Insulation Medium EPDM/Silicon EPDM/Silicon EPDM/Silicon Rubber Rubber Rubber Mechanical Operations 10,000 10,000 10,000 Operating Temperatures -40ºC to 65 ºC -40ºC to 65 ºC -40ºC to 65 ºC Voltage Sensor Accuracy (Load/Line) 3% / 1% 3% / 1% 3% / 1% CT Accuracy Class 1 Class 1 Class 1 Weight (Single phase/three phase) 57/208 57/208 58/211

File: MVR-RS-0412 Page: 5 of 6 6.0 TESTS 6.1 The Elastimold MVR is tested in accordance with ANSI/IEEE C37.60, section 7 (Production Test), before shipment. Two (2) copies of certified Production Test reports are furnished to verify correctness of control wiring and proper functioning of all equipment. 7.0 NAMEPLATE 8.0 INSTALLATION Reclosers are provided with stainless steel name plate securely attached to the recloser housing containing, the following information: Manufacturers Name: Manufacturers Model Number: Manufacturers Serial Number: Control Voltage in Volts: Date of Manufacturing: Recloser Maximum Rated kv: Maximum Interrupting Rating: Purchase Order Number: Elastimold three-phase MVRs are provided with lifting points that will enable a balanced unit when lifting the unit into its operating position. Detail installation instructions are provided in Elastimold Molded Vacuum Recloser Installation Manual. 9.0 PACKAGING AND SHIPPING 9.1 Elastimold MVRs are securely banded to pallets such that in no case will the recloser tip over during normal handling. Pallets are designed to accommodate the use of a fork lift for moving and storage. Packaging will provide for outside storage with no adverse effects on the recloser or its control. 9.2 Two sets of packing list are included with each shipment along with any instructions needed to assure the proper installation and operation of the reclosers.

File: MVR-RS-0412 Page: 6 of 6 10.0 SERVICE AND MAINTENANCE AND RELIABILITY 10.1 No field calibration shall be required to maintain accuracy of the Elastimold MVR.